Device type: Active Master
Note: "A Device that responds and passes the token"
Total Messages Sent: 185
Tolal Messages Received: 130
-------------------------------------------------------------------------------
Table of Sent/Received MSTP Frames:
-------------------------------------------------------------------------------
00 Token Sent: 60 - 32
00 Token Received: 60 - 46
01 Poll For Master Sent: 54 - 29
01 Poll For Master Received: 0 - 0
02 Reply To Poll For Master Sent: 0 - 0
02 Reply To Poll For Master Received: 0 - 0
03 Test_Request Sent: 0 - 0
03 Test_Request Received: 0 - 0
04 Test_Response Sent: 0 - 0
04 Test_Response Received: 0 - 0
05 Data Expecting Reply Sent: 71 - 38
05 Data Expecting Reply Received: 0 - 0
06 Data Not Expecting Reply Sent: 0 - 0
06 Data Not Expecting Reply Received: 70 - 53
07 Reply Postponed Sent: 0 - 0
07 Reply Postponed Received: 0 - 0
-------------------------------------------------------------------------------
Table of Token time:
-------------------------------------------------------------------------------
longest shortest
Time between receiving the token : 3599403ms 65ms
Time holding the token : 3599352ms 25ms
Start at [2009-08-25 10:46:44:232] Received 60 Tokens. The Average receive time is : 900354ms. Holding time :900304ms
Device Broke a sequence!!
Note: "The device talked out of turn, it didn't have the token but it
still sent messages on the network"
Out of turn message count: 2
Time stamp of last 2 out of turn messages:
[2009-08-25 10:46:22:979]
[2009-08-25 10:46:22:991]
-------------------------------------------------------------------------------
Pdu Types Count:
-------------------------------------------------------------------------------
Recv : complex_ack_pdu : 19
Recv : error_pdu : 1
Recv : simple_ack_pdu : 4
Sent : complex_ack_pdu : 19
Sent : confirmed_request_pdu : 24
Sent : error_pdu : 1
Sent : simple_ack_pdu : 4
-------------------------------------------------------------------------------
Pdu Types by Object ID:
-------------------------------------------------------------------------------
Analog output (101)
Recv
simple_ack_pdu : 2
Sent
confirmed_request_pdu : 1
simple_ack_pdu : 2
Analog output (102)
Recv
simple_ack_pdu : 3
Sent
confirmed_request_pdu : 2
simple_ack_pdu : 2
Analog output (104)
Recv
simple_ack_pdu : 3
Sent
confirmed_request_pdu : 2
simple_ack_pdu : 2
Analog output (115)
Recv
simple_ack_pdu : 2
Sent
confirmed_request_pdu : 1
simple_ack_pdu : 2
Analog_input (200)
Recv
complex_ack_pdu : 2
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 1
Analog_input (201)
Recv
complex_ack_pdu : 2
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 1
Analog_input (202)
Recv
complex_ack_pdu : 2
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 1
Analog_input (203)
Recv
complex_ack_pdu : 2
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 1
Analog_input (232)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 4
confirmed_request_pdu : 2
Analog_input (240)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 3
confirmed_request_pdu : 2
Analog_input (241)
Recv
complex_ack_pdu : 3
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 2
Analog_input (242)
Recv
complex_ack_pdu : 5
Sent
complex_ack_pdu : 6
confirmed_request_pdu : 2
Analog_input (243)
Recv
complex_ack_pdu : 5
Sent
complex_ack_pdu : 5
confirmed_request_pdu : 2
Analog_input (244)
Recv
complex_ack_pdu : 3
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 2
Analog_input (245)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 4
confirmed_request_pdu : 2
Analog_input (247)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 4
confirmed_request_pdu : 2
Analog_input (250)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 4
confirmed_request_pdu : 2
Analog_input (253)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 4
confirmed_request_pdu : 2
Analog_input (254)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 4
confirmed_request_pdu : 2
Analog_input (277)
Recv
complex_ack_pdu : 2
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 1
Analog_input (281)
Recv
complex_ack_pdu : 4
Sent
complex_ack_pdu : 3
confirmed_request_pdu : 2
Analog_input (285)
Recv
complex_ack_pdu : 3
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 2
Binary input (100)
Recv
complex_ack_pdu : 3
Sent
complex_ack_pdu : 2
confirmed_request_pdu : 2
Device (4194303)
Recv
error_pdu : 56
Sent
confirmed_request_pdu : 32
error_pdu : 47