Device type: Active Master
Note: "A Device that responds and passes the token"
Device type: Passive Slave
Note: "A Device that respond to polls but does not part of token network"
Total Messages Sent: 107
Tolal Messages Received: 76
-------------------------------------------------------------------------------
Table of Sent/Received MSTP Frames:
-------------------------------------------------------------------------------
00 Token Sent: 60 - 56
00 Token Received: 60 - 78
01 Poll For Master Sent: 31 - 28
01 Poll For Master Received: 0 - 0
02 Reply To Poll For Master Sent: 0 - 0
02 Reply To Poll For Master Received: 0 - 0
03 Test_Request Sent: 0 - 0
03 Test_Request Received: 0 - 0
04 Test_Response Sent: 0 - 0
04 Test_Response Received: 0 - 0
05 Data Expecting Reply Sent: 0 - 0
05 Data Expecting Reply Received: 16 - 21
06 Data Not Expecting Reply Sent: 16 - 14
06 Data Not Expecting Reply Received: 0 - 0
07 Reply Postponed Sent: 0 - 0
07 Reply Postponed Received: 0 - 0
-------------------------------------------------------------------------------
Table of Token time:
-------------------------------------------------------------------------------
longest shortest
Time between receiving the token : 3599401ms 65ms
Time holding the token : 3599013ms 11ms
Start at [2009-08-25 10:46:44:271] Received 60 Tokens. The Average receive time is : 900370ms. Holding time :120001ms
Device Broke a sequence!!
Note: "The device talked out of turn, it didn't have the token but it
still sent messages on the network"
Out of turn message count: 9
[2009-08-25 10:46:26:854]
[2009-08-25 10:46:26:254]
[2009-08-25 10:46:27:055]
[2009-08-25 10:46:28:844]
[2009-08-25 10:46:29:649]
-------------------------------------------------------------------------------
Pdu Types Count:
-------------------------------------------------------------------------------
Recv : complex_ack_pdu : 19
Recv : confirmed_request_pdu : 16
Recv : error_pdu : 1
Recv : simple_ack_pdu : 4
Sent : complex_ack_pdu : 19
Sent : error_pdu : 1
Sent : simple_ack_pdu : 4
-------------------------------------------------------------------------------
Pdu Types by Object ID:
-------------------------------------------------------------------------------
Analog output (101)
Recv
simple_ack_pdu : 1
Sent
simple_ack_pdu : 2
Analog output (102)
Recv
confirmed_request_pdu : 1
simple_ack_pdu : 1
Sent
simple_ack_pdu : 3
Analog output (104)
Recv
confirmed_request_pdu : 1
simple_ack_pdu : 1
Sent
simple_ack_pdu : 3
Analog output (115)
Recv
simple_ack_pdu : 1
Sent
simple_ack_pdu : 2
Analog_input (200)
Recv
complex_ack_pdu : 1
Sent
complex_ack_pdu : 1
Analog_input (201)
Recv
complex_ack_pdu : 1
Sent
complex_ack_pdu : 1
Analog_input (202)
Recv
complex_ack_pdu : 1
Sent
complex_ack_pdu : 1
Analog_input (203)
Recv
complex_ack_pdu : 1
Sent
complex_ack_pdu : 1
Analog_input (232)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (240)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (241)
Recv
complex_ack_pdu : 1
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 3
Analog_input (242)
Recv
complex_ack_pdu : 3
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 5
Analog_input (243)
Recv
complex_ack_pdu : 3
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 6
Analog_input (244)
Recv
complex_ack_pdu : 1
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 2
Analog_input (245)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (247)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (250)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (253)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (254)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (277)
Recv
complex_ack_pdu : 1
Sent
complex_ack_pdu : 1
Analog_input (281)
Recv
complex_ack_pdu : 2
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 4
Analog_input (285)
Recv
complex_ack_pdu : 1
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 2
Binary input (100)
Recv
complex_ack_pdu : 1
confirmed_request_pdu : 1
Sent
complex_ack_pdu : 3
Device (4194303)
Recv
error_pdu : 25
Sent
error_pdu : 39