Multistack Support, Knowledge and FAQ

 

Data Sheets and Manuals

Data Sheet – FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller

Manual – FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller

FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller

FieldServer Driver Manual – Serial – FS-8705-18 – Multistack Comput25 Master Controller

Multistack – The Modular Water Chiller – Master Control User Manual

BACnet Portal Technical Manual Multistack – The Modular Water Chiller – (MS20/30/50 Application – BACnet over TCP/IP )

Multistack – The Modular Water Chiller – BACnet Portal Technical Manual (MS20/30/50 Application – BACnet over TCP/IP Heat Pump)
More Data Sheets

Points List

This points list may change when firmware is updated or the device is configured differently. Contact us to check for the lastest points list.

 

Water Cooler Chiller

Map_Descriptor_Name Data_Type Address Function Units
num_of_compressors Av 001 Server No_Units
capacity Av 002 Server No_Units
demand Av 003 Server No_Units
current_faults Av 004 Server No_Units
echw_sys_temp Av 005 Server No_Units
lchw_sys_temp Av 006 Server No_Units
ecw_sys_temp Av 007 Server No_Units
lcw_sys_temp Av 008 Server No_Units
lead_comp_read Av 009 Server No_Units
load_limit_read Av 010 Server No_Units
upsetpt_read Av 011 Server No_Units
lowsetpt_read Av 012 Server No_Units
vsp_read Av 013 Server No_Units
tdiff_read Av 014 Server No_Units
fail_indic_read Av 015 Server No_Units
flush_time_read Av 016 Server No_Units
flush_duration_read Av 017 Server No_Units
month Av 018 Server No_Units
day Av 019 Server No_Units
year Av 020 Server No_Units
hour Av 021 Server No_Units
minute Av 022 Server No_Units
faults_c1 Av 023 Server No_Units
faults_c2 Av 024 Server No_Units
faults_c3 Av 025 Server No_Units
faults_c4 Av 026 Server No_Units
faults_c5 Av 027 Server No_Units
faults_c6 Av 028 Server No_Units
faults_c7 Av 029 Server No_Units
faults_c8 Av 030 Server No_Units
faults_c9 Av 031 Server No_Units
faults_c10 Av 032 Server No_Units
faults_c11 Av 033 Server No_Units
faults_c12 Av 034 Server No_Units
faults_c13 Av 035 Server No_Units
faults_c14 Av 036 Server No_Units
faults_c15 Av 037 Server No_Units
faults_c16 Av 038 Server No_Units
faults_c17 Av 039 Server No_Units
faults_c18 Av 040 Server No_Units
faults_c19 Av 041 Server No_Units
faults_c20 Av 042 Server No_Units
faults_c21 Av 043 Server No_Units
faults_c22 Av 044 Server No_Units
faults_c23 Av 045 Server No_Units
faults_c24 Av 046 Server No_Units
c1_suct_temp Av 047 Server No_Units
c1_lchw_temp Av 048 Server No_Units
c2_suct_temp Av 049 Server No_Units
c2_lchw_temp Av 050 Server No_Units
c3_suct_temp Av 051 Server No_Units
c3_lchw_temp Av 052 Server No_Units
c4_suct_temp Av 053 Server No_Units
c4_lchw_temp Av 054 Server No_Units
c5_suct_temp Av 055 Server No_Units
c5_lchw_temp Av 056 Server No_Units
c6_suct_temp Av 057 Server No_Units
c6_lchw_temp Av 058 Server No_Units
c7_suct_temp Av 059 Server No_Units
c7_lchw_temp Av 060 Server No_Units
c8_suct_temp Av 061 Server No_Units
c8_lchw_temp Av 062 Server No_Units
c9_suct_temp Av 063 Server No_Units
c9_lchw_temp Av 064 Server No_Units
c10_suct_temp Av 065 Server No_Units
c10_lchw_temp Av 066 Server No_Units
c11_suct_temp Av 067 Server No_Units
c11_lchw_temp Av 068 Server No_Units
c12_suct_temp Av 069 Server No_Units
c12_lchw_temp Av 070 Server No_Units
c13_suct_temp Av 071 Server No_Units
c13_lchw_temp Av 072 Server No_Units
c14_suct_temp Av 073 Server No_Units
c14_lchw_temp Av 074 Server No_Units
c15_suct_temp Av 075 Server No_Units
c15_lchw_temp Av 076 Server No_Units
c16_suct_temp Av 077 Server No_Units
c16_lchw_temp Av 078 Server No_Units
c17_suct_temp Av 079 Server No_Units
c17_lchw_temp Av 080 Server No_Units
c18_suct_temp Av 081 Server No_Units
c18_lchw_temp Av 082 Server No_Units
c19_suct_temp Av 083 Server No_Units
c19_lchw_temp Av 084 Server No_Units
c20_suct_temp Av 085 Server No_Units
c20_lchw_temp Av 086 Server No_Units
c21_suct_temp Av 087 Server No_Units
c21_lchw_temp Av 088 Server No_Units
c22_suct_temp Av 089 Server No_Units
c22_lchw_temp Av 090 Server No_Units
c23_suct_temp Av 091 Server No_Units
c23_lchw_temp Av 092 Server No_Units
c24_suct_temp Av 093 Server No_Units
c24_lchw_temp Av 094 Server No_Units
fault_1_type Av 095 Server No_Units
fault_2_type Av 096 Server No_Units
fault_3_type Av 097 Server No_Units
fault_4_type Av 098 Server No_Units
fault_5_type Av 099 Server No_Units
fault_6_type Av 100 Server No_Units
fault_7_type Av 101 Server No_Units
fault_8_type Av 102 Server No_Units
fault_9_type Av 103 Server No_Units
fault_10_type Av 104 Server No_Units
fault_11_type Av 105 Server No_Units
fault_12_type Av 106 Server No_Units
fault_13_type Av 107 Server No_Units
fault_14_type Av 108 Server No_Units
fault_15_type Av 109 Server No_Units
fault_16_type Av 110 Server No_Units
fault_17_type Av 111 Server No_Units
fault_18_type Av 112 Server No_Units
fault_19_type Av 113 Server No_Units
fault_20_type Av 114 Server No_Units
fault_1_comp Av 115 Server No_Units
fault_2_comp Av 116 Server No_Units
fault_3_comp Av 117 Server No_Units
fault_4_comp Av 118 Server No_Units
fault_5_comp Av 119 Server No_Units
fault_6_comp Av 120 Server No_Units
fault_7_comp Av 121 Server No_Units
fault_8_comp Av 122 Server No_Units
fault_9_comp Av 123 Server No_Units
fault_10_comp Av 124 Server No_Units
fault_11_comp Av 125 Server No_Units
fault_12_comp Av 126 Server No_Units
fault_13_comp Av 127 Server No_Units
fault_14_comp Av 128 Server No_Units
fault_15_comp Av 129 Server No_Units
fault_16_comp Av 130 Server No_Units
fault_17_comp Av 131 Server No_Units
fault_18_comp Av 132 Server No_Units
fault_19_comp Av 133 Server No_Units
fault_20_comp Av 134 Server No_Units
upsetpt_write Av 135 Server No_Units
lowsetpt_write Av 136 Server No_Units
vsp_write Av 137 Server No_Units
load_limit_write Av 138 Server No_Units
tdiff_write Av 139 Server No_Units
fail_indic_write Av 140 Server No_Units
lead_comp_write Av 141 Server No_Units
flush_time_write Av 142 Server No_Units
flush_duration_write Av 143 Server No_Units
LP0HR – HRS 144rating 00-144 Av 144 Server No_Units
LP1HR – HRS 145rating 10-145 Av 145 Server No_Units
LP2HR – HRS 146rating 20-146 Av 146 Server No_Units
LP3HR – HRS 147rating 30-147 Av 147 Server No_Units
LP4HR – HRS 148rating 40-148 Av 148 Server No_Units
LP5HR – HRS 149rating 50-149 Av 149 Server No_Units
LP6HR – HRS 150rating 60-150 Av 150 Server No_Units
LP7HR – HRS 151rating 70-151 Av 151 Server No_Units
LP8HR – HRS 152rating 80-152 Av 152 Server No_Units
LP9HR – HRS 153rating 90-153 Av 153 Server No_Units
most_crnt_flt Av 154 Server No_Units
on_off_ctrl_read Bv 001 Server
ex1_fault Bv 002 Server
remote_on_off Bv 003 Server
ex3_fault Bv 004 Server
ex4_fault Bv 005 Server
low_chw_flow Bv 006 Server
low_cw_flow Bv 007 Server
low_chw_temp Bv 008 Server
c1_status Bv 009 Server
c2_status Bv 010 Server
c3_status Bv 011 Server
c4_status Bv 012 Server
c5_status Bv 013 Server
c6_status Bv 014 Server
c7_status Bv 015 Server
c8_status Bv 016 Server
c9_status Bv 017 Server
c10_status Bv 018 Server
c11_status Bv 019 Server
c12_status Bv 020 Server
c13_status Bv 021 Server
c14_status Bv 022 Server
c15_status Bv 023 Server
c16_status Bv 024 Server
c17_status Bv 025 Server
c18_status Bv 026 Server
c19_status Bv 027 Server
c20_status Bv 028 Server
c21_status Bv 029 Server
c22_status Bv 030 Server
c23_status Bv 031 Server
c24_status Bv 032 Server
on_off_ctrl_write Bv 033 Server

 

Heat Pumps

Map_Descriptor_Name Data_Type Address Function Units
CAPACITY Av 001 SERVER No_Units
DEMAND Av 002 SERVER No_Units
NUMBER OF COMPS Av 003 SERVER No_Units
CURRENT FAULTS Av 004 SERVER No_Units
OPERATING MODE Av 005 SERVER No_Units
ENT LOAD TEMP Av 006 SERVER No_Units
LEV LOAD TEMP Av 007 SERVER No_Units
ENT SOURCE TEMP Av 008 SERVER No_Units
LEV SOURCE TEMP Av 009 SERVER No_Units
COOL UPSETPT Av 010 SERVER No_Units
COOL LOWSETPT Av 011 SERVER No_Units
COOL VSP Av 012 SERVER No_Units
COOL TDIFF Av 013 SERVER No_Units
HEAT UPSETPT Av 014 SERVER No_Units
HEAT LOWSETPT Av 015 SERVER No_Units
HEAT VSP Av 016 SERVER No_Units
HEAT TDIFF Av 017 SERVER No_Units
LOAD LIMIT Av 018 SERVER No_Units
FAIL INDICATOR Av 019 SERVER No_Units
LEAD COMPRESSOR Av 020 SERVER No_Units
FLUSH TIME Av 021 SERVER No_Units
FLUSH DURATION Av 022 SERVER No_Units
MONTH Av 023 SERVER No_Units
DAY Av 024 SERVER No_Units
YEAR Av 025 SERVER No_Units
HOUR Av 026 SERVER No_Units
MINUTE Av 027 SERVER No_Units
C1 SUCTION TEMP Av 028 SERVER No_Units
C1 LLW TEMP Av 029 SERVER No_Units
C1 LSW TEMP Av 030 SERVER No_Units
C2 SUCTION TEMP Av 031 SERVER No_Units
C2 LLW TEMP Av 032 SERVER No_Units
C2 LSW TEMP Av 033 SERVER No_Units
C3 SUCTION TEMP Av 034 SERVER No_Units
C3 LLW TEMP Av 035 SERVER No_Units
C3 LSW TEMP Av 036 SERVER No_Units
C4 SUCTION TEMP Av 037 SERVER No_Units
C4 LLW TEMP Av 038 SERVER No_Units
C4 LSW TEMP Av 039 SERVER No_Units
C5 SUCTION TEMP Av 040 SERVER No_Units
C5 LLW TEMP Av 041 SERVER No_Units
C5 LSW TEMP Av 042 SERVER No_Units
C6 SUCTION TEMP Av 043 SERVER No_Units
C6 LLW TEMP Av 044 SERVER No_Units
C6 LSW TEMP Av 045 SERVER No_Units
C7 SUCTION TEMP Av 046 SERVER No_Units
C7 LLW TEMP Av 047 SERVER No_Units
C7 LSW TEMP Av 048 SERVER No_Units
C8 SUCTION TEMP Av 049 SERVER No_Units
C8 LLW TEMP Av 050 SERVER No_Units
C8 LSW TEMP Av 051 SERVER No_Units
C9 SUCTION TEMP Av 052 SERVER No_Units
C9 LLW TEMP Av 053 SERVER No_Units
C9 LSW TEMP Av 054 SERVER No_Units
C10 SUCTION TEMP Av 055 SERVER No_Units
C10 LLW TEMP Av 056 SERVER No_Units
C10 LSW TEMP Av 057 SERVER No_Units
C11 SUCTION TEMP Av 058 SERVER No_Units
C11 LLW TEMP Av 059 SERVER No_Units
C11 LSW TEMP Av 060 SERVER No_Units
C12 SUCTION TEMP Av 061 SERVER No_Units
C12 LLW TEMP Av 062 SERVER No_Units
C12 LSW TEMP Av 063 SERVER No_Units
C13 SUCTION TEMP Av 064 SERVER No_Units
C13 LLW TEMP Av 065 SERVER No_Units
C13 LSW TEMP Av 066 SERVER No_Units
C14 SUCTION TEMP Av 067 SERVER No_Units
C14 LLW TEMP Av 068 SERVER No_Units
C14 LSW TEMP Av 069 SERVER No_Units
C15 SUCTION TEMP Av 070 SERVER No_Units
C15 LLW TEMP Av 071 SERVER No_Units
C15 LSW TEMP Av 072 SERVER No_Units
C16 SUCTION TEMP Av 073 SERVER No_Units
C16 LLW TEMP Av 074 SERVER No_Units
C16 LSW TEMP Av 075 SERVER No_Units
C17 SUCTION TEMP Av 076 SERVER No_Units
C17 LLW TEMP Av 077 SERVER No_Units
C17 LSW TEMP Av 078 SERVER No_Units
C18 SUCTION TEMP Av 079 SERVER No_Units
C18 LLW TEMP Av 080 SERVER No_Units
C18 LSW TEMP Av 081 SERVER No_Units
C19 SUCTION TEMP Av 082 SERVER No_Units
C19 LLW TEMP Av 083 SERVER No_Units
C19 LSW TEMP Av 084 SERVER No_Units
C20 SUCTION TEMP Av 085 SERVER No_Units
C20 LLW TEMP Av 086 SERVER No_Units
C20 LSW TEMP Av 087 SERVER No_Units
C21 SUCTION TEMP Av 088 SERVER No_Units
C21 LLW TEMP Av 089 SERVER No_Units
C21 LSW TEMP Av 090 SERVER No_Units
C22 SUCTION TEMP Av 091 SERVER No_Units
C22 LLW TEMP Av 092 SERVER No_Units
C22 LSW TEMP Av 093 SERVER No_Units
C23 SUCTION TEMP Av 094 SERVER No_Units
C23 LLW TEMP Av 095 SERVER No_Units
C23 LSW TEMP Av 096 SERVER No_Units
C24 SUCTION TEMP Av 097 SERVER No_Units
C24 LLW TEMP Av 098 SERVER No_Units
C24 LSW TEMP Av 099 SERVER No_Units
C1 FAULTS Av 100 SERVER No_Units
C2 FAULTS Av 101 SERVER No_Units
C3 FAULTS Av 102 SERVER No_Units
C4 FAULTS Av 103 SERVER No_Units
C5 FAULTS Av 104 SERVER No_Units
C6 FAULTS Av 105 SERVER No_Units
C7 FAULTS Av 106 SERVER No_Units
C8 FAULTS Av 107 SERVER No_Units
C9 FAULTS Av 108 SERVER No_Units
C10 FAULTS Av 109 SERVER No_Units
C11 FAULTS Av 110 SERVER No_Units
C12 FAULTS Av 111 SERVER No_Units
C13 FAULTS Av 112 SERVER No_Units
C14 FAULTS Av 113 SERVER No_Units
C15 FAULTS Av 114 SERVER No_Units
C16 FAULTS Av 115 SERVER No_Units
C17 FAULTS Av 116 SERVER No_Units
C18 FAULTS Av 117 SERVER No_Units
C19 FAULTS Av 118 SERVER No_Units
C20 FAULTS Av 119 SERVER No_Units
C21 FAULTS Av 120 SERVER No_Units
C22 FAULTS Av 121 SERVER No_Units
C23 FAULTS Av 122 SERVER No_Units
C24 FAULTS Av 123 SERVER No_Units
FAULT 1 COMP # Av 124 SERVER No_Units
FAULT 2 COMP # Av 125 SERVER No_Units
FAULT 3 COMP # Av 126 SERVER No_Units
FAULT 4 COMP # Av 127 SERVER No_Units
FAULT 5 COMP # Av 128 SERVER No_Units
FAULT 6 COMP # Av 129 SERVER No_Units
FAULT 7 COMP # Av 130 SERVER No_Units
FAULT 8 COMP # Av 131 SERVER No_Units
FAULT 9 COMP # Av 132 SERVER No_Units
FAULT 10 COMP # Av 133 SERVER No_Units
FAULT 11 COMP # Av 134 SERVER No_Units
FAULT 12 COMP # Av 135 SERVER No_Units
FAULT 13 COMP # Av 136 SERVER No_Units
FAULT 14 COMP # Av 137 SERVER No_Units
FAULT 15 COMP # Av 138 SERVER No_Units
FAULT 16 COMP # Av 139 SERVER No_Units
FAULT 17 COMP # Av 140 SERVER No_Units
FAULT 18 COMP # Av 141 SERVER No_Units
FAULT 19 COMP # Av 142 SERVER No_Units
FAULT 20 COMP # Av 143 SERVER No_Units
FAULT 1 TYPE Av 144 SERVER No_Units
FAULT 2 TYPE Av 145 SERVER No_Units
FAULT 3 TYPE Av 146 SERVER No_Units
FAULT 4 TYPE Av 147 SERVER No_Units
FAULT 5 TYPE Av 148 SERVER No_Units
FAULT 6 TYPE Av 149 SERVER No_Units
FAULT 7 TYPE Av 150 SERVER No_Units
FAULT 8 TYPE Av 151 SERVER No_Units
FAULT 9 TYPE Av 152 SERVER No_Units
FAULT 10 TYPE Av 153 SERVER No_Units
FAULT 11 TYPE Av 154 SERVER No_Units
FAULT 12 TYPE Av 155 SERVER No_Units
FAULT 13 TYPE Av 156 SERVER No_Units
FAULT 14 TYPE Av 157 SERVER No_Units
FAULT 15 TYPE Av 158 SERVER No_Units
FAULT 16 TYPE Av 159 SERVER No_Units
FAULT 17 TYPE Av 160 SERVER No_Units
FAULT 18 TYPE Av 161 SERVER No_Units
FAULT 19 TYPE Av 162 SERVER No_Units
FAULT 20 TYPE Av 163 SERVER No_Units
LP0HR – HRS Cooling -00-09 aV 164 Server No_Units
LP1HR – HRS Cooling -10-19 aV 165 Server No_Units
LP2HR – HRS Cooling -20-29 aV 166 Server No_Units
LP3HR – HRS Cooling -30-39 aV 167 Server No_Units
LP4HR – HRS Cooling -40-49 aV 168 Server No_Units
LP5HR – HRS Cooling -50-59 aV 169 Server No_Units
LP6HR – HRS Cooling -60-69 aV 170 Server No_Units
LP7HR – HRS Cooling -70-79 aV 171 Server No_Units
LP8HR – HRS Cooling -80-89 aV 172 Server No_Units
LP9HR – HRS Cooling -90-100 aV 173 Server No_Units
HLP0HR – HRS Heating – 0-9 aV 174 Server No_Units
HLP1HR – HRS Heating – 10-19 aV 175 Server No_Units
HLP2HR – HRS Heating – 20-29 aV 176 Server No_Units
HLP3HR – HRS Heating – 30-39 aV 177 Server No_Units
HLP4HR – HRS Heating – 40-49 aV 178 Server No_Units
HLP5HR – HRS Heating – 50-59 aV 179 Server No_Units
HLP6HR – HRS Heating – 60-69 aV 180 Server No_Units
HLP7HR – HRS Heating – 70-79 aV 181 Server No_Units
HLP8HR – HRS Heating – 80-89 aV 182 Server No_Units
HLP9HR – HRS Heating – 90-100 aV 183 Server No_Units
COOL UPSETPT Av 184 SERVER No_Units
COOL LOWSETPT Av 185 SERVER No_Units
COOL VSP Av 186 SERVER No_Units
COOL TDIFF Av 187 SERVER No_Units
HEAT UPSETPT Av 188 SERVER No_Units
HEAT LOWSETPT Av 189 SERVER No_Units
HEAT VSP Av 190 SERVER No_Units
HEAT TDIFF Av 191 SERVER No_Units
LOAD LIMIT Av 192 SERVER No_Units
FAIL INDICATOR Av 193 SERVER No_Units
LEAD COMPRESSOR Av 194 SERVER No_Units
FLUSH TIME Av 195 SERVER No_Units
FLUSH DURATION Av 196 SERVER No_Units
OPERATING MODE Av 197 SERVER No_Units
MOST CURRENT FLT Av 198 SERVER No_Units
HEAT DELAY (READ) Av 199 SERVER No_Units
HEAT DELAY (wRITE) Av 200 SERVER No_Units
on_off_ctrl_read Bv 001 Server
ex1_fault Bv 002 Server
remote_on_off Bv 003 Server
ex3_fault Bv 004 Server
ex4_fault Bv 005 Server
low_chw_flow Bv 006 Server
low_cw_flow Bv 007 Server
LOW LLW TEMP Bv 008 Server
LOW LSW TEMP Bv 009 Server
c1_status Bv 010 Server
c2_status Bv 011 Server
c3_status Bv 012 Server
c4_status Bv 013 Server
c5_status Bv 014 Server
c6_status Bv 015 Server
c7_status Bv 016 Server
c8_status Bv 017 Server
c9_status Bv 018 Server
c10_status Bv 019 Server
c11_status Bv 020 Server
c12_status Bv 021 Server
c13_status Bv 022 Server
c14_status Bv 023 Server
c15_status Bv 024 Server
c16_status Bv 025 Server
c17_status Bv 026 Server
c18_status Bv 027 Server
c19_status Bv 028 Server
c20_status Bv 029 Server
c21_status Bv 030 Server
c22_status Bv 031 Server
c23_status Bv 032 Server
c24_status Bv 033 Server
on_off_ctrl_write Bv 034 Server

 

 