EMCP 3.1, 3.2, and 3.3 Modbus Memory Map

We may be able to provide you with the complete manual. Email us and ask.

102 GENERATOR
AVERAGE AC RMS FREQUENCY
1
REGISTER (2 BYTES) LONG
READ Average AC frequency measured at the generator output. 1/128 Hz
/ bit
0 Hz 0 to
501.9922 Hz
100 GENERATOR
AVERAGE LINE-LINE AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Average Line to Line RMS voltage measured at the
generator output.
1 V / bit 0 V 0 to
64255 V
163 GENERATOR
AVERAGE LINE-LINE AC RMS VOLTAGE PERCENT
1
REGISTER (2 BYTES) LONG
READ Average Line to Line RMS voltage at the generator, as a
percentage of nominal generator voltage.
0.0078125
% / bit
-251.00% -251 to
250.99%
108 GENERATOR
PHASE A LINE-LINE AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Line to Line RMS voltage measured at the generator
phase AB output.
1 V / bit 0 V 0 to
64255 V
109 GENERATOR
PHASE B LINE-LINE AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Line to Line RMS voltage measured at the generator
phase BC output.
1 V / bit 0 V 0 to
64255 V
110 GENERATOR
PHASE C LINE-LINE AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Line to Line RMS voltage measured at the generator
phase CA output.
1 V / bit 0 V 0 to
64255 V
148 GENERATOR
AVERAGE LINE-NEUTRAL AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ The average Line to Neutral AC RMS voltage measured at
the generator output.
1 V / bit 0 V 0 to
64255 V
114 GENERATOR
PHASE A LINE-NEUTRAL AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Line to Neutral RMS voltage measured at the generator
phase A output.
1 V / bit 0 V 0 to
64255 V
115 GENERATOR
PHASE B LINE-NEUTRAL AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Line to Neutral RMS voltage measured at the generator
phase B output.
1 V / bit 0 V 0 to
64255 V
116 GENERATOR
PHASE C LINE-NEUTRAL AC RMS VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Line to Neutral RMS voltage measured at the generator
phase C output.
1 V / bit 0 V 0 to
64255 V
101 GENERATOR
AVERAGE AC RMS CURRENT
1
REGISTER (2 BYTES) LONG
READ Average RMS current measured at the generator output. 1 A / bit 0 A 0 to
64255 V
111 GENERATOR
PHASE A AC RMS CURRENT
1
REGISTER (2 BYTES) LONG
READ RMS current measured at the generator phase A output. 1 A / bit 0 A 0 to
64255 V
112 GENERATOR
PHASE B AC RMS CURRENT
1
REGISTER (2 BYTES) LONG
READ RMS current measured at the generator phase B output. 1 A / bit 0 A 0 to
64255 V
113 GENERATOR
PHASE C AC RMS CURRENT
1
REGISTER (2 BYTES) LONG
READ RMS current measured at the generator phase C output. 1 A / bit 0 A 0 to
64255 V
103 GENERATOR
OVERALL POWER FACTOR
1
REGISTER (2 BYTES) LONG
READ The average power factor of the generator. See APPENDIX
A for a programming example.
1/16384
/ bit
-1.0 -1.0 to
1.0
104 GENERATOR
OVERALL POWER FACTOR LAGGING
1
REGISTER (2 BYTES) LONG
READ Lead/lag status for generator average power factor. 00 =
Power factor leading
01 =
Power factor lagging
10 =
Error
11 = Not
available
105 GENERATOR
TOTAL PERCENT KW
1
REGISTER (2 BYTES) LONG
READ Total real power delivered by the generator, as a
percentage of generator rated power.
0.0078125
% / bit
-251.00% -251 to
250.99 %
106 GENERATOR
TOTAL REAL POWER
2
REGISTERS (4 BYTES) LONG
READ Total real power delivered by the generator. 1 W / bit -2000000000
W
-2000000000
to +2211081215W
117 GENERATOR
PHASE A REAL POWER
2
REGISTERS (4 BYTES) LONG
READ The real power delivered by phase A of the generator. 1 W / bit -2000000000
W
-2000000000
to +2211081215W
119 GENERATOR
PHASE B REAL POWER
2
REGISTERS (4 BYTES) LONG
READ The real power delivered by phase B of the generator. 1 W / bit -2000000000
W
-2000000000
to +2211081215W
121 GENERATOR
PHASE C REAL POWER
2
REGISTERS (4 BYTES) LONG
READ The real power delivered by phase C of the generator. 1 W / bit -2000000000
W
-2000000000
to +2211081215W
123 GENERATOR
PHASE A APPARENT POWER
2
REGISTERS (4 BYTES) LONG
READ The apparent power delivered by phase A of the
generator.
1 VA /
bit
-2000000000
VA
-2000000000
to +2211081215VA
125 GENERATOR
PHASE B APPARENT POWER
2
REGISTERS (4 BYTES) LONG
READ The apparent power delivered by phase B of the
generator.
1 VA /
bit
-2000000000
VA
-2000000000
to +2211081215VA
127 GENERATOR
PHASE C APPARENT POWER
2
REGISTERS (4 BYTES) LONG
READ The apparent power delivered by phase C of the
generator.
1 VA /
bit
-2000000000
VA
-2000000000
to +2211081215VA
129 GENERATOR
PHASE A REACTIVE POWER
2
REGISTERS (4 BYTES) LONG
READ The reactive power delivered by phase A of the
generator.
1 VAr /
bit
-2000000000
VAr
-2000000000
to +2211081215VAr
131 GENERATOR
PHASE B REACTIVE POWER
2
REGISTERS (4 BYTES) LONG
READ The reactive power delivered by phase B of the
generator.
1 VAr /
bit
-2000000000
VAr
-2000000000
to +2211081215VAr
133 GENERATOR
PHASE C REACTIVE POWER
2
REGISTERS (4 BYTES) LONG
READ The reactive power delivered by phase C of the
generator.
1 VAr /
bit
-2000000000
VAr
-2000000000
to +2211081215VAr
135 GENERATOR
PHASE A POWER FACTOR
1
REGISTER (2 BYTES) LONG
READ The power factor of phase A of the generator. 1/16384
/ bit
-1.0 -1.0 to
1.0
136 GENERATOR
PHASE B POWER FACTOR
1
REGISTER (2 BYTES) LONG
READ The power factor of phase B of the generator. 1/16384
/ bit
-1.0 -1.0 to
1.0
137 GENERATOR
PHASE C POWER FACTOR
1
REGISTER (2 BYTES) LONG
READ The power factor of phase C of the generator. 1/16384
/ bit
-1.0 -1.0 to
1.0
138 GENERATOR
TOTAL APPARENT POWER
2
REGISTERS (4 BYTES) LONG
READ The total apparent power delivered by the generator. 1 VA /
bit
-2000000000
VA
-2000000000
to +2211081215VA
140 GENERATOR
TOTAL PERCENT KVA
1
REGISTER (2 BYTES) LONG
READ The total apparent power delivered by the generator, as a percentage of generator rated apparent power. 0.0078125
% / bit
-251.00% -251 to
250.99 %
141 GENERATOR
TOTAL REACTIVE POWER
2
REGISTERS (4 BYTES) LONG
READ The total reactive power delivered by the generator. 1 VAr /
bit
-2000000000
VAr
-2000000000
to +2211081215VAr
143 GENERATOR
TOTAL PERCENT KVAR
1
REGISTER (2 BYTES) LONG
READ The total reactive power delivered by the generator, as
a percentage of generator rated reactive power.
0.0078125
% / bit
-251.00% -251 to
250.99 %
144 GENERATOR
TOTAL KW HOURS EXPORT
2
REGISTERS (4 BYTES) LONG
READ The total kilowatt-hours that have been exported by the
generator.
1 kWh /
bit
0 kWh 0 to
4211081215kWh
146 GENERATOR
TOTAL KVAR HOURS EXPORT
2
REGISTERS (4 BYTES) LONG
READ The total kilovar-hours that have been exported by the
generator.
1 kVArh
/ bit
0 kVArh 0 to
4211081215kVArh
159 GENERATOR
PHASE A POWER FACTOR LAGGING
1
REGISTER (2 BYTES) LONG
READ Lead/lag status for generator phase A power factor. 00 =
Power factor leading
01 =
Power factor lagging
10 =
Error
11 = Not
available
160 GENERATOR
PHASE B POWER FACTOR LAGGING
1
REGISTER (2 BYTES) LONG
READ Lead/lag status for generator phase B power factor. 00 =
Power factor leading
01 =
Power factor lagging
10 =
Error
11 = Not
available
161 GENERATOR
PHASE C POWER FACTOR LAGGING
1
REGISTER (2 BYTES) LONG
READ Lead/lag status for generator phase C power factor. 00 =
Power factor leading
01 =
Power factor lagging
10 =
Error
11 = Not
available
1057 DESIRED
GENSET OUTPUT VOLTAGE
1
REGISTER (2 BYTES) LONG
READ Applies to EMCP 3.3 only. The desired RMS voltage to be
delivered by the genset.
1 V / bit 0 V 0 to
64255 V
1067 GENERATOR
FREQUENCY WITHIN LIMITS
1
REGISTER (2 BYTES) LONG
READ Indicates whether the generator frequency is below the threshold for a generator over frequency shutdown and above the threshold for a generator under frequency shutdown. 00 =
FALSE
01 = TRUE
1068 GENERATOR
VOLTAGE WITHIN LIMITS
1
REGISTER (2 BYTES) LONG
READ Indicates whether the generator voltage is below the threshold for a generator over voltage shutdown and above the threshold for a generator under voltage shutdown. 00 =
FALSE
01 = TRUE

 

FAQ

Q:Having problems trying to establish the caterpillar Node ID, set the Node_ID to 0 in the
configuration?

A:Watch the error screen on reboot – the remote device will usually send a
message back with an error stating that it cannot accept a response message from a certain
Node ID. That Node ID is the relevant Node ID.

The FieldServer cannot be connected directly to the generator/engine controller but must be
connected via the CCM module.
 
 
Q:What is Caterpillar CATM5X Protocol Driver?
A:The Caterpillar M5X driver allows the FieldServer to transfer data to and from devices over RS-
232 using Caterpillar M5X protocol. The FieldServer can emulate either a Server or Client. The
driver is capable of communications with any device that uses the Caterpillar M5X protocol but
has been designed primarily for connection to a Caterpillar CCM which is in turn connected to
the Caterpillar engines to be monitored/controlled.

The driver provides a limited set of M5X protocol commands and may address a sub-set of the
parameters available in each device. The driver provides formal support for 3500 engines and
EMCPII devices only. Other devices may be polled using the address of the parameter required
as opposed to user friendly parameter names.

  

Q:FieldServer Driver – Serial-A communications interface solution for Caterpillar
A:The Caterpillar CATM5X driver can act as a Master. Any Caterpillar device supporting the CATM5X protocol on any serial port (P1-P8, R1 & R2) can be polled. Typically the Caterpillar engines are connected to a CCM module and the driver connects to the CMM module. Parameters to be polled can be specified by a descriptive keyword such as “ECM Hourmeter” or by specifying the Caterpillar PID (parameter ID). Parameters to be polled can be specified by the PID numbers allowing this driver to access parameters not defined at the time of development. The driver can login to the Caterpillar CCM module it is connected to. The driver can connect at other standard baud rate/bit settings provided that the Caterpillar CATM5X device supports them. The Caterpillar driver can act as a server. The driver can be polled by a Caterpillar CATM5X Master and return data from the FieldServer’s data arrays.

 