QuickServer – BACnet/IP to Modbus RTU

FS-QS-1010-0104 QuickServer – BACnet/IP – Modbus RTU

The FS-QS-1010-0104 QuickServer provides a cost-effective, easy to use interface from BACnet/IP to Modbus RTU. The QuickServer is delivered with both drivers preloaded and ready to be configured using the provided instructions and software.

 

QuickServer Key Features:

  • BACnet Testing Laboratory (BTL) Mark
  • Ability to interface up to 250 points of common BAS protocols
  • Multi-configuration capability; specific configurations selectable via DIP switches or software
  • Flat panel mount standard, DIN rail mount option
  • DIP switches to select baud rate or node ID on the fly

BACnet/IP driver:

  • Driver type: Client or Server
  • Data Link layer: BACnet IP, (Annex J)
  • Connection type: BACnet/IP Internet Protocol (IP), 10/100BaseT, BBMD supported
  • BACnet COV support for fast data communication while reducing traffic over a BACnet network
  • Data types supported:
    • AI – Analog Input Object
    • AO – Analog Output Object
    • AV – Analog Value Object
    • BI – Binary Input Object
    • BO – Binary Output Object
    • BV – Binary Value Object
    • MI – Multi-state Input Object
    • MO – Multi-state Output Object
    • MV – Multi-state Value Object

Modbus RTU driver:

  • Driver type: Client or Server
  • Connection type: RS-232 or RS-485 (Two-wire, Half-Duplex)
  • Baud rate: 110 – 115200, standard baud rates only
  • Commands supported:
    • 01 – Read Discrete Output Status (0xxxx)
    • 02 – Read Discrete Input Status ((1xxxx)
    • 03 – Read Output Registers (4xxxx)
    • 04 – Read Input Registers (3xxxx)
    • 05 – Force Single Coil (0xxxx)
    • 06 – Preset Single Register (4xxxx)
    • 15 – Force Multiple Coils (0xxxx)
    • 16 – Preset Multiple Registers (4xxxx)

 

Block Diagram