Configuration Sample 1

FSb0228 – Project Notes – MSTP to N2

 

Please read this document to completion. It has important info.

We will make any changes necessary and email you a revised configuration. Simply ask us. You do not need make changes yourself if you do not feel comfortable.

 

Steps to completion

1. Prep for site by downloading and installing relevant test tools – see section.
2. Review this doc and check your field settings correspond to the way the gateway has been configured. Changes may be required.
3. Install and connect field wiring
4. Do some testing.


 

Prep for site

 

Download and install the FieldServer utilities from this page:
http://www.fieldserver.com/techsupport/technicalsupport.php
Download, install and activate the CAS BACnet Explorer from this page.
http://www.chipkin.com/technical-resources/cas-bacnet-explorer/

 

IP Allocation

192.168.1.168

 

Port Allocation

Serial 1 : MSTP for chiller
Serial 2: N2 Open Server

 

Settings – MSTP

FieldServer MAC Address = 11

 

This is where this is set in the configuration file
Bridge
Title ,System_station_address,
Ref=FSb0228 Rev=1.00 ,11 ,

 

Wiring MSTP

 

Settings N2

N2 Device Address is set with the Node_ID below. Use the address allocated or change the address by changing the configuration.

 

 

Wiring N2

 

N2 Map and Data objects

 

 

N2 Data Object
MODE Control Mode AO-01
STATUS Run Status AO-02
T_START Start Inhibit Timer AO-03
SYS_ALM System Alert/Alarm AO-04
T_RESET Temperature Reset AO-05
LCW_STPT Control Point AO-06
CHW_TMP Chilled Water Temp AO-07
DEM_LIM Active Demand Limit AO-08
LNAMPS_P Percent Line Current AO-09
LINEKW_P Percent Line Kilowatts AO-10
AUTO_DEM Auto Demand Limit Input AO-11
AUTO_RES Auto Chilled Water Reset AO-12
R_RESET Remote Reset Sensor AO-13
C_STARTS Total Compressor Starts AO-14
STARTS Starts in 12 Hours AO-15
C_HRS Compressor Ontime AO-16
S_HRS Service Ontime AO-17
VFD_OUT Target VFD Speed AO-18
VFD_OUT Target VFD Speed AO-19
GV_POS Actual Guide Vane Pos AO-20
GV_POS Actual Guide Vane Pos AO-21
DIFF_ACT Diffuser Actuator AO-22
CRT Condenser Refrig Temp AO-23
ERT Calc Evap Sat Temp AO-24
CDW_DT Active Delta Tsat AO-25
DELTA_TX Surge Line Delta Tsat AO-26
DELTATXF Calculated Delta Txfs AO-27
CHW_DT Chilled Water Delta T AO-28
SP_HIGH Surge Line High Offset AO-29
DTsatmin Surge/HGBP Delta Tsmin AO-30
GV_MIN Surge/HGBP IGVmin AO-31
DTsatmax Surge/HGBP Delta Tsmax AO-32
GV_MAX Surge/HGBP IGVmax AO-33
shapefac Surge Line Shape Factor AO-34
VFD_POW Surge Line Speed Factor AO-35
surge_a Surge Delta % Amps AO-36
surge_t Surge Time Period AO-37
OILPD Oil Pump Delta P AO-38
OILT Oil Sump Temp AO-39
CPR_RPM Comp Motor RPM AO-40
VFD_FREQ Comp Motor Frequency AO-41
OCC Occupied? BO-01
CHIL_S_S Chiller Start/Stop BO-02
REM_CON Remote Start Contact BO-03
ICE_CON Ice Build Contact BO-04
EMSTOP Emergency Stop BO-05
ALM Alarm Relay BO-06
HGBYPASS Hot Gas Bypass Relay BO-07
SHG_ACT Surge Prevention Active? BO-08
CHLP Chilled Water Pump BO-09
CHW_FLOW Chilled Water Flow BO-10
CDP Condenser Water Pump BO-11
CDW_FLOW Condenser Water Flow BO-12
OILPUMP Oil Pump Relay BO-13
VFDSTART VFD Start BO-14
START_OK Start Complete BO-15
STOP_OK Stop Complete BO-16
TFR_LOW Tower Fan Relay Low BO-17
TFR_HIGH Tower Fan Relay High BO-18
SAFETY Spare Safety Input BO-19
Setpoints
DLM Base Demand Limit AO-42
lcw_sp LCW Setpoint AO-43
ecw_sp ECW Setpoint AO-44
ice_sp Ice Build Setpoint AO-45
TFH_SP Tower Fan High Setpoint AO-46

 

 

CCN Point Description – Run Status
CCN Variable-Status
0 = Timeout
1 = Ready
2 = Recycle
3 = Start-up
4 = Running
5 = Demand
6 = Ramping
7 = Auto Restart
8 = Override
9 = Tripout
10 = Control Test
11 = Lockout
12= Pumpdown
13 = Prestart
CCN Point Description – Control Mode
CCN Variable-Mode
0 = Off
1 = Local
2 = CCN
3 = Reset
CCN Point Description – System Alert/Alarm
CCN Variable-SYS_ALM
1 = Normal
2 = Alert
3 = Alarm

 

 

How to test the data

 

These notes are general and have not been customized for your project.

1. From the main menu of ruinet select A for Data Arrays

 

2. Look at the config file. Observe where the data is served from / collected into.

 

3. Now find that array in the list. In this example Array index=03.

You see this screen

 

Configuration File

Download: FSb0228 – Configuration File

//================================================================================,,,,,,,,
//,,,,,,,,
//,,,,,,,,
// 1.00 01 Sep 10 PMC Created ,,,,,,,,
// 2.00 01 Sep 10 PMC Added 2 chillers rushiaf@nationwide.com ,,,,,,,,
// 3.00 Added AV_000 thru AV020 ekilleen – Carrier,,,,,,,,
// 4.00 31 Mar 11 PMC CHanged server to single objects (length=1)
// 4.00 31 Mar 11 PMC Tested using the S4 N2 ROuter
//
//==============================================================================*/,,,,,,,,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Notes : None.,,,,,,,,
//,,,,,,,,
//,,,,,,,,
//================================================================================,,,,,,,,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Common Information,,,,,,,,
//,,,,,,,,
,,,,,,,,
Bridge,,,,,,,,
Title ,System_station_address,,,,,,,
Ref=FSb0228 Rev=4.00 ,11,,,,,,,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Data Arrays,,,,,,,,
//,,,,,,,,
,,,,,,,,
Data_Arrays,,,,,,,,
Data_Array_Name ,Data_Format ,Data_Array_Length,,,,,,
DA_FLOAT1 ,FLOAT ,100,,,,,,
DA_BIT1 ,BIT ,100,,,,,,
DA_FLOAT2 ,FLOAT ,100,,,,,,
DA_BIT2 ,BIT ,100,,,,,,
DA_FLOAT3 ,FLOAT ,100,,,,,,
DA_BIT3 ,BIT ,100,,,,,,
,,,,,,,,

 

//================================================================================,,,,,,,,
//,,,,,,,,
// Client Side Connections,,,,,,,,
//,,,,,,,,
,,,,,,,,
Connections,,,,,,,,
Port ,Baud ,Parity ,Data_Bits ,Stop_Bits ,Protocol ,Timeout ,Connection_Type ,
R1 ,38400,None ,8,1,Bacnet_MSTP ,30,MSTP_Master_Node,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Client Side Nodes,,,,,,,,
//,,,,,,,,
,,,,,,,,
Nodes,,,,,,,,
Node_Name ,Node_ID ,Protocol ,Port,,,,,
Chil01 ,1,Bacnet_MSTP ,R1 ,,,,,
Chil02 ,2,Bacnet_MSTP ,R1 ,,,,,
Chil03 ,3,Bacnet_MSTP ,R1 ,,,,,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Client Side Map Descriptors,,,,,,,,
//,,,,,,,,
,,,,,,,,
Map_Descriptors,,,,,,,,
Data_Type ,Object_ID ,Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Node_Name ,Property ,Scan_Interval,Function
AV,0,Control Mode,DA_FLOAT1 ,0,Chil01 ,Present_Value ,0.0s ,rdbc
AV,1,Run Status,DA_FLOAT1 ,1,Chil01 ,Present_Value ,0.0s ,rdbc
AV,2,Start Inhibit Timer,DA_FLOAT1 ,2,Chil01 ,Present_Value ,0.0s ,rdbc
AV,3,System Alert/Alarm,DA_FLOAT1 ,3,Chil01 ,Present_Value ,0.0s ,rdbc
AV,4,Temperature Reset,DA_FLOAT1 ,4,Chil01 ,Present_Value ,0.0s ,rdbc
AV,5,Control Point,DA_FLOAT1 ,5,Chil01 ,Present_Value ,0.0s ,rdbc
AV,6,Chilled Water Temp,DA_FLOAT1 ,6,Chil01 ,Present_Value ,0.0s ,rdbc
AV,7,Active Demand Limit,DA_FLOAT1 ,7,Chil01 ,Present_Value ,0.0s ,rdbc
AV,8,Percent Line Current,DA_FLOAT1 ,8,Chil01 ,Present_Value ,0.0s ,rdbc
AV,9,Percent Line Kilowatts,DA_FLOAT1 ,9,Chil01 ,Present_Value ,0.0s ,rdbc
AV,10,Auto Demand Limit Input,DA_FLOAT1 ,10,Chil01 ,Present_Value ,0.0s ,rdbc
AV,11,Auto Chilled Water Reset,DA_FLOAT1 ,11,Chil01 ,Present_Value ,0.0s ,rdbc
AV,12,Remote Reset Sensor,DA_FLOAT1 ,12,Chil01 ,Present_Value ,0.0s ,rdbc
AV,13,Total Compressor Starts,DA_FLOAT1 ,13,Chil01 ,Present_Value ,0.0s ,rdbc
AV,14,Starts in 12 Hours,DA_FLOAT1 ,14,Chil01 ,Present_Value ,0.0s ,rdbc
AV,15,Compressor Ontime,DA_FLOAT1 ,15,Chil01 ,Present_Value ,0.0s ,rdbc
AV,16,Service Ontime,DA_FLOAT1 ,16,Chil01 ,Present_Value ,0.0s ,rdbc
AV,17,Target VFD Speed,DA_FLOAT1 ,17,Chil01 ,Present_Value ,0.0s ,rdbc
AV,18,Actual Guide Vane Pos,DA_FLOAT1 ,18,Chil01 ,Present_Value ,0.0s ,rdbc
AV,19,Diffuser Actuator,DA_FLOAT1 ,19,Chil01 ,Present_Value ,0.0s ,rdbc
AV,20,Condenser Refrig Temp,DA_FLOAT1 ,20,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,21,ERT_Calc Evap Sat Temp ,DA_FLOAT1 ,21,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,22,CDW_DT_Active Delta Tsat ,DA_FLOAT1 ,22,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,23,DELTA_TX_Surge Line Delta Tsat ,DA_FLOAT1 ,23,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,24,DELTATXF_Calculated Delta Txfs ,DA_FLOAT1 ,24,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,25,CHW_DT_Chilled Water Delta T ,DA_FLOAT1 ,25,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,26,SP_HIGH_Surge Line High Offset ,DA_FLOAT1 ,26,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,27,DTsatmin_Surge/HGBP Delta Tsmin ,DA_FLOAT1 ,27,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,28,GV_MIN_Surge/HGBP IGVmin ,DA_FLOAT1 ,28,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,29,DTsatmax_Surge/HGBP Delta Tsmax ,DA_FLOAT1 ,29,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,30,GV_MAX_Surge/HGBP IGVmax ,DA_FLOAT1 ,30,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,31,shapefac_Surge Line Shape Factor ,DA_FLOAT1 ,31,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,32,VFD_POW_Surge Line Speed Factor ,DA_FLOAT1 ,32,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,33,surge_a_Surge Delta % Amps ,DA_FLOAT1 ,33,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,34,surge_t_Surge Time Period ,DA_FLOAT1 ,34,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,36,OILPD_Oil Pump Delta P ,DA_FLOAT1 ,36,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,37,OILT_Oil Sump Temp ,DA_FLOAT1 ,37,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,39,CPR_RPM_Comp Motor RPM ,DA_FLOAT1 ,39,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,40,VFD_FREQ_Comp Motor Frequency ,DA_FLOAT1 ,40,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,41,DLM_Base Demand Limit ,DA_FLOAT1 ,41,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,42,lcw_sp_LCW Setpoint ,DA_FLOAT1 ,42,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,43,ecw_sp_ECW Setpoint ,DA_FLOAT1 ,43,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,44,ice_sp_Ice Build Setpoint ,DA_FLOAT1 ,44,Chil01 ,Present_Value ,0.0s ,rdbc
AV ,45,TFH_SP_Tower Fan High Setpoint ,DA_FLOAT1 ,45,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,0,OCC_Occupied? ,DA_BIT1 ,0,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,1,CHIL_S_S_Chiller Start/Stop ,DA_BIT1 ,1,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,2,REM_CON_Remote Start Contact ,DA_BIT1 ,2,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,3,ICE_CON_Ice Build Contact ,DA_BIT1 ,3,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,4,EMSTOP_Emergency Stop ,DA_BIT1 ,4,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,5,ALM_Alarm Relay ,DA_BIT1 ,5,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,6,HGBYPASS_Hot Gas Bypass Relay ,DA_BIT1 ,6,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,7,SHG_ACT_Surge Prevention Active? ,DA_BIT1 ,7,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,8,CHLP_Chilled Water Pump ,DA_BIT1 ,8,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,9,CHW_FLOW_Chilled Water Flow ,DA_BIT1 ,9,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,10,CDP_Condenser Water Pump ,DA_BIT1 ,10,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,11,CDW_FLOW_Condenser Water Flow ,DA_BIT1 ,11,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,12,OILPUMP_Oil Pump Relay ,DA_BIT1 ,12,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,13,VFDSTART_VFD Start ,DA_BIT1 ,13,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,14,START_OK_Start Complete ,DA_BIT1 ,14,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,15,STOP_OK_Stop Complete ,DA_BIT1 ,15,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,16,TFR_LOW_Tower Fan Relay Low ,DA_BIT1 ,16,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,17,TFR_HIGH_Tower Fan Relay High ,DA_BIT1 ,17,Chil01 ,Present_Value ,0.0s ,rdbc
BV ,18,SAFETY_Spare Safety Input ,DA_BIT1 ,18,Chil01 ,Present_Value ,0.0s ,rdbc
,,,,,,,,
,,,,,,,,
,,,,,,,,
Map_Descriptors,,,,,,,,
Data_Type ,Object_ID ,Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Node_Name ,Property ,Scan_Interval,Function
AV,0,Control Mode,DA_FLOAT2 ,0,Chil02 ,Present_Value ,0.0s ,rdbc
AV,1,Run Status,DA_FLOAT2 ,1,Chil02 ,Present_Value ,0.0s ,rdbc
AV,2,Start Inhibit Timer,DA_FLOAT2 ,2,Chil02 ,Present_Value ,0.0s ,rdbc
AV,3,System Alert/Alarm,DA_FLOAT2 ,3,Chil02 ,Present_Value ,0.0s ,rdbc
AV,4,Temperature Reset,DA_FLOAT2 ,4,Chil02 ,Present_Value ,0.0s ,rdbc
AV,5,Control Point,DA_FLOAT2 ,5,Chil02 ,Present_Value ,0.0s ,rdbc
AV,6,Chilled Water Temp,DA_FLOAT2 ,6,Chil02 ,Present_Value ,0.0s ,rdbc
AV,7,Active Demand Limit,DA_FLOAT2 ,7,Chil02 ,Present_Value ,0.0s ,rdbc
AV,8,Percent Line Current,DA_FLOAT2 ,8,Chil02 ,Present_Value ,0.0s ,rdbc
AV,9,Percent Line Kilowatts,DA_FLOAT2 ,9,Chil02 ,Present_Value ,0.0s ,rdbc
AV,10,Auto Demand Limit Input,DA_FLOAT2 ,10,Chil02 ,Present_Value ,0.0s ,rdbc
AV,11,Auto Chilled Water Reset,DA_FLOAT2 ,11,Chil02 ,Present_Value ,0.0s ,rdbc
AV,12,Remote Reset Sensor,DA_FLOAT2 ,12,Chil02 ,Present_Value ,0.0s ,rdbc
AV,13,Total Compressor Starts,DA_FLOAT2 ,13,Chil02 ,Present_Value ,0.0s ,rdbc
AV,14,Starts in 12 Hours,DA_FLOAT2 ,14,Chil02 ,Present_Value ,0.0s ,rdbc
AV,15,Compressor Ontime,DA_FLOAT2 ,15,Chil02 ,Present_Value ,0.0s ,rdbc
AV,16,Service Ontime,DA_FLOAT2 ,16,Chil02 ,Present_Value ,0.0s ,rdbc
AV,17,Target VFD Speed,DA_FLOAT2 ,17,Chil02 ,Present_Value ,0.0s ,rdbc
AV,18,Actual Guide Vane Pos,DA_FLOAT2 ,18,Chil02 ,Present_Value ,0.0s ,rdbc
AV,19,Diffuser Actuator,DA_FLOAT2 ,19,Chil02 ,Present_Value ,0.0s ,rdbc
AV,20,Condenser Refrig Temp,DA_FLOAT2 ,20,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,21,ERT_Calc Evap Sat Temp ,DA_FLOAT2 ,21,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,22,CDW_DT_Active Delta Tsat ,DA_FLOAT2 ,22,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,23,DELTA_TX_Surge Line Delta Tsat ,DA_FLOAT2 ,23,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,24,DELTATXF_Calculated Delta Txfs ,DA_FLOAT2 ,24,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,25,CHW_DT_Chilled Water Delta T ,DA_FLOAT2 ,25,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,26,SP_HIGH_Surge Line High Offset ,DA_FLOAT2 ,26,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,27,DTsatmin_Surge/HGBP Delta Tsmin ,DA_FLOAT2 ,27,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,28,GV_MIN_Surge/HGBP IGVmin ,DA_FLOAT2 ,28,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,29,DTsatmax_Surge/HGBP Delta Tsmax ,DA_FLOAT2 ,29,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,30,GV_MAX_Surge/HGBP IGVmax ,DA_FLOAT2 ,30,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,31,shapefac_Surge Line Shape Factor ,DA_FLOAT2 ,31,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,32,VFD_POW_Surge Line Speed Factor ,DA_FLOAT2 ,32,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,33,surge_a_Surge Delta % Amps ,DA_FLOAT2 ,33,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,34,surge_t_Surge Time Period ,DA_FLOAT2 ,34,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,36,OILPD_Oil Pump Delta P ,DA_FLOAT2 ,36,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,37,OILT_Oil Sump Temp ,DA_FLOAT2 ,37,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,39,CPR_RPM_Comp Motor RPM ,DA_FLOAT2 ,39,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,40,VFD_FREQ_Comp Motor Frequency ,DA_FLOAT2 ,40,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,41,DLM_Base Demand Limit ,DA_FLOAT2 ,41,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,42,lcw_sp_LCW Setpoint ,DA_FLOAT2 ,42,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,43,ecw_sp_ECW Setpoint ,DA_FLOAT2 ,43,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,44,ice_sp_Ice Build Setpoint ,DA_FLOAT2 ,44,Chil02 ,Present_Value ,0.0s ,rdbc
AV ,45,TFH_SP_Tower Fan High Setpoint ,DA_FLOAT2 ,45,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,0,OCC_Occupied? ,DA_BIT2 ,0,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,1,CHIL_S_S_Chiller Start/Stop ,DA_BIT2 ,1,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,2,REM_CON_Remote Start Contact ,DA_BIT2 ,2,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,3,ICE_CON_Ice Build Contact ,DA_BIT2 ,3,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,4,EMSTOP_Emergency Stop ,DA_BIT2 ,4,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,5,ALM_Alarm Relay ,DA_BIT2 ,5,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,6,HGBYPASS_Hot Gas Bypass Relay ,DA_BIT2 ,6,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,7,SHG_ACT_Surge Prevention Active? ,DA_BIT2 ,7,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,8,CHLP_Chilled Water Pump ,DA_BIT2 ,8,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,9,CHW_FLOW_Chilled Water Flow ,DA_BIT2 ,9,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,10,CDP_Condenser Water Pump ,DA_BIT2 ,10,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,11,CDW_FLOW_Condenser Water Flow ,DA_BIT2 ,11,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,12,OILPUMP_Oil Pump Relay ,DA_BIT2 ,12,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,13,VFDSTART_VFD Start ,DA_BIT2 ,13,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,14,START_OK_Start Complete ,DA_BIT2 ,14,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,15,STOP_OK_Stop Complete ,DA_BIT2 ,15,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,16,TFR_LOW_Tower Fan Relay Low ,DA_BIT2 ,16,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,17,TFR_HIGH_Tower Fan Relay High ,DA_BIT2 ,17,Chil02 ,Present_Value ,0.0s ,rdbc
BV ,18,SAFETY_Spare Safety Input ,DA_BIT2 ,18,Chil02 ,Present_Value ,0.0s ,rdbc
,,,,,,,,
,,,,,,,,
,,,,,,,,

 

Map_Descriptors,,,,,,,,
Data_Type ,Object_ID ,Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Node_Name ,Property ,Scan_Interval,Function
AV,0,Control Mode,DA_FLOAT3 ,0,Chil03 ,Present_Value ,0.0s ,rdbc
AV,1,Run Status,DA_FLOAT3 ,1,Chil03 ,Present_Value ,0.0s ,rdbc
AV,2,Start Inhibit Timer,DA_FLOAT3 ,2,Chil03 ,Present_Value ,0.0s ,rdbc
AV,3,System Alert/Alarm,DA_FLOAT3 ,3,Chil03 ,Present_Value ,0.0s ,rdbc
AV,4,Temperature Reset,DA_FLOAT3 ,4,Chil03 ,Present_Value ,0.0s ,rdbc
AV,5,Control Point,DA_FLOAT3 ,5,Chil03 ,Present_Value ,0.0s ,rdbc
AV,6,Chilled Water Temp,DA_FLOAT3 ,6,Chil03 ,Present_Value ,0.0s ,rdbc
AV,7,Active Demand Limit,DA_FLOAT3 ,7,Chil03 ,Present_Value ,0.0s ,rdbc
AV,8,Percent Line Current,DA_FLOAT3 ,8,Chil03 ,Present_Value ,0.0s ,rdbc
AV,9,Percent Line Kilowatts,DA_FLOAT3 ,9,Chil03 ,Present_Value ,0.0s ,rdbc
AV,10,Auto Demand Limit Input,DA_FLOAT3 ,10,Chil03 ,Present_Value ,0.0s ,rdbc
AV,11,Auto Chilled Water Reset,DA_FLOAT3 ,11,Chil03 ,Present_Value ,0.0s ,rdbc
AV,12,Remote Reset Sensor,DA_FLOAT3 ,12,Chil03 ,Present_Value ,0.0s ,rdbc
AV,13,Total Compressor Starts,DA_FLOAT3 ,13,Chil03 ,Present_Value ,0.0s ,rdbc
AV,14,Starts in 12 Hours,DA_FLOAT3 ,14,Chil03 ,Present_Value ,0.0s ,rdbc
AV,15,Compressor Ontime,DA_FLOAT3 ,15,Chil03 ,Present_Value ,0.0s ,rdbc
AV,16,Service Ontime,DA_FLOAT3 ,16,Chil03 ,Present_Value ,0.0s ,rdbc
AV,17,Target VFD Speed,DA_FLOAT3 ,17,Chil03 ,Present_Value ,0.0s ,rdbc
AV,18,Actual Guide Vane Pos,DA_FLOAT3 ,18,Chil03 ,Present_Value ,0.0s ,rdbc
AV,19,Diffuser Actuator,DA_FLOAT3 ,19,Chil03 ,Present_Value ,0.0s ,rdbc
AV,20,Condenser Refrig Temp,DA_FLOAT3 ,20,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,21,ERT_Calc Evap Sat Temp ,DA_FLOAT3 ,21,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,22,CDW_DT_Active Delta Tsat ,DA_FLOAT3 ,22,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,23,DELTA_TX_Surge Line Delta Tsat ,DA_FLOAT3 ,23,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,24,DELTATXF_Calculated Delta Txfs ,DA_FLOAT3 ,24,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,25,CHW_DT_Chilled Water Delta T ,DA_FLOAT3 ,25,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,26,SP_HIGH_Surge Line High Offset ,DA_FLOAT3 ,26,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,27,DTsatmin_Surge/HGBP Delta Tsmin ,DA_FLOAT3 ,27,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,28,GV_MIN_Surge/HGBP IGVmin ,DA_FLOAT3 ,28,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,29,DTsatmax_Surge/HGBP Delta Tsmax ,DA_FLOAT3 ,29,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,30,GV_MAX_Surge/HGBP IGVmax ,DA_FLOAT3 ,30,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,31,shapefac_Surge Line Shape Factor ,DA_FLOAT3 ,31,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,32,VFD_POW_Surge Line Speed Factor ,DA_FLOAT3 ,32,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,33,surge_a_Surge Delta % Amps ,DA_FLOAT3 ,33,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,34,surge_t_Surge Time Period ,DA_FLOAT3 ,34,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,36,OILPD_Oil Pump Delta P ,DA_FLOAT3 ,36,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,37,OILT_Oil Sump Temp ,DA_FLOAT3 ,37,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,39,CPR_RPM_Comp Motor RPM ,DA_FLOAT3 ,39,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,40,VFD_FREQ_Comp Motor Frequency ,DA_FLOAT3 ,40,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,41,DLM_Base Demand Limit ,DA_FLOAT3 ,41,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,42,lcw_sp_LCW Setpoint ,DA_FLOAT3 ,42,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,43,ecw_sp_ECW Setpoint ,DA_FLOAT3 ,43,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,44,ice_sp_Ice Build Setpoint ,DA_FLOAT3 ,44,Chil03 ,Present_Value ,0.0s ,rdbc
AV ,45,TFH_SP_Tower Fan High Setpoint ,DA_FLOAT3 ,45,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,0,OCC_Occupied? ,DA_BIT3 ,0,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,1,CHIL_S_S_Chiller Start/Stop ,DA_BIT3 ,1,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,2,REM_CON_Remote Start Contact ,DA_BIT3 ,2,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,3,ICE_CON_Ice Build Contact ,DA_BIT3 ,3,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,4,EMSTOP_Emergency Stop ,DA_BIT3 ,4,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,5,ALM_Alarm Relay ,DA_BIT3 ,5,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,6,HGBYPASS_Hot Gas Bypass Relay ,DA_BIT3 ,6,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,7,SHG_ACT_Surge Prevention Active? ,DA_BIT3 ,7,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,8,CHLP_Chilled Water Pump ,DA_BIT3 ,8,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,9,CHW_FLOW_Chilled Water Flow ,DA_BIT3 ,9,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,10,CDP_Condenser Water Pump ,DA_BIT3 ,10,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,11,CDW_FLOW_Condenser Water Flow ,DA_BIT3 ,11,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,12,OILPUMP_Oil Pump Relay ,DA_BIT3 ,12,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,13,VFDSTART_VFD Start ,DA_BIT3 ,13,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,14,START_OK_Start Complete ,DA_BIT3 ,14,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,15,STOP_OK_Stop Complete ,DA_BIT3 ,15,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,16,TFR_LOW_Tower Fan Relay Low ,DA_BIT3 ,16,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,17,TFR_HIGH_Tower Fan Relay High ,DA_BIT3 ,17,Chil03 ,Present_Value ,0.0s ,rdbc
BV ,18,SAFETY_Spare Safety Input ,DA_BIT3 ,18,Chil03 ,Present_Value ,0.0s ,rdbc
,,,,,,,,
,,,,,,,,
,,,,,,,,

 

//================================================================================,,,,,,,,
//,,,,,,,,
// Server Side Connections,,,,,,,,
//,,,,,,,,
,,,,,,,,
Connections,,,,,,,,
Port ,Baud ,Data_Bits ,Parity ,Protocol ,Line_Drive_On ,Line_Drive_Off,,
R2 ,9600,8,None ,Metasys_N2 ,0.001s ,0,,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Server Side Nodes,,,,,,,,
//,,,,,,,,
Nodes,,,,,,,,
Node_Name ,Node_ID ,Protocol,Srv_Offline_Method,,,,,
Chiller01 ,1,Metasys_N2,Always_respond,,,,,
Chiller02 ,2,Metasys_N2,Always_respond,,,,,
Chiller03 ,3,Metasys_N2,Always_respond,,,,,
,,,,,,,,
,,,,,,,,
//================================================================================,,,,,,,,
//,,,,,,,,
// Server Side Map Descriptors,,,,,,,,
//,,,,,,,,
,,,,,,,,
Map_Descriptors,,,,,,,,
Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_name ,Address ,Length ,Data_Type,
Srv_Bits_Dev01_Pnt01,DA_BIT1 ,00,Server ,Chiller01 ,01,1 ,Dig_output,
Srv_Bits_Dev01_Pnt02,DA_BIT1 ,01,Server ,Chiller01 ,02,1 ,Dig_output,
Srv_Bits_Dev01_Pnt03,DA_BIT1 ,02,Server ,Chiller01 ,03,1 ,Dig_output,
Srv_Bits_Dev01_Pnt04,DA_BIT1 ,03,Server ,Chiller01 ,04,1 ,Dig_output,
Srv_Bits_Dev01_Pnt05,DA_BIT1 ,04,Server ,Chiller01 ,05,1 ,Dig_output,
Srv_Bits_Dev01_Pnt06,DA_BIT1 ,05,Server ,Chiller01 ,06,1 ,Dig_output,
Srv_Bits_Dev01_Pnt07,DA_BIT1 ,06,Server ,Chiller01 ,07,1 ,Dig_output,
Srv_Bits_Dev01_Pnt08,DA_BIT1 ,07,Server ,Chiller01 ,08,1 ,Dig_output,
Srv_Bits_Dev01_Pnt09,DA_BIT1 ,08,Server ,Chiller01 ,09,1 ,Dig_output,
Srv_Bits_Dev01_Pnt10,DA_BIT1 ,09,Server ,Chiller01 ,10,1 ,Dig_output,
Srv_Bits_Dev01_Pnt11,DA_BIT1 ,10,Server ,Chiller01 ,11,1 ,Dig_output,
Srv_Bits_Dev01_Pnt12,DA_BIT1 ,11,Server ,Chiller01 ,12,1 ,Dig_output,
Srv_Bits_Dev01_Pnt13,DA_BIT1 ,12,Server ,Chiller01 ,13,1 ,Dig_output,
Srv_Bits_Dev01_Pnt14,DA_BIT1 ,13,Server ,Chiller01 ,14,1 ,Dig_output,
Srv_Bits_Dev01_Pnt15,DA_BIT1 ,14,Server ,Chiller01 ,15,1 ,Dig_output,
Srv_Bits_Dev01_Pnt16,DA_BIT1 ,15,Server ,Chiller01 ,16,1 ,Dig_output,
Srv_Bits_Dev01_Pnt17,DA_BIT1 ,16,Server ,Chiller01 ,17,1 ,Dig_output,
Srv_Bits_Dev01_Pnt18,DA_BIT1 ,17,Server ,Chiller01 ,18,1 ,Dig_output,
Srv_Bits_Dev01_Pnt19,DA_BIT1 ,18,Server ,Chiller01 ,19,1 ,Dig_output,
Srv_Bits_Dev01_Pnt20,DA_BIT1 ,19,Server ,Chiller01 ,20,1 ,Dig_output,

 

Srv_Bits_Dev02_Pnt01,DA_BIT2 ,00,Server ,Chiller02 ,01,1 ,Dig_output,
Srv_Bits_Dev02_Pnt02,DA_BIT2 ,01,Server ,Chiller02 ,02,1 ,Dig_output,
Srv_Bits_Dev02_Pnt03,DA_BIT2 ,02,Server ,Chiller02 ,03,1 ,Dig_output,
Srv_Bits_Dev02_Pnt04,DA_BIT2 ,03,Server ,Chiller02 ,04,1 ,Dig_output,
Srv_Bits_Dev02_Pnt05,DA_BIT2 ,04,Server ,Chiller02 ,05,1 ,Dig_output,
Srv_Bits_Dev02_Pnt06,DA_BIT2 ,05,Server ,Chiller02 ,06,1 ,Dig_output,
Srv_Bits_Dev02_Pnt07,DA_BIT2 ,06,Server ,Chiller02 ,07,1 ,Dig_output,
Srv_Bits_Dev02_Pnt08,DA_BIT2 ,07,Server ,Chiller02 ,08,1 ,Dig_output,
Srv_Bits_Dev02_Pnt09,DA_BIT2 ,08,Server ,Chiller02 ,09,1 ,Dig_output,
Srv_Bits_Dev02_Pnt10,DA_BIT2 ,09,Server ,Chiller02 ,10,1 ,Dig_output,
Srv_Bits_Dev02_Pnt11,DA_BIT2 ,10,Server ,Chiller02 ,11,1 ,Dig_output,
Srv_Bits_Dev02_Pnt12,DA_BIT2 ,11,Server ,Chiller02 ,12,1 ,Dig_output,
Srv_Bits_Dev02_Pnt13,DA_BIT2 ,12,Server ,Chiller02 ,13,1 ,Dig_output,
Srv_Bits_Dev02_Pnt14,DA_BIT2 ,13,Server ,Chiller02 ,14,1 ,Dig_output,
Srv_Bits_Dev02_Pnt15,DA_BIT2 ,14,Server ,Chiller02 ,15,1 ,Dig_output,
Srv_Bits_Dev02_Pnt16,DA_BIT2 ,15,Server ,Chiller02 ,16,1 ,Dig_output,
Srv_Bits_Dev02_Pnt17,DA_BIT2 ,16,Server ,Chiller02 ,17,1 ,Dig_output,
Srv_Bits_Dev02_Pnt18,DA_BIT2 ,17,Server ,Chiller02 ,18,1 ,Dig_output,
Srv_Bits_Dev02_Pnt19,DA_BIT2 ,18,Server ,Chiller02 ,19,1 ,Dig_output,
Srv_Bits_Dev02_Pnt20,DA_BIT2 ,19,Server ,Chiller02 ,20,1 ,Dig_output,

 

Srv_Bits_Dev03_Pnt01,DA_BIT3 ,00,Server ,Chiller03 ,01,1 ,Dig_output,
Srv_Bits_Dev03_Pnt02,DA_BIT3 ,01,Server ,Chiller03 ,02,1 ,Dig_output,
Srv_Bits_Dev03_Pnt03,DA_BIT3 ,02,Server ,Chiller03 ,03,1 ,Dig_output,
Srv_Bits_Dev03_Pnt04,DA_BIT3 ,03,Server ,Chiller03 ,04,1 ,Dig_output,
Srv_Bits_Dev03_Pnt05,DA_BIT3 ,04,Server ,Chiller03 ,05,1 ,Dig_output,
Srv_Bits_Dev03_Pnt06,DA_BIT3 ,05,Server ,Chiller03 ,06,1 ,Dig_output,
Srv_Bits_Dev03_Pnt07,DA_BIT3 ,06,Server ,Chiller03 ,07,1 ,Dig_output,
Srv_Bits_Dev03_Pnt08,DA_BIT3 ,07,Server ,Chiller03 ,08,1 ,Dig_output,
Srv_Bits_Dev03_Pnt09,DA_BIT3 ,08,Server ,Chiller03 ,09,1 ,Dig_output,
Srv_Bits_Dev03_Pnt10,DA_BIT3 ,09,Server ,Chiller03 ,10,1 ,Dig_output,
Srv_Bits_Dev03_Pnt11,DA_BIT3 ,10,Server ,Chiller03 ,11,1 ,Dig_output,
Srv_Bits_Dev03_Pnt12,DA_BIT3 ,11,Server ,Chiller03 ,12,1 ,Dig_output,
Srv_Bits_Dev03_Pnt13,DA_BIT3 ,12,Server ,Chiller03 ,13,1 ,Dig_output,
Srv_Bits_Dev03_Pnt14,DA_BIT3 ,13,Server ,Chiller03 ,14,1 ,Dig_output,
Srv_Bits_Dev03_Pnt15,DA_BIT3 ,14,Server ,Chiller03 ,15,1 ,Dig_output,
Srv_Bits_Dev03_Pnt16,DA_BIT3 ,15,Server ,Chiller03 ,16,1 ,Dig_output,
Srv_Bits_Dev03_Pnt17,DA_BIT3 ,16,Server ,Chiller03 ,17,1 ,Dig_output,
Srv_Bits_Dev03_Pnt18,DA_BIT3 ,17,Server ,Chiller03 ,18,1 ,Dig_output,
Srv_Bits_Dev03_Pnt19,DA_BIT3 ,18,Server ,Chiller03 ,19,1 ,Dig_output,
Srv_Bits_Dev03_Pnt20,DA_BIT3 ,19,Server ,Chiller03 ,20,1 ,Dig_output,

 

Srv_Ana_Dev01_Pnt01 ,DA_FLOAT1 ,00,Server ,Chiller01 ,01,1 ,Ana_output,
Srv_Ana_Dev01_Pnt02 ,DA_FLOAT1 ,01,Server ,Chiller01 ,02,1 ,Ana_output,
Srv_Ana_Dev01_Pnt03 ,DA_FLOAT1 ,02,Server ,Chiller01 ,03,1 ,Ana_output,
Srv_Ana_Dev01_Pnt04 ,DA_FLOAT1 ,03,Server ,Chiller01 ,04,1 ,Ana_output,
Srv_Ana_Dev01_Pnt05 ,DA_FLOAT1 ,04,Server ,Chiller01 ,05,1 ,Ana_output,
Srv_Ana_Dev01_Pnt06 ,DA_FLOAT1 ,05,Server ,Chiller01 ,06,1 ,Ana_output,
Srv_Ana_Dev01_Pnt07 ,DA_FLOAT1 ,06,Server ,Chiller01 ,07,1 ,Ana_output,
Srv_Ana_Dev01_Pnt08 ,DA_FLOAT1 ,07,Server ,Chiller01 ,08,1 ,Ana_output,
Srv_Ana_Dev01_Pnt09 ,DA_FLOAT1 ,08,Server ,Chiller01 ,09,1 ,Ana_output,
Srv_Ana_Dev01_Pnt10 ,DA_FLOAT1 ,09,Server ,Chiller01 ,10,1 ,Ana_output,
Srv_Ana_Dev01_Pnt11 ,DA_FLOAT1 ,10,Server ,Chiller01 ,11,1 ,Ana_output,
Srv_Ana_Dev01_Pnt12 ,DA_FLOAT1 ,11,Server ,Chiller01 ,12,1 ,Ana_output,
Srv_Ana_Dev01_Pnt13 ,DA_FLOAT1 ,12,Server ,Chiller01 ,13,1 ,Ana_output,
Srv_Ana_Dev01_Pnt14 ,DA_FLOAT1 ,13,Server ,Chiller01 ,14,1 ,Ana_output,
Srv_Ana_Dev01_Pnt15 ,DA_FLOAT1 ,14,Server ,Chiller01 ,15,1 ,Ana_output,
Srv_Ana_Dev01_Pnt16 ,DA_FLOAT1 ,15,Server ,Chiller01 ,16,1 ,Ana_output,
Srv_Ana_Dev01_Pnt17 ,DA_FLOAT1 ,16,Server ,Chiller01 ,17,1 ,Ana_output,
Srv_Ana_Dev01_Pnt18 ,DA_FLOAT1 ,17,Server ,Chiller01 ,18,1 ,Ana_output,
Srv_Ana_Dev01_Pnt19 ,DA_FLOAT1 ,18,Server ,Chiller01 ,19,1 ,Ana_output,
Srv_Ana_Dev01_Pnt20 ,DA_FLOAT1 ,19,Server ,Chiller01 ,20,1 ,Ana_output,
Srv_Ana_Dev01_Pnt21 ,DA_FLOAT1 ,20,Server ,Chiller01 ,21,1 ,Ana_output,
Srv_Ana_Dev01_Pnt22 ,DA_FLOAT1 ,21,Server ,Chiller01 ,22,1 ,Ana_output,
Srv_Ana_Dev01_Pnt23 ,DA_FLOAT1 ,22,Server ,Chiller01 ,23,1 ,Ana_output,
Srv_Ana_Dev01_Pnt24 ,DA_FLOAT1 ,23,Server ,Chiller01 ,24,1 ,Ana_output,
Srv_Ana_Dev01_Pnt25 ,DA_FLOAT1 ,24,Server ,Chiller01 ,25,1 ,Ana_output,
Srv_Ana_Dev01_Pnt26 ,DA_FLOAT1 ,25,Server ,Chiller01 ,26,1 ,Ana_output,
Srv_Ana_Dev01_Pnt27 ,DA_FLOAT1 ,26,Server ,Chiller01 ,27,1 ,Ana_output,
Srv_Ana_Dev01_Pnt28 ,DA_FLOAT1 ,27,Server ,Chiller01 ,28,1 ,Ana_output,
Srv_Ana_Dev01_Pnt29 ,DA_FLOAT1 ,28,Server ,Chiller01 ,29,1 ,Ana_output,
Srv_Ana_Dev01_Pnt30 ,DA_FLOAT1 ,29,Server ,Chiller01 ,30,1 ,Ana_output,
Srv_Ana_Dev01_Pnt31 ,DA_FLOAT1 ,30,Server ,Chiller01 ,31,1 ,Ana_output,
Srv_Ana_Dev01_Pnt32 ,DA_FLOAT1 ,31,Server ,Chiller01 ,32,1 ,Ana_output,
Srv_Ana_Dev01_Pnt33 ,DA_FLOAT1 ,32,Server ,Chiller01 ,33,1 ,Ana_output,
Srv_Ana_Dev01_Pnt34 ,DA_FLOAT1 ,33,Server ,Chiller01 ,34,1 ,Ana_output,
Srv_Ana_Dev01_Pnt35 ,DA_FLOAT1 ,34,Server ,Chiller01 ,35,1 ,Ana_output,
Srv_Ana_Dev01_Pnt36 ,DA_FLOAT1 ,35,Server ,Chiller01 ,36,1 ,Ana_output,
Srv_Ana_Dev01_Pnt37 ,DA_FLOAT1 ,36,Server ,Chiller01 ,37,1 ,Ana_output,
Srv_Ana_Dev01_Pnt38 ,DA_FLOAT1 ,37,Server ,Chiller01 ,38,1 ,Ana_output,
Srv_Ana_Dev01_Pnt39 ,DA_FLOAT1 ,38,Server ,Chiller01 ,39,1 ,Ana_output,
Srv_Ana_Dev01_Pnt40 ,DA_FLOAT1 ,39,Server ,Chiller01 ,40,1 ,Ana_output,
Srv_Ana_Dev01_Pnt41 ,DA_FLOAT1 ,40,Server ,Chiller01 ,41,1 ,Ana_output,
Srv_Ana_Dev01_Pnt42 ,DA_FLOAT1 ,41,Server ,Chiller01 ,42,1 ,Ana_output,
Srv_Ana_Dev01_Pnt43 ,DA_FLOAT1 ,42,Server ,Chiller01 ,43,1 ,Ana_output,
Srv_Ana_Dev01_Pnt44 ,DA_FLOAT1 ,43,Server ,Chiller01 ,44,1 ,Ana_output,
Srv_Ana_Dev01_Pnt45 ,DA_FLOAT1 ,44,Server ,Chiller01 ,45,1 ,Ana_output,

 

Srv_Ana_Dev02_Pnt01 ,DA_FLOAT2 ,00,Server ,Chiller02 ,01,1 ,Ana_output,
Srv_Ana_Dev02_Pnt02 ,DA_FLOAT2 ,01,Server ,Chiller02 ,02,1 ,Ana_output,
Srv_Ana_Dev02_Pnt03 ,DA_FLOAT2 ,02,Server ,Chiller02 ,03,1 ,Ana_output,
Srv_Ana_Dev02_Pnt04 ,DA_FLOAT2 ,03,Server ,Chiller02 ,04,1 ,Ana_output,
Srv_Ana_Dev02_Pnt05 ,DA_FLOAT2 ,04,Server ,Chiller02 ,05,1 ,Ana_output,
Srv_Ana_Dev02_Pnt06 ,DA_FLOAT2 ,05,Server ,Chiller02 ,06,1 ,Ana_output,
Srv_Ana_Dev02_Pnt07 ,DA_FLOAT2 ,06,Server ,Chiller02 ,07,1 ,Ana_output,
Srv_Ana_Dev02_Pnt08 ,DA_FLOAT2 ,07,Server ,Chiller02 ,08,1 ,Ana_output,
Srv_Ana_Dev02_Pnt09 ,DA_FLOAT2 ,08,Server ,Chiller02 ,09,1 ,Ana_output,
Srv_Ana_Dev02_Pnt10 ,DA_FLOAT2 ,09,Server ,Chiller02 ,10,1 ,Ana_output,
Srv_Ana_Dev02_Pnt11 ,DA_FLOAT2 ,10,Server ,Chiller02 ,11,1 ,Ana_output,
Srv_Ana_Dev02_Pnt12 ,DA_FLOAT2 ,11,Server ,Chiller02 ,12,1 ,Ana_output,
Srv_Ana_Dev02_Pnt13 ,DA_FLOAT2 ,12,Server ,Chiller02 ,13,1 ,Ana_output,
Srv_Ana_Dev02_Pnt14 ,DA_FLOAT2 ,13,Server ,Chiller02 ,14,1 ,Ana_output,
Srv_Ana_Dev02_Pnt15 ,DA_FLOAT2 ,14,Server ,Chiller02 ,15,1 ,Ana_output,
Srv_Ana_Dev02_Pnt16 ,DA_FLOAT2 ,15,Server ,Chiller02 ,16,1 ,Ana_output,
Srv_Ana_Dev02_Pnt17 ,DA_FLOAT2 ,16,Server ,Chiller02 ,17,1 ,Ana_output,
Srv_Ana_Dev02_Pnt18 ,DA_FLOAT2 ,17,Server ,Chiller02 ,18,1 ,Ana_output,
Srv_Ana_Dev02_Pnt19 ,DA_FLOAT2 ,18,Server ,Chiller02 ,19,1 ,Ana_output,
Srv_Ana_Dev02_Pnt20 ,DA_FLOAT2 ,19,Server ,Chiller02 ,20,1 ,Ana_output,
Srv_Ana_Dev02_Pnt21 ,DA_FLOAT2 ,20,Server ,Chiller02 ,21,1 ,Ana_output,
Srv_Ana_Dev02_Pnt22 ,DA_FLOAT2 ,21,Server ,Chiller02 ,22,1 ,Ana_output,
Srv_Ana_Dev02_Pnt23 ,DA_FLOAT2 ,22,Server ,Chiller02 ,23,1 ,Ana_output,
Srv_Ana_Dev02_Pnt24 ,DA_FLOAT2 ,23,Server ,Chiller02 ,24,1 ,Ana_output,
Srv_Ana_Dev02_Pnt25 ,DA_FLOAT2 ,24,Server ,Chiller02 ,25,1 ,Ana_output,
Srv_Ana_Dev02_Pnt26 ,DA_FLOAT2 ,25,Server ,Chiller02 ,26,1 ,Ana_output,
Srv_Ana_Dev02_Pnt27 ,DA_FLOAT2 ,26,Server ,Chiller02 ,27,1 ,Ana_output,
Srv_Ana_Dev02_Pnt28 ,DA_FLOAT2 ,27,Server ,Chiller02 ,28,1 ,Ana_output,
Srv_Ana_Dev02_Pnt29 ,DA_FLOAT2 ,28,Server ,Chiller02 ,29,1 ,Ana_output,
Srv_Ana_Dev02_Pnt30 ,DA_FLOAT2 ,29,Server ,Chiller02 ,30,1 ,Ana_output,
Srv_Ana_Dev02_Pnt31 ,DA_FLOAT2 ,30,Server ,Chiller02 ,31,1 ,Ana_output,
Srv_Ana_Dev02_Pnt32 ,DA_FLOAT2 ,31,Server ,Chiller02 ,32,1 ,Ana_output,
Srv_Ana_Dev02_Pnt33 ,DA_FLOAT2 ,32,Server ,Chiller02 ,33,1 ,Ana_output,
Srv_Ana_Dev02_Pnt34 ,DA_FLOAT2 ,33,Server ,Chiller02 ,34,1 ,Ana_output,
Srv_Ana_Dev02_Pnt35 ,DA_FLOAT2 ,34,Server ,Chiller02 ,35,1 ,Ana_output,
Srv_Ana_Dev02_Pnt36 ,DA_FLOAT2 ,35,Server ,Chiller02 ,36,1 ,Ana_output,
Srv_Ana_Dev02_Pnt37 ,DA_FLOAT2 ,36,Server ,Chiller02 ,37,1 ,Ana_output,
Srv_Ana_Dev02_Pnt38 ,DA_FLOAT2 ,37,Server ,Chiller02 ,38,1 ,Ana_output,
Srv_Ana_Dev02_Pnt39 ,DA_FLOAT2 ,38,Server ,Chiller02 ,39,1 ,Ana_output,
Srv_Ana_Dev02_Pnt40 ,DA_FLOAT2 ,39,Server ,Chiller02 ,40,1 ,Ana_output,
Srv_Ana_Dev02_Pnt41 ,DA_FLOAT2 ,40,Server ,Chiller02 ,41,1 ,Ana_output,
Srv_Ana_Dev02_Pnt42 ,DA_FLOAT2 ,41,Server ,Chiller02 ,42,1 ,Ana_output,
Srv_Ana_Dev02_Pnt43 ,DA_FLOAT2 ,42,Server ,Chiller02 ,43,1 ,Ana_output,
Srv_Ana_Dev02_Pnt44 ,DA_FLOAT2 ,43,Server ,Chiller02 ,44,1 ,Ana_output,
Srv_Ana_Dev02_Pnt45 ,DA_FLOAT2 ,44,Server ,Chiller02 ,45,1 ,Ana_output,

 

Srv_Ana_Dev03_Pnt01 ,DA_FLOAT3 ,00,Server ,Chiller03 ,01,1 ,Ana_output,
Srv_Ana_Dev03_Pnt02 ,DA_FLOAT3 ,01,Server ,Chiller03 ,02,1 ,Ana_output,
Srv_Ana_Dev03_Pnt03 ,DA_FLOAT3 ,02,Server ,Chiller03 ,03,1 ,Ana_output,
Srv_Ana_Dev03_Pnt04 ,DA_FLOAT3 ,03,Server ,Chiller03 ,04,1 ,Ana_output,
Srv_Ana_Dev03_Pnt05 ,DA_FLOAT3 ,04,Server ,Chiller03 ,05,1 ,Ana_output,
Srv_Ana_Dev03_Pnt06 ,DA_FLOAT3 ,05,Server ,Chiller03 ,06,1 ,Ana_output,
Srv_Ana_Dev03_Pnt07 ,DA_FLOAT3 ,06,Server ,Chiller03 ,07,1 ,Ana_output,
Srv_Ana_Dev03_Pnt08 ,DA_FLOAT3 ,07,Server ,Chiller03 ,08,1 ,Ana_output,
Srv_Ana_Dev03_Pnt09 ,DA_FLOAT3 ,08,Server ,Chiller03 ,09,1 ,Ana_output,
Srv_Ana_Dev03_Pnt10 ,DA_FLOAT3 ,09,Server ,Chiller03 ,10,1 ,Ana_output,
Srv_Ana_Dev03_Pnt11 ,DA_FLOAT3 ,10,Server ,Chiller03 ,11,1 ,Ana_output,
Srv_Ana_Dev03_Pnt12 ,DA_FLOAT3 ,11,Server ,Chiller03 ,12,1 ,Ana_output,
Srv_Ana_Dev03_Pnt13 ,DA_FLOAT3 ,12,Server ,Chiller03 ,13,1 ,Ana_output,
Srv_Ana_Dev03_Pnt14 ,DA_FLOAT3 ,13,Server ,Chiller03 ,14,1 ,Ana_output,
Srv_Ana_Dev03_Pnt15 ,DA_FLOAT3 ,14,Server ,Chiller03 ,15,1 ,Ana_output,
Srv_Ana_Dev03_Pnt16 ,DA_FLOAT3 ,15,Server ,Chiller03 ,16,1 ,Ana_output,
Srv_Ana_Dev03_Pnt17 ,DA_FLOAT3 ,16,Server ,Chiller03 ,17,1 ,Ana_output,
Srv_Ana_Dev03_Pnt18 ,DA_FLOAT3 ,17,Server ,Chiller03 ,18,1 ,Ana_output,
Srv_Ana_Dev03_Pnt19 ,DA_FLOAT3 ,18,Server ,Chiller03 ,19,1 ,Ana_output,
Srv_Ana_Dev03_Pnt20 ,DA_FLOAT3 ,19,Server ,Chiller03 ,20,1 ,Ana_output,
Srv_Ana_Dev03_Pnt21 ,DA_FLOAT3 ,20,Server ,Chiller03 ,21,1 ,Ana_output,
Srv_Ana_Dev03_Pnt22 ,DA_FLOAT3 ,21,Server ,Chiller03 ,22,1 ,Ana_output,
Srv_Ana_Dev03_Pnt23 ,DA_FLOAT3 ,22,Server ,Chiller03 ,23,1 ,Ana_output,
Srv_Ana_Dev03_Pnt24 ,DA_FLOAT3 ,23,Server ,Chiller03 ,24,1 ,Ana_output,
Srv_Ana_Dev03_Pnt25 ,DA_FLOAT3 ,24,Server ,Chiller03 ,25,1 ,Ana_output,
Srv_Ana_Dev03_Pnt26 ,DA_FLOAT3 ,25,Server ,Chiller03 ,26,1 ,Ana_output,
Srv_Ana_Dev03_Pnt27 ,DA_FLOAT3 ,26,Server ,Chiller03 ,27,1 ,Ana_output,
Srv_Ana_Dev03_Pnt28 ,DA_FLOAT3 ,27,Server ,Chiller03 ,28,1 ,Ana_output,
Srv_Ana_Dev03_Pnt29 ,DA_FLOAT3 ,28,Server ,Chiller03 ,29,1 ,Ana_output,
Srv_Ana_Dev03_Pnt30 ,DA_FLOAT3 ,29,Server ,Chiller03 ,30,1 ,Ana_output,
Srv_Ana_Dev03_Pnt31 ,DA_FLOAT3 ,30,Server ,Chiller03 ,31,1 ,Ana_output,
Srv_Ana_Dev03_Pnt32 ,DA_FLOAT3 ,31,Server ,Chiller03 ,32,1 ,Ana_output,
Srv_Ana_Dev03_Pnt33 ,DA_FLOAT3 ,32,Server ,Chiller03 ,33,1 ,Ana_output,
Srv_Ana_Dev03_Pnt34 ,DA_FLOAT3 ,33,Server ,Chiller03 ,34,1 ,Ana_output,
Srv_Ana_Dev03_Pnt35 ,DA_FLOAT3 ,34,Server ,Chiller03 ,35,1 ,Ana_output,
Srv_Ana_Dev03_Pnt36 ,DA_FLOAT3 ,35,Server ,Chiller03 ,36,1 ,Ana_output,
Srv_Ana_Dev03_Pnt37 ,DA_FLOAT3 ,36,Server ,Chiller03 ,37,1 ,Ana_output,
Srv_Ana_Dev03_Pnt38 ,DA_FLOAT3 ,37,Server ,Chiller03 ,38,1 ,Ana_output,
Srv_Ana_Dev03_Pnt39 ,DA_FLOAT3 ,38,Server ,Chiller03 ,39,1 ,Ana_output,
Srv_Ana_Dev03_Pnt40 ,DA_FLOAT3 ,39,Server ,Chiller03 ,40,1 ,Ana_output,
Srv_Ana_Dev03_Pnt41 ,DA_FLOAT3 ,40,Server ,Chiller03 ,41,1 ,Ana_output,
Srv_Ana_Dev03_Pnt42 ,DA_FLOAT3 ,41,Server ,Chiller03 ,42,1 ,Ana_output,
Srv_Ana_Dev03_Pnt43 ,DA_FLOAT3 ,42,Server ,Chiller03 ,43,1 ,Ana_output,
Srv_Ana_Dev03_Pnt44 ,DA_FLOAT3 ,43,Server ,Chiller03 ,44,1 ,Ana_output,
Srv_Ana_Dev03_Pnt45 ,DA_FLOAT3 ,44,Server ,Chiller03 ,45,1 ,Ana_output,

 

 

If you liked this post;