FS-QS-1010-0309 QuickServer – BACnet MS/TP to JCI Metasys N2
The FS-QS-1010-0309 QuickServer provides a cost-effective, easy to use interface from BACnet MS/TP to JCI Metasys N2. The QuickServer is delivered with both drivers preloaded and ready to be configured using the provided instructions and software.
QuickServer Key Features:
- BACnet Testing Laboratory (BTL) Mark
- Ability to interface up to 250 points of common BAS protocols
- Multi-configuration capability; specific configurations selectable via DIP switches or software
- Flat panel mount standard, DIN rail mount option
- DIP switches to select baud rate or node ID on the fly
BACnet MS/TP driver:
- Driver type: Client or Server
- Data Link layer: MS/TP master (Clause 9), baud rate up to 38.4 Kbps, MS/TP slave (Clause 9), baud rate up to 38.4 Kbps
- Connection type: RS-485 (two wire, half duplex)
- Baud rates: 9600, 38400, 76800
- BACnet COV support for fast data communication while reducing traffic over a BACnet network
- Data types supported:
- AI – Analog Input Object
- AO – Analog Output Object
- AV – Analog Value Object
- BI – Binary Input Object
- BO – Binary Output Object
- BV – Binary Value Object
- MI – Multi-state Input Object
- MO – Multi-state Output Object
- MV – Multi-state Value Object
JCI Metasys N2 driver:
- Supports communication with following devices or classes of devices when acting as a Client
- N2OPEN-compliant devices
- VMA 1400 series
- DX9100 and XT9100
- Driver type: Client or Server
- Connection type: RS-485 (two wire, half duplex)
- Baud rates: 9600
- Devices tested:
- UNT
- VMA1410,
- VMA1420
- DX9100 with XT9100 extension
- NCM (FieldServer as N2Open server)
- VAV
- AHU
- VND
Block Diagram
Metasys® as used in this document is a trademark of Johnson Controls, Inc.