Points List
This points list may change when firmware is updated or the device is configured differently. Contact us to check for the lastest points list.
Water Cooler Chiller
| Map_Descriptor_Name | Data_Type | Address | Function | Units |
|---|---|---|---|---|
| num_of_compressors | Av | 001 | Server | No_Units |
| capacity | Av | 002 | Server | No_Units |
| demand | Av | 003 | Server | No_Units |
| current_faults | Av | 004 | Server | No_Units |
| echw_sys_temp | Av | 005 | Server | No_Units |
| lchw_sys_temp | Av | 006 | Server | No_Units |
| ecw_sys_temp | Av | 007 | Server | No_Units |
| lcw_sys_temp | Av | 008 | Server | No_Units |
| lead_comp_read | Av | 009 | Server | No_Units |
| load_limit_read | Av | 010 | Server | No_Units |
| upsetpt_read | Av | 011 | Server | No_Units |
| lowsetpt_read | Av | 012 | Server | No_Units |
| vsp_read | Av | 013 | Server | No_Units |
| tdiff_read | Av | 014 | Server | No_Units |
| fail_indic_read | Av | 015 | Server | No_Units |
| flush_time_read | Av | 016 | Server | No_Units |
| flush_duration_read | Av | 017 | Server | No_Units |
| month | Av | 018 | Server | No_Units |
| day | Av | 019 | Server | No_Units |
| year | Av | 020 | Server | No_Units |
| hour | Av | 021 | Server | No_Units |
| minute | Av | 022 | Server | No_Units |
| faults_c1 | Av | 023 | Server | No_Units |
| faults_c2 | Av | 024 | Server | No_Units |
| faults_c3 | Av | 025 | Server | No_Units |
| faults_c4 | Av | 026 | Server | No_Units |
| faults_c5 | Av | 027 | Server | No_Units |
| faults_c6 | Av | 028 | Server | No_Units |
| faults_c7 | Av | 029 | Server | No_Units |
| faults_c8 | Av | 030 | Server | No_Units |
| faults_c9 | Av | 031 | Server | No_Units |
| faults_c10 | Av | 032 | Server | No_Units |
| faults_c11 | Av | 033 | Server | No_Units |
| faults_c12 | Av | 034 | Server | No_Units |
| faults_c13 | Av | 035 | Server | No_Units |
| faults_c14 | Av | 036 | Server | No_Units |
| faults_c15 | Av | 037 | Server | No_Units |
| faults_c16 | Av | 038 | Server | No_Units |
| faults_c17 | Av | 039 | Server | No_Units |
| faults_c18 | Av | 040 | Server | No_Units |
| faults_c19 | Av | 041 | Server | No_Units |
| faults_c20 | Av | 042 | Server | No_Units |
| faults_c21 | Av | 043 | Server | No_Units |
| faults_c22 | Av | 044 | Server | No_Units |
| faults_c23 | Av | 045 | Server | No_Units |
| faults_c24 | Av | 046 | Server | No_Units |
| c1_suct_temp | Av | 047 | Server | No_Units |
| c1_lchw_temp | Av | 048 | Server | No_Units |
| c2_suct_temp | Av | 049 | Server | No_Units |
| c2_lchw_temp | Av | 050 | Server | No_Units |
| c3_suct_temp | Av | 051 | Server | No_Units |
| c3_lchw_temp | Av | 052 | Server | No_Units |
| c4_suct_temp | Av | 053 | Server | No_Units |
| c4_lchw_temp | Av | 054 | Server | No_Units |
| c5_suct_temp | Av | 055 | Server | No_Units |
| c5_lchw_temp | Av | 056 | Server | No_Units |
| c6_suct_temp | Av | 057 | Server | No_Units |
| c6_lchw_temp | Av | 058 | Server | No_Units |
| c7_suct_temp | Av | 059 | Server | No_Units |
| c7_lchw_temp | Av | 060 | Server | No_Units |
| c8_suct_temp | Av | 061 | Server | No_Units |
| c8_lchw_temp | Av | 062 | Server | No_Units |
| c9_suct_temp | Av | 063 | Server | No_Units |
| c9_lchw_temp | Av | 064 | Server | No_Units |
| c10_suct_temp | Av | 065 | Server | No_Units |
| c10_lchw_temp | Av | 066 | Server | No_Units |
| c11_suct_temp | Av | 067 | Server | No_Units |
| c11_lchw_temp | Av | 068 | Server | No_Units |
| c12_suct_temp | Av | 069 | Server | No_Units |
| c12_lchw_temp | Av | 070 | Server | No_Units |
| c13_suct_temp | Av | 071 | Server | No_Units |
| c13_lchw_temp | Av | 072 | Server | No_Units |
| c14_suct_temp | Av | 073 | Server | No_Units |
| c14_lchw_temp | Av | 074 | Server | No_Units |
| c15_suct_temp | Av | 075 | Server | No_Units |
| c15_lchw_temp | Av | 076 | Server | No_Units |
| c16_suct_temp | Av | 077 | Server | No_Units |
| c16_lchw_temp | Av | 078 | Server | No_Units |
| c17_suct_temp | Av | 079 | Server | No_Units |
| c17_lchw_temp | Av | 080 | Server | No_Units |
| c18_suct_temp | Av | 081 | Server | No_Units |
| c18_lchw_temp | Av | 082 | Server | No_Units |
| c19_suct_temp | Av | 083 | Server | No_Units |
| c19_lchw_temp | Av | 084 | Server | No_Units |
| c20_suct_temp | Av | 085 | Server | No_Units |
| c20_lchw_temp | Av | 086 | Server | No_Units |
| c21_suct_temp | Av | 087 | Server | No_Units |
| c21_lchw_temp | Av | 088 | Server | No_Units |
| c22_suct_temp | Av | 089 | Server | No_Units |
| c22_lchw_temp | Av | 090 | Server | No_Units |
| c23_suct_temp | Av | 091 | Server | No_Units |
| c23_lchw_temp | Av | 092 | Server | No_Units |
| c24_suct_temp | Av | 093 | Server | No_Units |
| c24_lchw_temp | Av | 094 | Server | No_Units |
| fault_1_type | Av | 095 | Server | No_Units |
| fault_2_type | Av | 096 | Server | No_Units |
| fault_3_type | Av | 097 | Server | No_Units |
| fault_4_type | Av | 098 | Server | No_Units |
| fault_5_type | Av | 099 | Server | No_Units |
| fault_6_type | Av | 100 | Server | No_Units |
| fault_7_type | Av | 101 | Server | No_Units |
| fault_8_type | Av | 102 | Server | No_Units |
| fault_9_type | Av | 103 | Server | No_Units |
| fault_10_type | Av | 104 | Server | No_Units |
| fault_11_type | Av | 105 | Server | No_Units |
| fault_12_type | Av | 106 | Server | No_Units |
| fault_13_type | Av | 107 | Server | No_Units |
| fault_14_type | Av | 108 | Server | No_Units |
| fault_15_type | Av | 109 | Server | No_Units |
| fault_16_type | Av | 110 | Server | No_Units |
| fault_17_type | Av | 111 | Server | No_Units |
| fault_18_type | Av | 112 | Server | No_Units |
| fault_19_type | Av | 113 | Server | No_Units |
| fault_20_type | Av | 114 | Server | No_Units |
| fault_1_comp | Av | 115 | Server | No_Units |
| fault_2_comp | Av | 116 | Server | No_Units |
| fault_3_comp | Av | 117 | Server | No_Units |
| fault_4_comp | Av | 118 | Server | No_Units |
| fault_5_comp | Av | 119 | Server | No_Units |
| fault_6_comp | Av | 120 | Server | No_Units |
| fault_7_comp | Av | 121 | Server | No_Units |
| fault_8_comp | Av | 122 | Server | No_Units |
| fault_9_comp | Av | 123 | Server | No_Units |
| fault_10_comp | Av | 124 | Server | No_Units |
| fault_11_comp | Av | 125 | Server | No_Units |
| fault_12_comp | Av | 126 | Server | No_Units |
| fault_13_comp | Av | 127 | Server | No_Units |
| fault_14_comp | Av | 128 | Server | No_Units |
| fault_15_comp | Av | 129 | Server | No_Units |
| fault_16_comp | Av | 130 | Server | No_Units |
| fault_17_comp | Av | 131 | Server | No_Units |
| fault_18_comp | Av | 132 | Server | No_Units |
| fault_19_comp | Av | 133 | Server | No_Units |
| fault_20_comp | Av | 134 | Server | No_Units |
| upsetpt_write | Av | 135 | Server | No_Units |
| lowsetpt_write | Av | 136 | Server | No_Units |
| vsp_write | Av | 137 | Server | No_Units |
| load_limit_write | Av | 138 | Server | No_Units |
| tdiff_write | Av | 139 | Server | No_Units |
| fail_indic_write | Av | 140 | Server | No_Units |
| lead_comp_write | Av | 141 | Server | No_Units |
| flush_time_write | Av | 142 | Server | No_Units |
| flush_duration_write | Av | 143 | Server | No_Units |
| LP0HR – HRS 144rating 00-144 | Av | 144 | Server | No_Units |
| LP1HR – HRS 145rating 10-145 | Av | 145 | Server | No_Units |
| LP2HR – HRS 146rating 20-146 | Av | 146 | Server | No_Units |
| LP3HR – HRS 147rating 30-147 | Av | 147 | Server | No_Units |
| LP4HR – HRS 148rating 40-148 | Av | 148 | Server | No_Units |
| LP5HR – HRS 149rating 50-149 | Av | 149 | Server | No_Units |
| LP6HR – HRS 150rating 60-150 | Av | 150 | Server | No_Units |
| LP7HR – HRS 151rating 70-151 | Av | 151 | Server | No_Units |
| LP8HR – HRS 152rating 80-152 | Av | 152 | Server | No_Units |
| LP9HR – HRS 153rating 90-153 | Av | 153 | Server | No_Units |
| most_crnt_flt | Av | 154 | Server | No_Units |
| on_off_ctrl_read | Bv | 001 | Server | |
| ex1_fault | Bv | 002 | Server | |
| remote_on_off | Bv | 003 | Server | |
| ex3_fault | Bv | 004 | Server | |
| ex4_fault | Bv | 005 | Server | |
| low_chw_flow | Bv | 006 | Server | |
| low_cw_flow | Bv | 007 | Server | |
| low_chw_temp | Bv | 008 | Server | |
| c1_status | Bv | 009 | Server | |
| c2_status | Bv | 010 | Server | |
| c3_status | Bv | 011 | Server | |
| c4_status | Bv | 012 | Server | |
| c5_status | Bv | 013 | Server | |
| c6_status | Bv | 014 | Server | |
| c7_status | Bv | 015 | Server | |
| c8_status | Bv | 016 | Server | |
| c9_status | Bv | 017 | Server | |
| c10_status | Bv | 018 | Server | |
| c11_status | Bv | 019 | Server | |
| c12_status | Bv | 020 | Server | |
| c13_status | Bv | 021 | Server | |
| c14_status | Bv | 022 | Server | |
| c15_status | Bv | 023 | Server | |
| c16_status | Bv | 024 | Server | |
| c17_status | Bv | 025 | Server | |
| c18_status | Bv | 026 | Server | |
| c19_status | Bv | 027 | Server | |
| c20_status | Bv | 028 | Server | |
| c21_status | Bv | 029 | Server | |
| c22_status | Bv | 030 | Server | |
| c23_status | Bv | 031 | Server | |
| c24_status | Bv | 032 | Server | |
| on_off_ctrl_write | Bv | 033 | Server |
Heat Pumps
| Map_Descriptor_Name | Data_Type | Address | Function | Units |
|---|---|---|---|---|
| CAPACITY | Av | 001 | SERVER | No_Units |
| DEMAND | Av | 002 | SERVER | No_Units |
| NUMBER OF COMPS | Av | 003 | SERVER | No_Units |
| CURRENT FAULTS | Av | 004 | SERVER | No_Units |
| OPERATING MODE | Av | 005 | SERVER | No_Units |
| ENT LOAD TEMP | Av | 006 | SERVER | No_Units |
| LEV LOAD TEMP | Av | 007 | SERVER | No_Units |
| ENT SOURCE TEMP | Av | 008 | SERVER | No_Units |
| LEV SOURCE TEMP | Av | 009 | SERVER | No_Units |
| COOL UPSETPT | Av | 010 | SERVER | No_Units |
| COOL LOWSETPT | Av | 011 | SERVER | No_Units |
| COOL VSP | Av | 012 | SERVER | No_Units |
| COOL TDIFF | Av | 013 | SERVER | No_Units |
| HEAT UPSETPT | Av | 014 | SERVER | No_Units |
| HEAT LOWSETPT | Av | 015 | SERVER | No_Units |
| HEAT VSP | Av | 016 | SERVER | No_Units |
| HEAT TDIFF | Av | 017 | SERVER | No_Units |
| LOAD LIMIT | Av | 018 | SERVER | No_Units |
| FAIL INDICATOR | Av | 019 | SERVER | No_Units |
| LEAD COMPRESSOR | Av | 020 | SERVER | No_Units |
| FLUSH TIME | Av | 021 | SERVER | No_Units |
| FLUSH DURATION | Av | 022 | SERVER | No_Units |
| MONTH | Av | 023 | SERVER | No_Units |
| DAY | Av | 024 | SERVER | No_Units |
| YEAR | Av | 025 | SERVER | No_Units |
| HOUR | Av | 026 | SERVER | No_Units |
| MINUTE | Av | 027 | SERVER | No_Units |
| C1 SUCTION TEMP | Av | 028 | SERVER | No_Units |
| C1 LLW TEMP | Av | 029 | SERVER | No_Units |
| C1 LSW TEMP | Av | 030 | SERVER | No_Units |
| C2 SUCTION TEMP | Av | 031 | SERVER | No_Units |
| C2 LLW TEMP | Av | 032 | SERVER | No_Units |
| C2 LSW TEMP | Av | 033 | SERVER | No_Units |
| C3 SUCTION TEMP | Av | 034 | SERVER | No_Units |
| C3 LLW TEMP | Av | 035 | SERVER | No_Units |
| C3 LSW TEMP | Av | 036 | SERVER | No_Units |
| C4 SUCTION TEMP | Av | 037 | SERVER | No_Units |
| C4 LLW TEMP | Av | 038 | SERVER | No_Units |
| C4 LSW TEMP | Av | 039 | SERVER | No_Units |
| C5 SUCTION TEMP | Av | 040 | SERVER | No_Units |
| C5 LLW TEMP | Av | 041 | SERVER | No_Units |
| C5 LSW TEMP | Av | 042 | SERVER | No_Units |
| C6 SUCTION TEMP | Av | 043 | SERVER | No_Units |
| C6 LLW TEMP | Av | 044 | SERVER | No_Units |
| C6 LSW TEMP | Av | 045 | SERVER | No_Units |
| C7 SUCTION TEMP | Av | 046 | SERVER | No_Units |
| C7 LLW TEMP | Av | 047 | SERVER | No_Units |
| C7 LSW TEMP | Av | 048 | SERVER | No_Units |
| C8 SUCTION TEMP | Av | 049 | SERVER | No_Units |
| C8 LLW TEMP | Av | 050 | SERVER | No_Units |
| C8 LSW TEMP | Av | 051 | SERVER | No_Units |
| C9 SUCTION TEMP | Av | 052 | SERVER | No_Units |
| C9 LLW TEMP | Av | 053 | SERVER | No_Units |
| C9 LSW TEMP | Av | 054 | SERVER | No_Units |
| C10 SUCTION TEMP | Av | 055 | SERVER | No_Units |
| C10 LLW TEMP | Av | 056 | SERVER | No_Units |
| C10 LSW TEMP | Av | 057 | SERVER | No_Units |
| C11 SUCTION TEMP | Av | 058 | SERVER | No_Units |
| C11 LLW TEMP | Av | 059 | SERVER | No_Units |
| C11 LSW TEMP | Av | 060 | SERVER | No_Units |
| C12 SUCTION TEMP | Av | 061 | SERVER | No_Units |
| C12 LLW TEMP | Av | 062 | SERVER | No_Units |
| C12 LSW TEMP | Av | 063 | SERVER | No_Units |
| C13 SUCTION TEMP | Av | 064 | SERVER | No_Units |
| C13 LLW TEMP | Av | 065 | SERVER | No_Units |
| C13 LSW TEMP | Av | 066 | SERVER | No_Units |
| C14 SUCTION TEMP | Av | 067 | SERVER | No_Units |
| C14 LLW TEMP | Av | 068 | SERVER | No_Units |
| C14 LSW TEMP | Av | 069 | SERVER | No_Units |
| C15 SUCTION TEMP | Av | 070 | SERVER | No_Units |
| C15 LLW TEMP | Av | 071 | SERVER | No_Units |
| C15 LSW TEMP | Av | 072 | SERVER | No_Units |
| C16 SUCTION TEMP | Av | 073 | SERVER | No_Units |
| C16 LLW TEMP | Av | 074 | SERVER | No_Units |
| C16 LSW TEMP | Av | 075 | SERVER | No_Units |
| C17 SUCTION TEMP | Av | 076 | SERVER | No_Units |
| C17 LLW TEMP | Av | 077 | SERVER | No_Units |
| C17 LSW TEMP | Av | 078 | SERVER | No_Units |
| C18 SUCTION TEMP | Av | 079 | SERVER | No_Units |
| C18 LLW TEMP | Av | 080 | SERVER | No_Units |
| C18 LSW TEMP | Av | 081 | SERVER | No_Units |
| C19 SUCTION TEMP | Av | 082 | SERVER | No_Units |
| C19 LLW TEMP | Av | 083 | SERVER | No_Units |
| C19 LSW TEMP | Av | 084 | SERVER | No_Units |
| C20 SUCTION TEMP | Av | 085 | SERVER | No_Units |
| C20 LLW TEMP | Av | 086 | SERVER | No_Units |
| C20 LSW TEMP | Av | 087 | SERVER | No_Units |
| C21 SUCTION TEMP | Av | 088 | SERVER | No_Units |
| C21 LLW TEMP | Av | 089 | SERVER | No_Units |
| C21 LSW TEMP | Av | 090 | SERVER | No_Units |
| C22 SUCTION TEMP | Av | 091 | SERVER | No_Units |
| C22 LLW TEMP | Av | 092 | SERVER | No_Units |
| C22 LSW TEMP | Av | 093 | SERVER | No_Units |
| C23 SUCTION TEMP | Av | 094 | SERVER | No_Units |
| C23 LLW TEMP | Av | 095 | SERVER | No_Units |
| C23 LSW TEMP | Av | 096 | SERVER | No_Units |
| C24 SUCTION TEMP | Av | 097 | SERVER | No_Units |
| C24 LLW TEMP | Av | 098 | SERVER | No_Units |
| C24 LSW TEMP | Av | 099 | SERVER | No_Units |
| C1 FAULTS | Av | 100 | SERVER | No_Units |
| C2 FAULTS | Av | 101 | SERVER | No_Units |
| C3 FAULTS | Av | 102 | SERVER | No_Units |
| C4 FAULTS | Av | 103 | SERVER | No_Units |
| C5 FAULTS | Av | 104 | SERVER | No_Units |
| C6 FAULTS | Av | 105 | SERVER | No_Units |
| C7 FAULTS | Av | 106 | SERVER | No_Units |
| C8 FAULTS | Av | 107 | SERVER | No_Units |
| C9 FAULTS | Av | 108 | SERVER | No_Units |
| C10 FAULTS | Av | 109 | SERVER | No_Units |
| C11 FAULTS | Av | 110 | SERVER | No_Units |
| C12 FAULTS | Av | 111 | SERVER | No_Units |
| C13 FAULTS | Av | 112 | SERVER | No_Units |
| C14 FAULTS | Av | 113 | SERVER | No_Units |
| C15 FAULTS | Av | 114 | SERVER | No_Units |
| C16 FAULTS | Av | 115 | SERVER | No_Units |
| C17 FAULTS | Av | 116 | SERVER | No_Units |
| C18 FAULTS | Av | 117 | SERVER | No_Units |
| C19 FAULTS | Av | 118 | SERVER | No_Units |
| C20 FAULTS | Av | 119 | SERVER | No_Units |
| C21 FAULTS | Av | 120 | SERVER | No_Units |
| C22 FAULTS | Av | 121 | SERVER | No_Units |
| C23 FAULTS | Av | 122 | SERVER | No_Units |
| C24 FAULTS | Av | 123 | SERVER | No_Units |
| FAULT 1 COMP # | Av | 124 | SERVER | No_Units |
| FAULT 2 COMP # | Av | 125 | SERVER | No_Units |
| FAULT 3 COMP # | Av | 126 | SERVER | No_Units |
| FAULT 4 COMP # | Av | 127 | SERVER | No_Units |
| FAULT 5 COMP # | Av | 128 | SERVER | No_Units |
| FAULT 6 COMP # | Av | 129 | SERVER | No_Units |
| FAULT 7 COMP # | Av | 130 | SERVER | No_Units |
| FAULT 8 COMP # | Av | 131 | SERVER | No_Units |
| FAULT 9 COMP # | Av | 132 | SERVER | No_Units |
| FAULT 10 COMP # | Av | 133 | SERVER | No_Units |
| FAULT 11 COMP # | Av | 134 | SERVER | No_Units |
| FAULT 12 COMP # | Av | 135 | SERVER | No_Units |
| FAULT 13 COMP # | Av | 136 | SERVER | No_Units |
| FAULT 14 COMP # | Av | 137 | SERVER | No_Units |
| FAULT 15 COMP # | Av | 138 | SERVER | No_Units |
| FAULT 16 COMP # | Av | 139 | SERVER | No_Units |
| FAULT 17 COMP # | Av | 140 | SERVER | No_Units |
| FAULT 18 COMP # | Av | 141 | SERVER | No_Units |
| FAULT 19 COMP # | Av | 142 | SERVER | No_Units |
| FAULT 20 COMP # | Av | 143 | SERVER | No_Units |
| FAULT 1 TYPE | Av | 144 | SERVER | No_Units |
| FAULT 2 TYPE | Av | 145 | SERVER | No_Units |
| FAULT 3 TYPE | Av | 146 | SERVER | No_Units |
| FAULT 4 TYPE | Av | 147 | SERVER | No_Units |
| FAULT 5 TYPE | Av | 148 | SERVER | No_Units |
| FAULT 6 TYPE | Av | 149 | SERVER | No_Units |
| FAULT 7 TYPE | Av | 150 | SERVER | No_Units |
| FAULT 8 TYPE | Av | 151 | SERVER | No_Units |
| FAULT 9 TYPE | Av | 152 | SERVER | No_Units |
| FAULT 10 TYPE | Av | 153 | SERVER | No_Units |
| FAULT 11 TYPE | Av | 154 | SERVER | No_Units |
| FAULT 12 TYPE | Av | 155 | SERVER | No_Units |
| FAULT 13 TYPE | Av | 156 | SERVER | No_Units |
| FAULT 14 TYPE | Av | 157 | SERVER | No_Units |
| FAULT 15 TYPE | Av | 158 | SERVER | No_Units |
| FAULT 16 TYPE | Av | 159 | SERVER | No_Units |
| FAULT 17 TYPE | Av | 160 | SERVER | No_Units |
| FAULT 18 TYPE | Av | 161 | SERVER | No_Units |
| FAULT 19 TYPE | Av | 162 | SERVER | No_Units |
| FAULT 20 TYPE | Av | 163 | SERVER | No_Units |
| LP0HR – HRS Cooling -00-09 | aV | 164 | Server | No_Units |
| LP1HR – HRS Cooling -10-19 | aV | 165 | Server | No_Units |
| LP2HR – HRS Cooling -20-29 | aV | 166 | Server | No_Units |
| LP3HR – HRS Cooling -30-39 | aV | 167 | Server | No_Units |
| LP4HR – HRS Cooling -40-49 | aV | 168 | Server | No_Units |
| LP5HR – HRS Cooling -50-59 | aV | 169 | Server | No_Units |
| LP6HR – HRS Cooling -60-69 | aV | 170 | Server | No_Units |
| LP7HR – HRS Cooling -70-79 | aV | 171 | Server | No_Units |
| LP8HR – HRS Cooling -80-89 | aV | 172 | Server | No_Units |
| LP9HR – HRS Cooling -90-100 | aV | 173 | Server | No_Units |
| HLP0HR – HRS Heating – 0-9 | aV | 174 | Server | No_Units |
| HLP1HR – HRS Heating – 10-19 | aV | 175 | Server | No_Units |
| HLP2HR – HRS Heating – 20-29 | aV | 176 | Server | No_Units |
| HLP3HR – HRS Heating – 30-39 | aV | 177 | Server | No_Units |
| HLP4HR – HRS Heating – 40-49 | aV | 178 | Server | No_Units |
| HLP5HR – HRS Heating – 50-59 | aV | 179 | Server | No_Units |
| HLP6HR – HRS Heating – 60-69 | aV | 180 | Server | No_Units |
| HLP7HR – HRS Heating – 70-79 | aV | 181 | Server | No_Units |
| HLP8HR – HRS Heating – 80-89 | aV | 182 | Server | No_Units |
| HLP9HR – HRS Heating – 90-100 | aV | 183 | Server | No_Units |
| COOL UPSETPT | Av | 184 | SERVER | No_Units |
| COOL LOWSETPT | Av | 185 | SERVER | No_Units |
| COOL VSP | Av | 186 | SERVER | No_Units |
| COOL TDIFF | Av | 187 | SERVER | No_Units |
| HEAT UPSETPT | Av | 188 | SERVER | No_Units |
| HEAT LOWSETPT | Av | 189 | SERVER | No_Units |
| HEAT VSP | Av | 190 | SERVER | No_Units |
| HEAT TDIFF | Av | 191 | SERVER | No_Units |
| LOAD LIMIT | Av | 192 | SERVER | No_Units |
| FAIL INDICATOR | Av | 193 | SERVER | No_Units |
| LEAD COMPRESSOR | Av | 194 | SERVER | No_Units |
| FLUSH TIME | Av | 195 | SERVER | No_Units |
| FLUSH DURATION | Av | 196 | SERVER | No_Units |
| OPERATING MODE | Av | 197 | SERVER | No_Units |
| MOST CURRENT FLT | Av | 198 | SERVER | No_Units |
| HEAT DELAY (READ) | Av | 199 | SERVER | No_Units |
| HEAT DELAY (wRITE) | Av | 200 | SERVER | No_Units |
| on_off_ctrl_read | Bv | 001 | Server | |
| ex1_fault | Bv | 002 | Server | |
| remote_on_off | Bv | 003 | Server | |
| ex3_fault | Bv | 004 | Server | |
| ex4_fault | Bv | 005 | Server | |
| low_chw_flow | Bv | 006 | Server | |
| low_cw_flow | Bv | 007 | Server | |
| LOW LLW TEMP | Bv | 008 | Server | |
| LOW LSW TEMP | Bv | 009 | Server | |
| c1_status | Bv | 010 | Server | |
| c2_status | Bv | 011 | Server | |
| c3_status | Bv | 012 | Server | |
| c4_status | Bv | 013 | Server | |
| c5_status | Bv | 014 | Server | |
| c6_status | Bv | 015 | Server | |
| c7_status | Bv | 016 | Server | |
| c8_status | Bv | 017 | Server | |
| c9_status | Bv | 018 | Server | |
| c10_status | Bv | 019 | Server | |
| c11_status | Bv | 020 | Server | |
| c12_status | Bv | 021 | Server | |
| c13_status | Bv | 022 | Server | |
| c14_status | Bv | 023 | Server | |
| c15_status | Bv | 024 | Server | |
| c16_status | Bv | 025 | Server | |
| c17_status | Bv | 026 | Server | |
| c18_status | Bv | 027 | Server | |
| c19_status | Bv | 028 | Server | |
| c20_status | Bv | 029 | Server | |
| c21_status | Bv | 030 | Server | |
| c22_status | Bv | 031 | Server | |
| c23_status | Bv | 032 | Server | |
| c24_status | Bv | 033 | Server | |
| on_off_ctrl_write | Bv | 034 | Server |
Manuals and Data Sheets
– FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller
– FieldServer Driver Manual – Serial – FS-8705-18 – Multistack Comput25 Master Controller
– Multistack – The Modular Water Chiller – Master Control User Manual
– Multistack – The Modular Water Chiller - BACnet Portal Technical Manual (MS20/30/50 Application – BACnet over TCP/IP )