Table 3 Remapped Registers

Kholer Decision Maker 550 Modbus Register Map / Point List

 

Table 3: Remapped Registers

Register Mapped to: Description
40740 41550 Emergency Stop
40741 41551 Overspeed
40742 41552 Overcrank
40743 41553 High Coolant Temperature Shutdown
40744 41554 Oil Pressure Shutdown
40745 41555 Low Coolant Temperature
40746 41556 Low Fuel
40747 41557 High Coolant Temperature Warning
40748 41558 Oil Pressure Warning
40749 41559 Master Not In Auto
40750 41560 NFPA 110 Fault
40751 41561 Low Battery Voltage
40752 41562 High Battery Voltage
40753 41563 Battery Charger Fault
40754 41564 System Ready
40755 41565 Loss of ECM Comm
40756 41566 No Oil Pressure Signal
40757 41567 High Oil Temperature Shutdown
40758 41568 No Coolant Temperature Signal
40759 41569 Low Coolant Level
40760 41570 Speed Sensor Fault
40761 41571 Locked Rotor
40762 41572 Master Switch Error
40763 41573 Master Switch Open
40764 41574 Master Switch Off
40765 41575 AC Sensing Loss
40766 41576 Over Voltage
40767 41577 Under Voltage
40768 41578 Weak Battery
40769 41579 Over Frequency
40770 41580 Under Frequency
40771 41581 Load Shed kW Overload
40772 41582 Load Shed kW Under Frequency
40773 41583 Over Current
40774 41584 EPS Supplying Load
40775 41585 Internal Fault
40776 41586 Engine Cooldown Delay
40777 41587 Engine Start Delay
40778 41588 Starting Aid
40779 41589 Generator Running
40780 41590 Air Damper Control
40781 41591 Ground Fault
40782 41592 EEPROM Write Failure
40783 41593 Critical Overvoltage
40784 41594 Alternator Protect Shutdown
40785 41595 Air Damper Indicator
40786 41596 Digital Input 01
40787 41597 Digital Input 02
40788 41598 Digital Input 03
40789 41599 Digital Input 04
40790 41600 Digital Input 05
40791 41601 Digital Input 06
40792 41602 Digital Input 07
40793 41603 Digital Input 08
40794 41604 Digital Input 09
40795 41605 Digital Input 10
40796 41606 Digital Input 11
40797 41607 Digital Input 12
40798 41608 Digital Input 13
40799 41609 Digital Input 14
40800 41610 Digital Input 15
40801 41611 Digital Input 16
40802 41612 Digital Input 17
40803 41613 Digital Input 18
40804 41614 Digital Input 19
40805 41615 Digital Input 20
40806 41616 Digital Input 21
40807 41617 Analog Input 01
40808 41618 Analog Input 02
40809 41619 Analog Input 03
40810 41620 Analog Input 04
40811 41621 Analog Input 05
40812 41622 Analog Input 06
40813 41623 Analog Input 07
40814 41624 Reserved for additional input
40815 41625 Reserved for additional input
40816 41626 Reserved for additional input
40817 41627 Reserved for additional input
40818 41628 Reserved for additional input
40819 41629 Reserved for additional input
40820 41630 Reserved for additional input
40821 41631 Reserved for additional input
40822 41632 Defined Common Fault
40823 41633 Software Controlled RDO#1
40824 41634 Software Controlled RDO#2
40825 41635 Software Controlled RDO#3
40826 41636 Software Controlled RDO#4
40827 41637 Reserved for factory use
40828 41638 Reserved for factory use
40829 41639 Reserved for factory use
40830 41640 Reserved for factory use
40831 41641 Reserved for factory use
40832 41642 Reserved for factory use
40833 41643 Reserved for factory use
40834 41644 Reserved for factory use
40835 41645 Reserved for factory use
40836 41646 Reserved for factory use
40837 41647 Reserved for factory use

 

See:

Table 1: Register Map Guide

Table 2: Modbus Registers

Table 4: System Event Codes

Table 5: System Event Code Table