Kholer Decision Maker 550 Modbus Register Map / Point List
Table 1: Register Map Guide
| Description | Registers |
|---|---|
| Monitoring | 40001–40083 |
| Electrical Output | 40001–40032 |
| Engine Status | 40033–40060 |
| Analog Input Status | 40061–40076 |
| Digital Input Status | 40077–40078 |
| Controller Status | 40079–40083 |
| Maintenance | 40084–40112 |
| Time/Date | 40113–40115 |
| Time Delay Settings | 40116–40124 |
| Settings and Setpoints | 40125–40146 |
| Factory Setup | 40147–40226 |
| Digital Input Setup | 40227–40499 |
| Analog Input Setup | 40500–40739 |
| Remapped Registers * | 40740–40837 |
| Relay Driver Output Status (see Section 2.5.4) | 40838–40839 |
| Relay Driver Output Setup | 40840–40870 |
| Event History | 40871–41270 |
| Customer-Defined Character Strings | 41271–41295 |
| Reserved and Write-Only Registers | 41296–41305 |
| Remote Functions | 41306–41413 |
| Reserved for Factory Use | 41314–41499 |
| “System Event Stack (status of fault warnings and shutdowns, inputs, outputs, and MDEC alarms; see Section 2.5.6.)” | 41500–41515 |
| Reserved for Wireless Monitor | 41516–41536 |
| Reserved | 41537–41549 |
| Defined Common Faults (Define/Inspect) | 41550–41805 |
| Reserved | 41806–49998 |
| Device ID | 49999 |
| * Registers 40740–40837 have been mapped to 41550–41647 (Defined Common Faults) for compatibility with earlier versions. See Table 3 |