CAS Newsletter October 2011
|
IN THIS ISSUE
|
|
Every Timezone
No more head scratching and finger counting. Everytimezone.com does the timezone math for you. |
CAS 2700-21 Mitsubishi UPS Gateway Device
The Mitsibishi UPS Gateway monitors and controls UPS’s that support SEC protocol using BACnet, Modbus or Web. It cycles though a list of preconfigured tasks to request values from Veeder Root devices. The values are then stored in an internal database. The values can be served in serveral formats, including BACnet IP, Modbus RTU, Modbus TCP, and Web Server. The driver is configured using a web browser, where the user can configure both the Gateway and the serving capabilities. The web browser can also be used to aid in debugging and can serve the current data to a web page for viewing. The Mitsubishi UPS Gateway device can be configured from the following web page: Automation professionals will need to have a web browser for web serving, configuration, and debugging. We recommend Firefox or Chrome. Mitsubishi UPS device is required if testing is needed. LogView4net or WireShark are recommended for troubleshooting. CAS developed this device to support Mitsubishi UPS 7011A, 2033C, 2033D, 9800AE, 9900A and 9900B. It was tested using the DP-A12-1.OK UPS device.
For further information about CAS 2700-21 Mitsubishi UPS Gateway Device, please visit http://www.chipkin.com/cas-2700-21-mitsubishi-ups-gateway |
BACnet Key ActivationThis step-by-step article explains how to activate CAS BACnet Key. First of all, a user should make sure that he or she has downloaded CAS BACnet Explorer on the computer before activating the BACnet Key. Then, click to Run CAS BACnet Explorer.
If the product key has expired or is invalid (or during the first time registration), an error message “FYI #017” will pop up. It will explain to the user that a maximum of three free software demo keys can be requested to evaluate CAS BACnet Explorer from the License dialog. Each key expires after 60 minutes upon successful activation. If user has a valid product key but is still receiving the same error message, please make sure that the USB product key is connected to the computer and then re-start the software.
Otherwise, click OK and the License dialog will pop up. Enter a valid email address here and click “Request a key” button. Read the instructions on the next screen and click OK.
A webpage with user’s information will appear. Verify the information and click “Request a key” button, it will then bring the user to a confirmation page.
Each trial key can be renewed three times, however, if a user needs to evaluate our CAS BACnet Explorer for more than an hour or on a different computer, we would suggest purchasing an USB-protection-key to avoid multiple activation processes. If user did not get the error message in the first place, he or she can still request a new product key from the Licence dialog. It can be done by clicking the “Settings” button on the main dialog, then select “License” on the left hand side. Please read our useful FAQ, or contact us directly if we can be of further assistance. |
Simplex 4100 Configuration
First of all, wait passively for the events to be sent from the panel. Above image shows Map Descriptors which capture event data from different Cards. A single point can report 8 states. These 8 states are stored as bits inside a storage word and the word can be served on BACnet or Modbus as a number, or it can be unpacked into individual bits and served bit by bit. For example: 1?0?0 reports an alarm. The value 1 is stored in the word allocated for this point. Thus, if 1?0?0 was in an alarm and trouble at the same time, the value 17 = 1 + 16 is stored. Bit Identifier Description 0 F Fire Alarm For example: Bacnet Object AI(101) contains the number.
Bacnet Object BI(101) contains the alarm state. The server map descriptor references DA_C_001b (a bit array) is displayed. The bit array gets its data from a Move. Then, the Move unpacks bits from the number values into individual bits.
Note that each BACnet object must have a unique (Type,Object_ID) pair. When a message arrives from the panel, the driver checks the c-p-s of the xpoint message and looks for a matching Map Descriptor. Let’s say a message comes from 18-2(-0) (implied). The driver looks for a Map Descriptor whose card=18, and it finds the Map Descriptor whose name is ZoneData . If it sees in the Map Descriptor that sim4100_sub=1, that means the driver reserves space for 1 subpoint(s) per point. Once the Map Descriptor has been found, the driver knows which Data Array to use. Thus: Data Array DA_ZONES offset 0 is for 18-0-0 If sim4100_sub=10 (instead of 1), this means that the driver reserves space for 10 subpoint(s) per point. Thus: Data Array DA_ZONES offset 0 is for 18-0-0 DA_ZONES offset 1 is for 18-0-1 Thus the data for 18-2-0 will be stored in offset 20. If a message arrives and the driver does not find a matching card, then the message is discarded. The data gets stored when a point status is obtained, the FieldServer will write one word of data to a Data Array. |
Microsoft Surface CES 2011 DemoBeyond touch.
Please visit our Facebook Page to watch the video. |
|
Safety Picture
|






















