Metasys N2 by JCI Knowledge and Solutions
Up one levelJohnson Controls Metasys N2 by JCI Cable Specification
What kind of cable should you use for Johnson Controls Metasys N2 by JCI Open installations. How should the cable be installed, biased and terminated. How to trouble shoot a N2 Network. These and other issues are addressed in this Metasys Network Technical Manual.
Sample of Typical N2 Traffic
7 [ 660] TX : >2211000288[CR]
41 [ 701] RX : A0000000000E0[CR]
20 [ 734] TX : >1712060293[CR]
33 [ 767] RX : A0060[CR]
6 [ 778] TX : >1812060294[CR]
46 [ 825] RX : A0060[CR]
7 [ 837] TX : >2311000289[CR]
39 [ 876] RX : A0000000000E0[CR]
6 [ 894] TX : >0C12010299[CR]
33 [ 927] RX : A0060[CR]
6 [ 938] TX : >0E1201029B[CR]
39 [ 977] RX : A0060[CR]
6 [ 988] TX : >241100028A[CR]
40 [ 1028] RX : A0000000000E0[CR]
6 [ 1048] TX : >251100028B[CR]
37 [ 1085] RX : A0000000000E0[CR]
6 [ 1107] TX : >0D1201029A[CR]
40 [ 1147] RX : A0060[CR]
6 [ 1158] TX : >261100028C[CR]
39 [ 1197] RX : A0000000000E0[CR]
7 [ 1216] TX : >0D1104029C[CR]
45 [ 1261] RX : A0000000000E0[CR]
40 [ 1310] TX : >17110A029D[CR]
43 [ 1353] RX : A0000000000E0[CR]
13 [ 1376] TX : >271100028D[CR]
36 [ 1412] RX : A0000000000E0[CR]
8 [ 1432] TX : >18110A029E[CR]
41 [ 1473] RX : A0000000000E0[CR]
7 [ 1491] TX : >2A11000297[CR]
39 [ 1530] RX : A0000000000E0[CR]
7 [ 1548] TX : >2B11000298[CR]
42 [ 1590] RX : A0000000000E0[CR]
7 [ 1607] TX : >0C1104029B[CR]
36 [ 1644] RX : A0000000000E0[CR]
7 [ 1662] TX : >0E1104029D[CR]
43 [ 1705] RX : A0000000000E0[CR]
7 [ 1722] TX : >2C11000299[CR]
39 [ 1761] RX : A0000000000E0[CR]
6 [ 1784] TX : >1712060293[CR]
32 [ 1817] RX : A0060[CR]
17 [ 1840] TX : >1812060294[CR]
36 [ 1876] RX : A0060[CR]
59 [ 1940] TX : >0C12010299[CR]
39 [ 1979] RX : A0060[CR]
8 [ 1987] TX : >2D1100029A[CR]
38 [ 2025] RX : A0000000000E0[CR]
7 [ 2042] TX : >0E1201029B[CR]
37 [ 2079] RX : A0060[CR]
6 [ 2090] TX : >2E1100029B[CR]
37 [ 2127] RX : A0000000000E0[CR]
7 [ 2149] TX : >3011000287[CR]
36 [ 2185] RX : A0000000000E0[CR]
7 [ 2207] TX : >0D1201029A[CR]
33 [ 2240] RX : A0060[CR]
8 [ 2254] TX : >2F1100029C[CR]
39 [ 2293] RX : A0000000000E0[CR]
7 [ 2310] TX : >0D1104029C[CR]
44 [ 2354] RX : A0000000000E0[CR]
7 [ 2371] TX : >17110A029D[CR]
39 [ 2410] RX : A0000000000E0[CR]
7 [ 2432] TX : >3111000288[CR]
37 [ 2469] RX : A0000000000E0[CR]
8 [ 2494] TX : >2011000286[CR]
41 [ 2536] RX : A0000000000E0[CR]
7 [ 2553] TX : >18110A029E[CR]
44 [ 2597] RX : A0000000000E0[CR]
7 [ 2614] TX : >2111000287[CR]
38 [ 2652] RX : A0000000000E0[CR]
7 [ 2675] TX : >0C1104029B[CR]
37 [ 2712] RX : A0000000000E0[CR]
8 [ 2736] TX : >0E1104029D[CR]
41 [ 2777] RX : A0000000000E0[CR]