Mapping Data Types from BACnet MSTP to Metasys N2 on Quickserver Gateway

 

Following aspects are to be considered while doing configuration of a Quickserver Gateway for the data points from BACnet MSTP to Metasys N2.

The data types supported by BACnet MSTP are;

AI Analogue Input
AO Analogue Output
AV Analogue Value
BI Binary Input
BO Binary Output
Bv Binary Value
MI Multi-state Input
MO Multi-state Output
MV Multi-state Value

 

The data types supported by Metasys N2 are;

AI Analogue Input
AO Analogue Output
BI Binary Input
BO Binary Output
ADI Integer
BD Byte
ADF Float Registe

 

Following table shows how the respective data types of BACnet are configured on Metasys N2;

 

BACnet Metasys N2
AI AI
AO AO
AV ADF
BI BI
BO BO
BV BD (Byte in config file)
MI ADI (Integer in config file)
MO ADF (Float_reg in config file)
MV ADF (Float_reg in config file)