FS-8700-30 - YorkTalk

Up one level

FieldServer Driver - Serial
FS-8700-30
YorkTalk

Driver Code: SPEC
Version: 1.00

Device Options:

  1. York Translator - The recommended option: A direct RS232 connection is made to the chiller. This is a very cost effective option as a single FieldServer can support 8 simultaneous connections. The aggregate bandwidth is then also 8 times higher than in the case of a single multidrop connection to 8 devices.
  2. XL Translator - A RS232 connection is made to the XL Translator (also known as ISN LDC 17 - Link Data Controller), which in turn communicates with York devices via RS485. For this configuration, the York Chillers must be fitted with the "Linc Chiller" module to allow compatibility with the LDC's RS485 network.
  3. MicroGateway - A RS232 connection is made to the MicroGateway, which in turn communicates with York devices via RS485. For this configuration, the York Chillers must be fitted with the "Linc Chiller" module to allow compatibility with the LDC's RS485 network.

Map of the FieldServer Yorktalk Client driver (XL Translator, York Translator)

8051 address York Talk Block (feature, section) York Talk Line Read/Write Comment
0 -> 81 f02s01 P01 -> P81 Read Only Read chiller status of length 82. Any single point can be read, or sub_blocks of any inclusive address range can be read.
82 f01s01 P01 Read or Write First set_point.
83 f01s02 P01 Read or Write Second set_point block.
84 f01s02 P02 Read or Write Same as above
85 none none Read or Write Enumerated York_Talk Client state machine error code. 0.0 means none. Write will clear
86 none none Read or Write York Talk returned error code. 0.0 means none. Will contain last logged error. Write will clear.

Notes (XL Translator, York Translator) :

The following combinations can be read:
  • 0-81 or any subset thereof
  • 82 by itself
  • 83-84 or any subset thereof
  • 85 by itself
  • 86 by itself

The following combinations can be written to:

  • 82 by itself. Only the value 0.0 (OFF) and 1.0 (ON)
  • 83 by itself
  • 84 by itself
  • 85 by itself. Will reset latched error code to 0.0
  • 86 by itself. Will reset latched error code to 0.0

The system is offset sensitive allowing single data blocks but multiple scan blocks.

Map of the FieldServer Yorktalk Client driver (MicroGateway)

The MicroGateway mode allows the f, s and p parameters (feature, section and page) to be specified directly for write messages, allowing all single-value fields (such as set points and digital outputs) to be written. For read messages, only f54 is available, but the section (s parameter) can be specified as required to address different devices.