FS-8700-26 - Notifier 200/300/400

Up one level

FieldServer Driver - Serial
FS-8700-26
Notifier 200/300/400

Driver Code: NOTA
Version 1.00
Devices Supported: Notifier AFP200, AFP300 and AFP400 Fire Alarm Panels
Interface: RS-232 utilizing Notifier Fire Alarm Panel Connector adapter
Baud: 2400
Parity: Even (AFP200); None (AFP300/AFP400)
Data Bits: 7 (AFP200); 8 (AFP300/AFP400)
Handshaking: None

Device Types Supported

Detectors
  • Alarms
  • Troubles
  • Pre-Alarms
  • Not Installed

Modules

  • Alarms
  • Troubles
  • Pre-Alarms
  • Not Installed

Zones

  • Only if the default "Zone xx" Labeling (where xx is the zone number) is used. If custom zone descriptions are used, they will not be reported to the driver.

System Alarm
Module Type Codes Supported

  • Monitor
  • Pull Station
  • Smoke Detect
  • Blank
  • Waterflow
  • Supervisory
  • Tamper
  • Hazard Alert
  • Fire Control
  • Abort Switch
  • Man-Release
  • Silence
  • System Reset
  • Evacuate
  • PAS Inhibit
  • Trouble Mon
  • Security
  • Tele Page
  • Allcall Page
  • Man Rel. Delay
  • Second Shot
  • Sprinkler Sys
  • Comb. Monitor

Note that status on control devices is not supported. As zones can be reported, this should not be a problem.