FS8705-14 - Harshaw Trane XML Schedule

Up one level

FieldServer Driver
FS8705-14
Harshaw Trane
-
Driver for
XML HVAC Building Automation Schedules

 

 

Description

 

The XML Schedule driver will use the HTTP protocol over TCP/IP to poll for XML Schedule data from a configurable URL. The data will be parsed according to fixed filter criteria and stored in Data Array locations that are configurable for each zone. This data may then be served or written to a remote device/system by using another FieldServer driver such as BACnet/IP.

 

The Driver will process an XML file looking for <Schedule> objects. It will identify the zone. For each zone the driver will compare the Start time against the FieldServer current time and find the <Schedule> object for that zone that is currently active or that will be active next. The start date and time will be extracted from the object and stored in FieldServer Data array configured for that zone. Each element of the date and time will be stored in a different data array location.

 

Since FieldServer allows any Data Array locations to be mapped onto another protocol it will be possible to serve or write this data to another device using another protocol such as Bacnet/IP.

 

For example – if this object

 

<Schedule>

<Zone>MRC Zone 1</Zone>

<Start>2008-10-07T11:30:00</Start>

<End>2008-10-07T14:30:00</End>

</Schedule>

 

 

The driver allows for a remote device to periodically synch the time of the FieldServer.

 

The driver will be a client only. This means that it can poll for the XML data but will not be able to process unsolicited XML pages sent to the FieldServer.

 

Server functionality is provided only to support our ongoing quality assurance program by facilitating automated testing of the driver. It is not documented or supported. If required please contact the FST sales group to discuss your requirements.

 

 

Max Nodes Supported

 

FieldServer Mode Nodes Comments
Client Many The FieldServer will be able to poll multiple XML servers
Server 0 Not supported or documented.

 

 

Formal Driver Type

Ethernet

Client

 

Compatibility Matrix

 

FieldServer Model Compatible with this driver
FS-x2010 Yes,

FS-x2011

Yes,
FS-x40 Yes,
FS-X30 Yes,

 

Connection Information

 

Connection type:       Ethernet TCP/IP

Hardware interface:   FieldServer Ethernet Adapters ( N1 / N2 as available)

Multidrop Capability   No

Source Port              80 – Configurable

 

 

Devices tested

 

Device Tested (FACTORY, SITE)
   
   

 

Connection configurations

Multiple upstream protocols and connection supported. See list of FieldServer Drivers.

 

Driver Functionality

 

The Driver will process an XML file looking for <Schedule> objects. It will identify the zone. For each zone the driver will compare the Start time against the FieldServer current time and find the <Schedule> object for that zone that is currently active or that will be active next. The start date and time will be extracted from the object and stored in FieldServer Data array configured for that zone. Each element of the date and time will be stored in a different data array location.

 

Since FieldServer allows any Data Array locations to be mapped onto another protocol it will be possible to serve or write this data to another device using another protocol such as Bacnet/IP.

 

For example – if this object

 

<Schedule>

<Zone>MRC Zone 1</Zone>

<Start>2008-10-07T11:30:00</Start>

<End>2008-10-07T14:30:00</End>

</Schedule>

 

 

is selected by the filtering process as the appropriate schedule for zone 1 then the FieldServer will store the following information.

 

Data Array Offset

(Relative to configured base Data offset for specific zone)

Data
0 2008
1 10
2 07
3 11
4 20
5 00
6 2008
7 10
8 07
9 14
10 20
11 00

 

Support

This driver was developed by Chipkin Automation Systems (CAS), a FieldServer Approved Integrator®. CAS are proud to provide support for the driver. For support please call CAS at (866) 383-1657.

Revision History

Date Resp Format Driver Ver. Doc. Ver. Comment
25 Sep 08 PMC    0.00  Created