FS-8705-15 - Networked Robotics NTMS4
Up one levelFieldServer Driver
FS8705-15
-
Driver for
Networked Robotics
NTMS4 Temperature Sensor Modules
Description
The NTMS4 driver can read temperatures from Networked Robotics NTMS4 modules using TCP/IP connections.
The driver can process data from multiple modules. The IP Address and Socket Port can be configured for each module.
The driver reads the temperature and cannot perform configuration of the module. It expects that the modules are correctly configured using the Vendor’s software or Instructions. The driver can store three data elements per module. The time stamp (in seconds since 1970) of the last time good data was obtained, the temperature data and a status value which is set non-zero when the module reports and error. If the module cannot be reached then the FieldServer will (after a configurable number of retries) mark the node offline. This state and the 3 data elements can be monitored using another protocol.
The driver can only be used as a client. Minimal server functionality is provided only to support our ongoing quality assurance program by facilitating automated testing of the driver. It is not documented or supported. If required please contact the FST sales group to discuss your requirements.
Max Nodes Supported
| FieldServer Mode | Nodes | Comments |
| Client | Many | The FieldServer will be able to poll multiple modules. The driver will support a max of 200 remote sensors. The driver has been tested with 70 remote sensors. |
| Server | 0 | Not supported or documented. |
Formal Driver Type
Ethernet
Client
Compatibility Matrix
| FieldServer Model | Compatible with this driver |
| FS-x2010 | Yes, |
| FS-x2011 | Yes, |
| FS-x40 | Yes, |
| FS-X30 | Yes, |
Connection Information
Connection type: Ethernet TCP/IP
Hardware interface: FieldServer Ethernet Adapters ( N1 / N2 as available)
Multidrop Capability No
Source Port Configurable
Devices tested
| Device | Tested (FACTORY, SITE) |
|
rack1/2/3/4/5.networkedrobotics.co m |
Factory |
Connection configurations
Multiple upstream protocols and connection supported. See list of FieldServer Drivers.

Driver Functionality
Temperatures are reported as floating point numbers in the format +-xxx.y. The driver stores data as floating point numbers and it is recommended that an appropriate data array type such as
‘FLOAT’ be used.
Each time a response is obtained which contained ‘Err-‘ or ‘Error-‘, then the driver extracts the number following the dash and stores that as a status value. If there is no error then the driver stores the value zero to the status value. When an error is reported the driver can, if configured correctly, store a specified value as the temperature value. Thus, it is easy for a consumer of the data to see if the temperature is no longer valid.
Support
This driver was developed by Chipkin Automation Systems (CAS), a FieldServer Approved Integrator®. CAS are proud to provide support for the driver. For support please call CAS at (866) 383-1657.
Revision History
| Date | Resp | Format | Driver Ver. | Doc. Ver. | Comment |
| 21 Apr 09 | PMC | 0.00 | 0 | Created | |
| 29 Apr 09 | PMC | 0.00 | 1 | Updated connection diagram | |
| 12 May 09 | PMC | 0.00 | 2 | Updated to say max=200. | |