FS-8704-09 - SNMP

Up one level

Driver Version:

1.03

Document Revision:

3

FieldServer Driver - Ethernet

FS-8704-09

SNMP


Description

 

The SNMP driver allows the FieldServer to transfer data to and from devices over Ethernet using the SNMP version 1 protocol. The FieldServer can emulate either a Server (SNMP Agent) or Client.

 

The Client can be configured to read values specified by their SNMP Object Identifiers (OID’s), which are defined in the MIB file (Management Information Base) of the target device.  When acting as an SNMP Agent (Server), the driver makes the contents of specified integer data arrays available to any SNMP Client.  The FieldServer MIB file sets out the OID’s to use.

 

The current version of the driver can send and receive SNMP traps. The following SNMP data types are currently supported:

· INTEGER

· OCTET_STREAM

· TIMER_TICKS

· STRING

 

The maximum number of traps currently supported is 255.

 

The FieldServer Enterprise ID is 6347.  MIB files are generated automatically from the FieldServer configuration files. A selection of standard MIB-2 OID’s are supported to allow interaction with popular Network Management packages.

 

FieldServer Mode

Nodes

Comments

Client

25

Each Node is specified by a unique IP address

Server

1

As a Server the SNMP driver can act as a single Node only

 

Formal Driver Type

Ethernet

Client (Active or Passive) or Server

 

Compatibility Matrix

 

FieldServer Model

Compatible with this driver

FS-x2010

Yes

FS-x2011

Yes

FS-x25

Yes

FS-x30

Yes

FS-x40

Yes

SlotServer

Yes

Connection Information

 

Connection type:

Ethernet

Ethernet Speeds Supported

10Base-T, 100Base-T[1]

 

Devices tested

 

Device

Tested (FACTORY, SITE)

MG-Soft MIB Browser and Trap Ringer

Factory

Visual MIBrowser Pro from NuDesign

Factory


Connection configurations

 

1. FieldServer as SNMP Agent (Server)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


2. FieldServer as SNMP Client

 


Connection Notes

 

1. TCP/IP Configuration: Ensure that the FieldServer and all Nodes to be monitored via SNMP have the same Netmask setting.

2. Default IP ports

  • Port 161 - Poll/Walk commands
  • Port 162 - Traps

Communications functions -Supported functions at a glance:

 


Data Types Supported

FieldServer Data Type

Description (or Device Data Type)

INTEGER

 

OCTET_STREAM

Character strings

TIMER_TICKS

Timer values in 1/100ths of a second

MIB-2 Variables Supported

Many Network Management systems poll these variables to connect to the SNMP Agent.

OID

Description (or Device Data Type)

1.3.6.1.2.1.1.1

sysDescr

1.3.6.1.2.1.1.2

sysObjectID

1.3.6.1.2.1.1.3

sysUpTime

1.3.6.1.2.1.1.4

sysContact

1.3.6.1.2.1.1.5

sysName

1.3.6.1.2.1.1.6

sysLocation

1.3.6.1.2.1.1.7

sysServices

Read Operations supported

 

FieldServer as a Client

FieldServer as a Server

SNMP Get Request

SNMP Get Request

SNMP GetNext Request / SNMP Walk (

SNMP GetNext Request / SNMP Walk

 

Write (Control) Operations supported

 

FieldServer as a Client

FieldServer as a Server

SNMP Set Request

SNMP Set Request

Unsolicited Operations supported

 

FieldServer as a Client

FieldServer as a Server

Receive Traps specified by OID

Data stored by matching OID or by using OID string values to form lookup string.

Send Traps specified by OID

Trap sent based on data change rules, periodic or on source data update.

Unsupported Functions and Data Types

 

Data Types

Reason

Only the following SNMP Data Types are supported:

INTEGER

OCTET_STREAM

TIMER_TICKS

STRING

Further types will be implemented as required.

MIB-2 variables not specified above

The FieldServer primarily being a protocol converter, these variables are not necessary.

 

Unsupported Devices or Protocol Options

 

Protocol Versions

Details

SNMPv2, SNMPv3

Not supported




[1] Not all FieldServer models support 100BaseT.  Consult the appropriate instruction manual for details of the Ethernet speed supported by specific hardware.