FS-8700-88 - Envirotronics Systems PlusTM Programmer/Controller

Up one level

 
  Text Box: Driver Version:	1.02

 

FieldServer Driver - Serial

FS-8700-88

Envirotronics Systems PlusTM[1] Programmer/Controller

 

Description

The Envirotronics Systems Plus driver allows for direct interfacing to a Systems Plus Programmer / Controller device. The driver acts as a Client to the device and can be used to read and set system parameters for status monitoring and control purposes. Combined with other protocol drivers on a FieldServer , complete Systems Plus monitoring and control is made possible via third party systems.

 

The driver is not available as a Server since a FieldServer cannot fully emulate a Systems Plus device’s interfaces. Any existing Server drivers are for FieldServer testing purposes only.

FieldServer Mode

Nodes

Comments

Client

1

Only 1 Client node per FieldServer serial port allowed.

Formal Driver Type

Serial

Client Only

Compatibility Matrix

FieldServer Model

Compatible with this driver

FS-x2010

Yes, No

FS-x2011

Yes, No

FS-x40

Yes, No

FS-x30

Yes, No

Connection Information

Connection type:

RS-232

Baud Rates:

300; 600; 1200; 2400; 4800; 9600; 19200 Baud

Data Bits:

7,8

Stop Bits:

1,2

Parity:

Odd, Even, None

Flow Control:

RTS / CTS

Multidrop Capability

No

Devices tested

Device

Tested (FACTORY, SITE)

Envirotronics Systems Plus Controller

Factory

 

 

Connection configurations

Connection Notes

Additional Systems Plus Controllers may be connected each to a separate serial port on the FieldServer.

Communications functions - Supported functions at a glance:

Data Types Supported

FieldServer Data Type

Description (or Device Data Type)

Analog Input

Device parameter data

Binary Input

Device parameter statuses

Analog Output

Device parameter data

Binary Output

Device parameter statuses

FieldServer as a Client

Read Analog Parameter Data:

Read Binary Parameter Status:

Write Analog Parameter Data:

Write Binary Parameter Status:

Read Setpoint

Read PV

Read Deviation

Read Program Status

Read Remaining Step Time

Read Remaining Step Cycles

Read Selected Program

Read Step Number

Read Step Time

Read Start Step

Read Initial Setpoint

Read Start Time

Read Stop Time

Read Software Version

Read Event

Read Events

Read Aux

Read Auxs

Read Start Time Enabled

Read Stop Time Enabled

Read Alarm Status

Read Alarm Log

Read Audible Alarm

Set Setpoint

Select Program

Set Start Step

Set Initial Setpoint

Set Start Time

Set Stop Time

Set Date

Set Time

Set Event

Set Aux

Set Circulators

Set Lights

Set Start Time Enabled

Set Stop Time Enabled

Set Audible Alarm

 

FieldServer as a Client

System Control Commands:

System Editing Commands:

Emergency Stop

Hold Program

Resume Program

Start Program

Start System

Stop Program

Stop System

Alarm Reset

Alarm Acknowledge

Use Keypad

Editing Programs:

End Edit

Edit Program

Read Program

Edit Step

Read Step

Remove Step

Insert Step

Add Step

Clear Program

Read Number Steps

Read Setpoint

Read Gsoak Enabled

Read Gsoak

Read Duration

Read Events

Read Aux

Read Cycles

Read Next

Set Setpoint

Set Gsoak Enabled

Set Gsoak

Set Duration

Set Events

 

Set Auxs

Set Cycles

Set Next

Read Units

Set Analog Min

Set Analog Max

Set Analog Type

Set Engineering Min

Set Engineering Max

Set Analog Address

Set Units

Editing Channel Configuration Parameters:

Edit Analog

Read Analog Min

Read Analog Max

Read Analog Type

Read Engineering Min

Read Engineering Max

Read Analog Address

 

Editing Alarm Configuration Parameters:

Edit Alarms

Read Scan

Set Scan

Editing Fuzzy Configuration Parameters:

Edit Fuzzy

Read Fuzzy

Set Fuzzy

Fuzzy phrases allowed:

Heat Cycle Time

Cool Cycle Time

Heat Sensitivity

Cool Sensitivity

Heat Max Power

Cool Max Power

Heat Min Time

Cool Min Time

Heat Stage Delay

Cool Stage Delay

Dead Band

Unsupported Functions and Data Types

 

Function

Reason

Use Emulator Mode

Emulator mode is used for remote user access via the device’s system menu and cannot be used against a FieldServer for status monitoring and control.

 

Functions Described

The functions listed are “read”, “write” or “control” type command functions. Read functions request data from the Systems Plus device and store the data in data arrays made accessible to other protocol drivers. Read functions normally run continuously to update data from the Systems Plus device to the FieldServer.

 

Write functions take dynamic or static preloaded data from data arrays and request the Systems Plus device to update the relevant data internally. Data for write may be set up by other protocol drivers or be available as static data. Write functions may be set to write once, continuously or be “triggered” by other protocol drivers on the FieldServer

 

Control type functions usually do not transfer data but are used to effect system control such as starting and stopping the device. Control functions are normally “triggered” from other protocol drivers on the FieldServer.