FS-8700-83 - Gamewell Serial Driver
Up one levelFieldServer Driver - Serial
FS-8700-83
Gamewell Serial Driver
Description
All Gamewell Fire Alarm panels are equipped with a serial port which produces panel, circuit or device status messages. This driver is designed to process these messages and store this status information in numeric form. The numeric value will indicate the type of event being reported and the storage location in the FieldServer’s data arrays is (configurable &) dependent on the origin of the message (panel / circuit / device ). Additional information such as event date and time and descriptions are ignored.
The driver is capable of supporting a panel configured to supervise the port by responding to the panel’s supervision queries.
This is a passive client driver. The driver listens passively for unsolicited messages produced by the Gamewell panel. In addition the driver is capable of sending the panel three messages: Ack, Silence and Reset. (This feature will be provided in a later release of the driver.)
Design Basis: Gamewell serial port protocol specification “IF 600r7 Message Stream” (not dated) and “SmartNet Data stream information” (not dated).
The driver is capable of exposing communication statistics in a FieldServer Data Array so they can be monitored by a remote device.
Formal Driver Type
Serial
Passive Client
Connection Information
Connection type: RS-232 or RS-485 (with converter)
Baud Rates: Gamewell Panel: 2400
Driver: 110; 300; 600; 1200; 2400; 4800; 9600; 19200; 28800; 38400; 57600; 115200
Data Bits: Gamewell Panel: 8 Driver: 7,8
Stop Bits: Gamewell Panel: 1 Driver: 1,2
Parity: Gamewell Panel: None Driver: Odd, Even, None
Multidrop Capability No.
Devices tested:
|
Device |
Tested |
|
IF610 |
@FieldServer, Milpitas, May2002. Tested port supervision, alarm generation, message filtering using data types, system reset clears data arrays. Test to send reset/ack/silence from Fieldserver passed. |
Connection configurations

Connection Notes
Only one Gamewell panel may be connected directly to a FieldServer port. The reason for this is that the messages produced by the panel do not identify the panel of origin.
Data Type Supported
|
Data_Type |
Type of Information Stored |
Notes |
|
Any |
Stores Status Information. |
Status:????. Stores non-zero value for any not-normal status. |
|
Alarms |
Stores Status Information |
Status:ALARM sets array non-zero. NORMAL sets array to zero. |
|
Faults |
Stores Status Information |
Status:FAULT sets array non-zero. NORMAL sets array to zero. |
|
Events |
Stores Status Information |
Status:EVENT sets array non-zero. NORMAL sets array to zero. |
|
Bus |
Stores Status Information |
Status:BUS sets array non-zero. NORMAL sets array to zero. |
|
Comm |
Stores Status Information |
Status:COMM sets array non-zero. NORMAL sets array to zero. |
|
Control |
Stores Status Information |
Status:CONTROL sets array non-zero. NORMAL sets array to zero. |
|
Ack |
Stores Status Information |
Status:ACK sets array non-zero. NORMAL sets array to zero. |
|
Signal Silence |
Stores Status Information |
Status:SIG SIL sets array non-zero. NORMAL sets array to zero. |
|
Troubles |
Stores Status Information |
Status:FAULT sets array non-zero. NORMAL sets array to zero. |
|
Supervisories |
Stores Status Information |
Status:EVENT and Action contains 'Supv. Event in ' sets array non-zero.
Or
Status:SUPV and any action.
NORMAL sets array to zero. |
|
Action_Numbers |
Stores Action information |
Value based on contents of 'Action' Field |
|
Action_Bits |
Stores Action information |
Sets bit whose offset is based on contents of 'Action' Field |
|
Dump |
Dump's ignored messages for user review. |
|
|
|
|
|
Communications functions
Supported functions at a glance:
Listen. Driver listens passively for status messages, parses them looking for Node, Status, Circuit/Device and action information and stores data based on this information.
Write. Driver can send an Ack, Silence and Reset command. (To be provided in a later release.)
Supervision Query / Response
The driver clears its data arrays when the following messages is received.
Status:NORMAL 08/31/95 16:23
System Idle
Driver Limitations and Unsupported Features
The driver stores a value representing the type of status message received. A table of status types vs. values is provided in the driver manual. Each message is inspected for circuit/device information. If none is present the message is assumed to report a status event for the panel. If the one or both are present then the circuit / device number is used to determine the storage location.
The driver can store a value to represent the status of a point ( device / Circuit / panel) and/or a value to represent the ‘action’ that caused the most recent message to be sent.
For messages reporting a status event for a circuit / device the driver uses only the device number to determine the location to store the indicating value.
The driver does not maintain an event / alarm history.
The value zero will be used to represent normal
The driver is programmed with a list of status types and action types that it recognizes. In the event that unrecognized information is found, the driver will store special value to indicate this. The driver provides a method which allows the user to extend the list of recognized status types and actions.
Revision History
|
Date |
Driver Version |
Document Revision |
Resp
|
Comment |
|
10May2002 |
1.00 |
0 |
PMC |
Draft Issued for customer signoff prior to development completion. |
|
29May2002 |
1.00 |
1 |
PMC |
Amended after completion of driver development.
|
|
13Jun2002 |
1.00 |
2 |
PMC |
Driver now supports Ack / Signal Silence and Reset. |
|
18Sep2002 |
1.00 |
3 |
PMC |
Driver now support messages containing ‘Status:SUPV’ |
|
20Aug2003 |
1.00 |
4 |
JD |
Releasing |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|