FS-8700-59 - Canatal Satchnet Driver
Up one level![]() |
FieldServer Driver
FS-8700-59
Canatal Satchnet Driver
Description
The Canatal Satchnet Protocol Driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using Canatal Satchnet Protocol Driver protocol. The FieldServer can emulate either a Server or Client.
This driver provides support for the Canatal International implementation of the “Satchwell Network (Full) and Net2 (Reduced)” protocol.
The Canatal Satchnet Protocol Driver can act as a Satchnet Master.
· Any Satchnet device on any serial port (P1-P8, R1 & R2 ) can be polled by FS-X40 Servers.
· FS-X20 Servers can poll P1/R1 only.
· Data from Series 2, 4, 5, 6,8, 9 devices can be polled.
· Data from any 'Table' can be read.
· Data in 'Tables' with “write permission” can be written to by the driver.
· The driver can read/write Bit, Byte, Swapped Integer, Word, BCD and Float Data.
The Canatal Satchnet Protocol Driver can act as a (passive) Server.
· The driver can be polled by a Satchnet Master and return data from the FieldServer's data arrays.
· The driver can emulate Series 2,4,5,6,8,9 devices.
· All “Tables” can be read/written in accordance with their read/write capability
|
Fieldserver Mode |
Nodes |
Comments |
|
Client |
63 |
expansion above 32 nodes normally requires a repeater |
|
Server |
63 |
expansion above 32 nodes normally requires a repeater |
Formal Driver Type
Serial
Client or Server
Compatibility Matrix
|
FieldServer Model |
Compatible with this driver |
|
FS-x2010 |
Yes |
|
FS-x2011 |
Yes |
|
FS-x40 |
Yes |
|
FS-x30 |
No |
Connection Information
|
Connection type: |
RS-232 or RS-485 (Two wire, Half-Duplex) |
|
Baud Rates: |
1200,2400,4800,9600 Vendor limitation. FieldServer support all standard Baud Rates110; 300; 600; 1200; 2400; 4800; 9600; 19200; 28800; 38400; 57600; 115200. |
|
Data Bits: |
7 Vendor limitation. FieldServer supports 7,8 |
|
Stop Bits: |
1 Vendor limitation. FieldServer supports 1,2 |
|
Parity: |
Even Vendor limitation.FieldServer supports Odd, Even, None |
|
Hardware interface: |
|
|
Multidrop Capability |
Yes , No |
Proprietary Physical Interfaces Supported
|
Fieldserver Model |
Adapter Model # |
Vendor |
Physical Medium |
|
|
|
|
|
|
|
|
|
|
Devices tested
|
Device |
Tested (FACTORY, SITE) |
|
Canatal Series 9 |
FACTORY |
|
Canatal Series 6,8 |
SITE |
Connection configurations

Connection Notes
See Driver manual for more detail.
Communications functions - Supported functions at a glance:
Read Operations supported
|
FieldServer as a Client |
FieldServer as a Server |
|
Read all Tables for Series 2, 4, 5, 6,8, 9 |
Provide Data from all Tables for 2, 4, 5, 6,8, 9 series. |
Write (Control) Operations supported
|
FieldServer as a Client |
FieldServer as a Server |
|
Write Data in tables with write permission |
Store Data in tables with write permission |
Unsupported Functions and Data Types
|
Function |
Reason |
|
none |
|
Functions Described
Unsupported Devices or Protocol Options
|
Device |
Details |
|
none |
|
THIS PAGE INTENTIONALLY LEFT BLANK