FS-8700-56 - Caterpillar CATM5X Protocol Driver
Up one level
FieldServer Driver - Serial
FS-8700-56
Caterpillar CATM5X Protocol Driver
Description
The Caterpillar M5X driver allows the FieldServer to transfer data to and from devices over RS-232 using Caterpillar M5X protocol. The FieldServer can emulate either a Server or Client. The driver is capable of communications with any device that uses the Caterpillar M5X protocol but has been designed primarily for connection to a Caterpillar CCM which is in turn connected to the Caterpillar engines to be monitored/controlled.
The driver provides a limited set of M5X protocol commands and may address a sub-set of the parameters available in each device. The driver provides formal support for 3500 engines and EMCPII devices only. Other devices may be polled using the address of the parameter required as opposed to user friendly parameter names.
|
FieldServer Mode |
Nodes |
Comments |
|
Client |
8 |
The number of Nodes this driver can connect to as a Client is not limited by the driver. Limitations are imposed by the CCM. Consult Caterpillar/CCM documentation for the current limit. The most recent documentation viewed indicates that a CMM can be connected to a maximum of 3 Marine Engine controllers, with no more than 8 controllers connected at any one time. Note that to date FieldServer has not tested any applications where more than one Node is connected to a CCM. |
|
Server |
255 |
Up to 255 Server Nodes can be emulated on one connection |
Formal Driver Type
Serial
Client or Server
Compatibility Matrix
|
FieldServer Model |
Compatible with this driver |
|
FS-x2010 |
Yes |
|
FS-x2011 |
Yes |
|
FS-x30 |
Yes |
|
FS-x40 |
Yes |
Connection Information
|
Connection type: |
RS-232 |
|
Baud Rates: |
110 – 115200, standard baud rates only. The default baud rate of a CCM module is 9600. |
|
Data Bits: |
7,8 |
|
Stop Bits: |
1 |
|
Parity: |
None |
|
Multidrop Capability |
Yes |
Devices tested
|
Device |
Tested (FACTORY, SITE) |
|
Caterpillar CCM Module |
Factory |
Connection configurations
Connection Notes
If having problems trying to establish the caterpillar Node ID, set the Node_ID to 0 in the configuration. Watch the error screen on reboot - the remote device will usually send a message back with an error stating that it cannot accept a response message from a certain Node ID. That Node ID is the relevant Node ID.
The FieldServer cannot be connected directly to the generator/engine controller but must be connected via the CCM module.