FS-8700-33 - Modbus Omniflow
Up one levelFieldServer Driver - Serial
FS-8700-33
Modbus Omniflow
Driver Code: MBO
Version: 1.0a
Devices Supported: Omniflow Modbus devices
Interface: RS-232 or RS-485
Command/SubCommand Supported:
Command |
Description |
|
01 |
Read Discrete Output Status (0xxxx) |
|
02 |
Read Discrete Input Status (1xxxx) |
|
03 |
Read Output Registers (4xxxx) |
|
04 05 |
Read Input Registers (3xxxx) Force Single Coil (0xxxx) |
|
06 |
Preset Single Register (4xxxx) |
|
15 |
Force Multiple Coils (0xxxx) |
|
16 |
Preset Multiple Registers (4xxxx) |
Configuring the Omniflow Controller to interface to FieldServer
Check PEER/ PEER: Disable.
Go to SET UP menu.
Press <PROG> <SETUP> <ENTER> respectively
Go to MISC configuration
Press <ENTER>
Go to PEER/PEER communication
Press <DOWN ARROW> until see PEER/PEER Comm then press <ENTER>.
· Change Next Master to 0
· Change Last ID to 0
(If ask for password then enter OMNI )
Go to MISC menu.
Press key <PROG>
Go to I/O menu
Press <UP ARROW> <2> <ENTER> respectively
· Set baud rate to 9600
· Set Data bit to 8
· Set parity to N
· Set Modbus ID to 1
· Set Modbus Type to 0
· Set Modicon compatible to Y
(If ask for password then Enter OMNI)
Press <PROG> repeatedly until go to Run Menu.