Chipkin.com

Navigation
CAS Modbus TCP Parser.

Have you ever needed to analyze a series of Modbus TCP message?
CAS Modbus TCP Parser

CAS Modbus RTU Parser.

Have you ever needed to analyze a Modbus RTU message?
CAS Modbus RTU Parser

CAS BACnet Explorer

Do you want to know more about your BACnet device on your network ?
CAS BACnet Explorer

FS-8700-26 - Notifier 200/300/400

Up one level

FieldServer Driver - Serial
FS-8700-26
Notifier 200/300/400

Driver Code: NOTA
Version 1.00
Devices Supported: Notifier AFP200, AFP300 and AFP400 Fire Alarm Panels
Interface: RS-232 utilizing Notifier Fire Alarm Panel Connector adapter
Baud: 2400
Parity: Even (AFP200); None (AFP300/AFP400)
Data Bits: 7 (AFP200); 8 (AFP300/AFP400)
Handshaking: None

Device Types Supported

Detectors
  • Alarms
  • Troubles
  • Pre-Alarms
  • Not Installed

Modules

  • Alarms
  • Troubles
  • Pre-Alarms
  • Not Installed

Zones

  • Only if the default "Zone xx" Labeling (where xx is the zone number) is used. If custom zone descriptions are used, they will not be reported to the driver.

System Alarm
Module Type Codes Supported

  • Monitor
  • Pull Station
  • Smoke Detect
  • Blank
  • Waterflow
  • Supervisory
  • Tamper
  • Hazard Alert
  • Fire Control
  • Abort Switch
  • Man-Release
  • Silence
  • System Reset
  • Evacuate
  • PAS Inhibit
  • Trouble Mon
  • Security
  • Tele Page
  • Allcall Page
  • Man Rel. Delay
  • Second Shot
  • Sprinkler Sys
  • Comb. Monitor

Note that status on control devices is not supported. As zones can be reported, this should not be a problem.