Chipkin.com

Navigation
CAS Modbus TCP Parser.

Have you ever needed to analyze a series of Modbus TCP message?
CAS Modbus TCP Parser

CAS Modbus RTU Parser.

Have you ever needed to analyze a Modbus RTU message?
CAS Modbus RTU Parser

CAS BACnet Explorer

Do you want to know more about your BACnet device on your network ?
CAS BACnet Explorer

Subscribe to our Newsletter
Name
E-mail Address

FS-8700-25 - Notifier INA

Up one level

FieldServer Driver - Serial

FS-8700-25

Notifier INA

 

Description

 

Due to the nature of the Notifier drivers and the adaptability of the FieldServer configuration of the Notifier side of the FieldServer is quite simple.  The Notifier driver will always function as a Server, thus the primary purpose is for the Notifier Fire Alarm Panel to write information to the FieldServer to be passed on to another device.  When the FieldServer is used with the Notifier INA additional Data Arrays need to be configured for each Panel connected to the INA.. The operator must configure the Data Arrays with Node ID’s with addresses of station 1,2, er=tc.  Following is an example that is in the default Notifier.

 

The driver is capable of parsing and storing zone alarm and trouble states. They are latched and cleared when a Network System Reset is received.

 


The Status Bits is the data string coming from Notifier to set or clear any one of 8209 bits of information in the following order:

Parameter

Bits

Detector Alarms

0 – 1023

Detector Alarms Unacknowledged

1024 – 2047

Module Alarms

2048 – 3071

Module Alarms Unacknowledged

3071 – 4095

Detector Trouble

4096 – 5119

Detector Trouble Unacknowledged

5120 – 6143

Module Trouble

6144 – 7167

Module Trouble Unacknowledged

7168 – 8191

Common Bits

8192 – 8207

Control Bits

8208 - 8209

Reserved for future use.

8210 - 8299

Zone Alarms

8220 – 8499

Zone Troubles

8500 - 8699

‘Level’ Alarms

8800-9099

‘Level’ Troubles

9100-9399

The Control Bits are as follows:

Parameter

Bit

Ack/Step

8208

System Reset

8209

The TAC-Americas heartbeat bit:

Parameter

Bit

TAC-Americas Heartbeat

8210

The Common Bits are as follows:

Parameter

Bit

Detector Alarms

8192

Detector Alarms Unacknowledged

8193

Module Alarms

8194

Module Alarms Unacknowledged

8195

Detector Trouble

8196

Detector Trouble Unacknowledged

8197

Module Trouble

8198

Module Trouble Unacknowledged

8199

Alarms

8200

Alarms Unacknowledged

8201

Trouble

8202

Trouble Unacknowledged

8203

Supervise Sent

8204

Ignored Message

8205

All Systems Normal

8206

ESC X NUL

8207


Text_Regs - This is the text string coming from Notifier that matches the information on the display of the 1010 or 2020 and contains two sets 400 16-bit registers which is equivalent to 10 lines by 80 characters for each set.

 

Supervise – This is a 2-character string from Notifier providing a “supervise” signal to the Notifier Fire Alarm Panel when hot standby is alive.  It also appears to the Client as 2 single coil if it is being sent.

 

When the customer receives a FieldServer with the Notifier driver installed, the Data Array is already configured and ready to use with the 1010 or 2020.  The customer only needs to configure the Server side of the FieldServer, the interface to the non-Notifier device.  As an example, if the user were connecting to a device using Modbus RTU communications protocol, they would configure the interface as if the FieldServer were another Modbus PLC.  They would have to configure the Modbus device to identify where to find the necessary Notifier information.  Thus, they would find the alarm for loop 1 detector 5 in the Status_Bits Data Array at address number 105

 

Level Status – ‘Level’ Alarms are only set when ‘ALARM’ messages are received. ‘ACTIVE’ messages are treated as troubles for the purpose of ‘Level’ status.

 

Should you use the Notifier INA driver or the Notifier NFA/1010/2020 Driver ?

 

Use the INA driver if your FieldServer is connected to an INA device and in turn, the Notifier field panels are connected to the INA which serves as a gateway. One INA panel can be connected to each FieldServer port.

 

Use the NFA(/1010/2020) driver if your Fieldserver is connected to NFA/1010/2020 Panel directly. One panel can be connected to each FieldServer port.

 

Revision History

 

Date

Driver

Version

Document

Revision

Resp

Comment

12/21/02

1.05a

1

MF

Updated formatting


7/23/03

1.05a

1

JD

Releasing