FS-8700-17 - Opto 22 Optomux

Up one level

FieldServer Driver - Serial

FS-8700-17

Opto 22 Optomux

 

Description

The Optomux Driver allows the FieldServer to transfer data to and from devices over either     RS-232 or RS-485 using the Optomux Driver protocol. The Optomux driver is a client only driver and can poll an Optomux protocol compliant device but not emulate one.

 

The Optomux protocol provides a large command set.  Many of the commands are used for OPTO22 device configuration.  This driver supports the full command set and thus the driver may be used to configure as well as to poll OPTO22 devices.

Operating Methods

The Optomux driver provides three methods of operation. Users may use any combination of methods.

Static Operation

If the hardware configuration is fixed and known then this is a suitable method. The devices to be polled/commanded are configured using the FieldServer CSV file.

Dynamic Operation

If the hardware configuration may change or if hardware settings may change dynamically or (more realistically) if you wish to change some aspect of the hardware configuration such as a delay time or reset a latch without changing the CSV file and resetting the FieldServer then this operating method is suitable. The commands set can be configured by changing the values in the FieldServer’s data arrays. This operating mode may be considered a data driven one.

Triggered Operation

This operating mode allows commands to be triggered by changing the value in the FieldServer’s data arrays. This operating mode is useful if requiring an action triggered by a remote device.

Statistics and Command Reponses

All FieldServer drivers report communication statistics that allow the operation of the driver to be monitored.

 

In addition to the standard statistics, this driver exposes the communication statistics for each port by presenting them in a user specified data array where they can be monitored by a remote device or HMI system.

 

The Optomux driver also exposes the response status to each poll and command (if required) by writing the response statuses to a user specified data array. This useful feature allows remote devices to check whether a command has been completed successfully.

Fieldserver Mode

Nodes

Comments

Client

 

 

Server

N/A

Server side is not supported. See description.

Formal Driver Type

Serial

Client Only

Compatibility Matrix

FieldServer Model

Compatible with this driver

FS-x2010

Yes

FS-x2011

Yes

FS-x30

Yes

FS-x40

Yes

Connection Information

Connection type:

RS-485 (Two wire, Half-Duplex)

Baud Rates:

At the time of publication of this manual the OPTO22 devices support standard baud rates in the range 300-38400.

Data Bits:

7,8

Stop Bits:

1

Parity:

Odd, Even, None

Multidrop Capability

No

 

Devices tested

Device

Tested (FACTORY, SITE)

OptoMux (by Opto22 Inc.)

SITE

 

Connection configurations

Communications functions - Supported functions at a glance:

The Optomux driver can perform the following commands / queries


POWER UP CLEAR

RESET

SET TURN-AROUND DELAY

SET WATCHDOG DELAY

SET WATCHDOG DELAY (Analog)

SET PROTOCOL

IDENTIFY Optomux TYPE

SET ENHANCED DIGITAL WATCHDOG

SET ENHANCED ANALOG WATCHDOG

SET TIMER RESOLUTION

SET TEMPERATURE PROBE TYPE

CONFIGURE POSITIONS

CONFIGURE AS INPUTS

CONFIGURE AS OUTPUTS

READ MODULE CONFIGURATION

WRITE OUTPUTS

ACTIVATE OUTPUTS

DEACTIVATE OUTPUTS

READ STATUS

SET LATCH EDGES

SET LATCH OFF TO ON

SET LATCH ON TO OFF

READ LATCHES

READ AND CLEAR LATCHES

CLEAR LATCHES

START/STOP COUNTERS

START COUNTERS

STOP COUNTERS

READ COUNTERS

READ AND CLEAR COUNTERS

CLEAR COUNTERS

SET TIME DELAY

INITIATE SQUARE WAVE

HIGH RESOLUTION SQUARE WAVE

RETRIGGER TIME DELAY

GENERATE N PULSES

START ON PULSE

START OFF PULSE

SET TRIGGER POLARITY

TRIGGER ON POSITIVE

TRIGGER ON NEGATIVE

READ PULSE COMPLETE BITS

READ DURATION COUNTERS

READ AND CLEAR DURATION COUNTERS

CLEAR DURATION COUNTERS

WRITE ANALOG OUTPUTS

READ ANALOG OUTPUTS

UPDATE ANALOG OUTPUTS

READ ANALOG INPUTS

READ AND AVERAGE INPUT

START INPUT AVERAGING

READ AVERAGE COMPLETE BITS

READ INPUT AVERAGE DATA

READ TEMPERATURE INPUTS

READ AVERAGE TEMPERATURE INPUTS

SET INPUT RANGE

READ OUT-OF-RANGE LATCHES

READ AND CLEAR RANGE LATCHES

CLEAR OUT-OF-RANGE LATCHES

READ LOWEST VALUES

CLEAR LOWEST VALUES

READ AND CLEAR LOWEST VALUES

READ PEAK VALUES

CLEAR PEAK VALUES

READ AND CLEAR PEAK

CALCULATE OFFSETS

SET OFFSETS

CALCULATE AND SET OFFSETS

CALCULATE GAIN COEFFICIENTS

SET GAIN COEFFICIENTS

CALCULATE AND SET GAIN

SET OUTPUT WAVEFORM R

IMPROVED OUTPUT WAVEFORMS


Unsupported Functions and Data Types

The driver was developed and tested using REV1 equipment.  The basis for development was the OPTOMUX PROTOCOL USER’S GUIDE dated April 2000. The Opto22 protocol specification identifies the following limitations for equipment with a revision prior to Rev1. The following list is a guide. Please consult with Opto to ensure the functions you wish to use are supported by your legacy equipment.

 

Baud rates

From Rev1 onwards, additional baud rates were supported.

 

 

Command Set

From Rev1 onwards, the following commands are supported.

 

Digital

SET ENHANCED DIGITAL WATCHDOG

SET TIMER RESOLUTION

READ MODULE CONFIGURATION

HIGH RESOLUTION SQUARE WAVE

RETRIGGER TIME DELAY

GENERATE n PULSES

START ON PULSE

START OFF PULSE

Analog

SET ANALOG WATCHDOG USER-DEFINED VALUE

SET ANALOG WATCHDOG

READ MODULE CONFIGURATION

SET TEMPERATURE PROBE TYPE

 

 

The following notes are extracted from the OPTOMUX PROTOCOL USER’S GUIDE - April 2000.

 

OPERATIONAL DIFFERENCES — OLD OPTOMUX BRAIN BOARDS

This protocol manual applies to Optomux units labeled “REV 1” and above. If the Optomux brain board (applies to B1 and B2 only) does not have a revision label, you have a very old Optomux unit and should be aware of the following differences. Brain board model B3000 is newer than “REV 1”.

Digital Brain Boards (B1)

1. The “REV 1” (or greater) Optomux units will notify the host that a serial watchdog has timed out by responding to the first command after a serial watchdog time-out with an N06cr error code. The command will not be executed. This is similar to a power-up operation. This error code will not be sent in response to a “POWER UP CLEAR” command.

2. Pulse duration counters are edge triggered with the newer Optomux brain boards. The previous versions were level triggered.

3. Maximum counter frequency is now 400 Hz, 50 percent duty cycle (minimum ON or OFF pulse time is 1.25 milliseconds). Use of the “GENERATE n PULSES” command will degrade counter frequency to 350 Hz maximum.

4. The baud rate may now be changed without cycling power to the Optomux. Additional baud rates of 600, 2,400, 4,800, and 38,400 are now supported when using “REV 1” brain boards or above.

5. Two question mark characters (??) may be used instead of the calculated checksum characters in command strings.

 

Analog Brain Boards (B2)

1. The “REV 1” (or greater) Optomux units will notify the host that a serial watchdog has timed out by responding to the first command after a serial watchdog time-out with an N06cr error code. The command will not be executed. This is similar to a power-up operation. This error code will not be sent in response to a “POWER UP CLEAR” command.

2. With “REV 1” (or greater) brain boards, averaging is performed using a continuous running average with a sample rate of 100 milliseconds. The number of samples to average is set with the “START INPUT AVERAGING” command as before, however, there is no need to restart the averaging after the number of samples has been reached. The “READ AVERAGE COMPLETE BITS” command indicates that the number of samples to average has been reached. The running average calculation used by Optomux is as follows (where n is the number of samples):  New Average = ((n-1) (Old Average) + (New Reading))/n

3. The baud rate may now be changed without cycling power to the Optomux. Additional baud rates of 600, 2,400, 4,800, and 38,400 are now supported when using “REV 1” brain boards or above.

4. Two question mark characters (??) may be used instead of the calculated checksum characters in command strings.


Revision History

Date

Resp

Format

Driver Version

Doc.

Rev.

Comment

2/10/05

PMC

 

1.00

0

Previous releases of this document had no revision info.

Updated by providing notes on limitation for legacy equipment (prior to rev1)

3/4/05

Meg

Meg

1.00

1

Formatting updated.  Connection diagram inserted.