FS-8700-15 - Modbus Daniels

Up one level

FieldServer Driver

FS-8700-15

Modbus Daniels

 

Description

Modbus Daniels is an inclusion into Modbus ASCII, allowing floats to be used. Modbus Daniels is designed to support floats in the address range 7000 to 7999. The "Double" data type is not supported. Other standard Modbus data types are supported. The FieldServer can only emulate a client.

FieldServer Mode

Nodes

Comments

Client

1

The FieldServer can only emulate one client node but can communicate with up to 255 other Modbus Daniels devices. The achievable number of devices may be limited due to device loading and network speed characteristics. Only one client node allowed on multidrop systems.

 

Formal Driver Type

Serial

Client only

Compatibility Matrix

FieldServer Model

Compatible with this driver

FS-x2010

Yes

FS-x2011

Yes

FS-x40

Yes

 

Connection Information

Connection type:

EIA232 or EIA485 (Two wire, Half-Duplex)

Baud Rates:

110; 300; 600; 1200; 2400; 4800; 9600; 19200; 28800; 38400; 57600; 115200 Baud

Data Bits:

7,8

Stop Bits:

1,2

Parity:

Odd, Even, None

Multidrop Capability

Yes , No

Devices tested

Device

Tested (FACTORY, SITE)

To be confirmed.

SITE

Connection configurations


Communications functions - Supported functions at a glance:

Data Types Supported

FieldServer Data Type

Description (or Device Data Type)

Analog Input

Analog Input Registers

Digital Input

Discrete Input Registers

Analog Register

Input and Output Registers

Digital Register

Input and Output Registers

Analog Output

Analog Output Registers

Digital Output

Discrete Output Registers

Floating Point

Floating Point Register

Read and Write Operations supported

 

FieldServer as a Client

Read Analog Status:

Read Output Registers (4xxxx)

Read Input Registers (3xxxx)

Read Binary Status:

Read Discrete Output Status (0xxxx)

Read Discrete Input Status (1xxxx)

Write Analog Setpoints:

Preset Single Register (4xxxx)

Preset Multiple Registers (4xxxx)

Write Binary Commands:

Force Single Coil (0xxxx) excluding (7xxx-7999)

Force Multiple Coils (0xxxx) excluding (7xxx-7999)

Read Floating Point Value:

Read Floating Point Register (7xxx – 7999)

Write Floating Point Value:

Set Floating Point Register (7xxx – 7999)

 

Unsupported Functions and Data Types

 

Function

Reason

Programming messages

FieldServer is a data transfer device, and as such, programming messages are not required

 


Revision History

 

Date

Resp

Format

Driver Ver.

Doc.

Rev.

Comment

12/08/03

DR

 

1.00dB

1

Updated to new format.

12/09/03

DR

 

1.00dB

2

Removed server driver capability until supported.

12/09/03

DR

 

1.00dB

3

Better explain client node capabilities.

04/05/04

Meg

Meg

1.00dB

4

Updated formatting.  Added connection diagram.  Added new revision table.

6/14/04

JD

 

1.00dB

5

Releasing