FS-8700-130 - Notifier NCA2/NFS2-3030

Up one level

 
  Text Box: Driver Version:	1.00

FieldServer Driver - Serial

 

 

FS-8700-130

Notifier NCA2/NFS2-3030

Description

The NCA2/NFS2-3030 Serial driver allows the FieldServer to record data from Notifier NCA2 or NFS2-3030 panels over RS-232 as per NFS2-3030/NCA-2 EIA-232 Protocol & Data Formats 53219 Rev A 1/3/2008.  There is no active polling by this driver; the communications are one-way through the panel's printer or CRT port.   The FieldServer acts as a Client; receives messages and records the status of a Panel.  The panel MUST output messages in160 characters ASCII format in English.

 

This driver is not capable of emulating a Notifier NCA2 or NFS-3030 panel.

 

The NCA2 controls all the devices (e.g. 3030, 640 panels) connected on the Notifier network.  Each Fire Alarm Panel on Network is considered as a Node.  240 Nodes can exist on one network.  NFS2-3030 can exist on a network or be self-standing.

 

NCA2 interacts with other Fire Alarm Panels, records the status of the panels and sends the events to printer and CRT ports.  FieldServer captures these events in text form, parses and stores them in Data Arrays.  These Data Arrays can be monitored by third party tools.  Since the FieldSever does not actively poll for data, the accuracy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues.

 

If a networked panel does not send the 'CLEARED' message for latched points via the NCA2 it is not possible to detect cleared points unless a system reset is done.  It is possible to configure the FieldServer to clear on reset message from NCA2.  See Driver Manual for more detail.

 

Please note that the FieldServer can be configured with a large number of points. The point limits purchased with the FieldServer prevent the entire database from being accessed in any one application.  It is therefore strongly advisable to ensure that only the point addresses of interest are configured, and that the FieldServer is purchased with the correct point count.

 

The types of Notifier messages supported by this driver are summarized later in the manual.  A detailed table shows each type of NCA2/NFS2-3030 message the FieldServer recognizes and the effect that it has on the status of the points in the Data Array.

 

Fieldserver Mode

Nodes

Comments

Client

1

Each FieldServer port can connect to only 1 Notifier panel

Server

0

This driver cannot be used as a Server.

Formal Driver Type

Serial

Client

Connection Information

Connection type:

RS-232

Baud Rates:

CRT Port

4800; 9600; 19200; 38400; 57600; (Vendor limitation)

Printer Port

9600 (Vendor limitation)

Data Bits:

8 (Device limitation)

Stop Bits:

1 (Device limitation)

Parity:

None (Device limitation)

Multidrop Capability

No

Devices Tested:

Device

Tested (FACTORY, SITE)

NCA2

NFS2-3030

Site

Site



Connection configurations

The FieldServer is connected to the Notifier NCA2/NFS2-3030 Fire Panel as shown in the following connection drawing.

 

Configure the Notifier Panel according to manufacturer’s instructions.

 

 

Connector Pinouts

TB5 CRT

Function

Receive

Reference

Transmit

Pin

CRX

REF

CTX

TB5 Printer

Function

Receive

Reference

Transmit

Pin

PRX

REF

PTX

RJ-45

Function

Transmit

Com

Receive

Pin

8

4

1

Wire Color

Orange/white

Blue/white

Brown

 

Hardware Connection Tips / Hints

· The FieldServer should preferably be connected to the TB5 Printer port.  It is theoretically possible to connect to the TB5 CRT port, but this has not been fully tested.

· The Panel’s port must be enabled and set to 80 Columns Not Supervised.

 

Communications functions - Supported functions at a glance:

Message Types Supported

The primary purpose of this driver is to record the status of devices connected to the Notifier panel by interpreting the text messages sent to the printer or CRT port.  Not all messages will be interpreted, as many messages do not directly pertain to device status, or are not currently supported.  The following subset of event messages is recognized:

 

Active Events:

FIRE ALARM

SECURITY ALARM (LIFE)

LIFE CRITICAL ALARM

MEDICAL EMERGENCY

SECURITY ALARM

CRITICAL PROCESS

SUPERVISORY

TROUBLE/ FAULT

DISABLED

PREALARM

ACTIVE

ON/ OFF

 

A detailed mapping of message interaction System Trouble messages provided by Notifier at the time this driver was written is tabulated in the Driver Manual.  Any changes or additions by Notifier will not be reflected in this driver unless specifically revised.

Zone Status:

This driver will not record information about zone status that is incorporated with point status messages.  A device can belong to multiple zones, however, only the primary zone is listed in the printer output.  This severely limits the accuracy of zone data based on event generated messages, and therefore will not be recorded.

Panel Status:  Memory Mapping:

This Driver divides the memory into various types.  Each location in each memory type is assigned an address.  It is therefore possible to map an address to a particular offset in a Data Array and make it accessible for reading by other connected devices.  The address structure is provided below.

 

Most of these addresses will only contain binary information to represent an active or inactive state.

 

Where multiple troubles are associated with a single device the addressed register corresponding to that device will be incremented as a counter for each trouble message and decremented when a trouble is cleared.  These addresses should preferably be stored in SINT16 format in the Data Array.

Parameter

Addresses

For each SLC loop per Node

Memory Type : Detector ; Module

Fire Alarm

1 – 159

Security Life

160 – 318

Life Critical

319 – 477

Medical Emergency

478 – 636

Security Alarm

637 – 795

Critical Process

796 – 954

Supervisory

955 - 1113

Disabled

1114 – 1272

Prealarm

1273 – 1431

Active

1432 – 1590

ON/OFF

1591 – 1749

Memory Type : Detector_Trouble; Module_Trouble

Troubles/Faults

1 – 159

 

Parameter

Addresses

For each Node

 

Memory Type : Node_Trouble

Troubles/Faults

1 – 508

Memory Type : Panel

Panel (Maximum12 Boards and 8 Panel circuits  per Board )

Hardware address        memory address

Board 1 panel 1           1

Board 1 panel 2           2

Board 2  panel 1           9

-----

-----

Board 12 panel 8           96

)

Fire Alarm

1 – 96

Security Life

97 - 192

Life Critical

193 - 288

Medical Emergency

289 - 384

Security Alarm

385 - 480

Critical Process

481 - 576

Supervisory

577 - 672

Disabled

673 - 768

Prealarm

769 - 864

Active

865 - 960

ON/OFF

961 - 1056

Memory Type : Panel_Trouble

Troubles/Faults

1–96

Memory Type : Bell_Trouble

Troubles/Faults

1-4

Driver Limitations & Exclusions

· Zone information will not be recorded.

· To synchronize the FieldServer with the panel, connect the running FieldServer and press the “System Reset” button on the panel.  All current events will be re-sent to the FieldServer.

· The port must be enabled on the unit and set to 80 columns with NO supervision

· All data related to non-event driven reports will not be recorded by the FieldServer

· This driver was written as a subset of NFS2-3030/NCA-2 EIA-232 Protocol & Data Formats 53219 Rev A 1/3/2008.  Any changes or additions by Notifier will not be reflected in this driver unless specifically revised.

· This driver will not record information about zone status that is incorporated with point status messages.

· There can only be one panel connected to any given FieldServer port.

· This driver records data as presented to the printer/CRT port by the Notifier panel, and can only be as accurate as this data.

· The driver cannot send messages to the Notifier panel.

· Driver will clear any data on “System Normal” only if this data is previously set by driver and is not yet cleared by “Cleared” message and is configured to Clear_on_Normal. By default Clear_on_Normal is “yes”.

· Driver will clear any Node data on “System RESET” only if this data is previously set by driver and is not yet cleared by “Cleared” message and is configured to Clear_on_Reset. By default Clear_on_Reset is “no”.