FS-8700-03 - Allen Bradley DF1, Full Duplex and Half Duplex

Up one level

FieldServer Driver - Serial
FS-8700-03
Allen Bradley DF1, Full Duplex and Half Duplex

Description

The DF1 driver allows the FieldServer to transfer data to and from devices over RS-232 using DF1 protocol. The FieldServer can emulate either a Server or Client.

Formal Driver Type

Serial
Client or Server

Compatibility Matrix

FieldServer Model Compatible with this driver
FS-x2010 Yes
FS-x2011 Yes
FS-x40 Yes

Connection Information

Connection type: RS-232 Half Duplex
Baud Rates: 300 to 115200; 9600
Data Bits: 8
Stop Bits: 1,2
Parity: Odd, Even, None
Multidrop Capability: No
Error Checking CRC, BCC (BCC recommended)
Handshaking None, RTS delay

Proprietary Devices tested

Device Tested (FACTORY, SITE)
SLC 5/01 Factory
SLC 5/02 Factory
SLC 5/03 Factory
SLC 5/04 Factory
PLC 3 Site
PLC 5 Site

Connection configurations

Communications functions - Supported functions at a glance:

Data Types Supported

FieldServer Data Type Description (or Device Data Type)
I Input
O Output
B Bit
N Integer
C Counter
T Timer
S System Status
St String
F Float

Command Support

The following commands are supported by the FieldServer for the various PLC types.

PLC_Type File_Type FNC Read FNC Write Typical Command
PLC 3 N
F
B
1
1
1
Range Read
Range Read
Range Read
0
0
2
Range Write
Range Write
Bit Write
N7: 3, L5
F12: 3 L5
B3/4: 5 L5
PLC 5 N
F
B
1
1
1
Range Read
Range Read
Range Read
0
67
26
Range Write
Typed Write
Read Modify Write
N7: 3, L5
F12: 3 L5
B3/4: 5 L5
SLC5 N
F
B
I
O
A2
A2
A2
A2
A2
Protracted Typed Logical Read
Protracted Typed Logical Read
Protracted Typed Logical Read
Protracted Typed Logical Read
Protracted Typed Logical Read
AA
AA
AB
-
-
Protracted Typed Logical Write
Protracted Typed Logical Write
Protracted Typed Logical Write
-
-
N7: 3, L5
B3/4: 5 L7
B3/4: 5 L8
I: 13. L5
O: 13, L5

Unsupported Functions and Data Types

Function Reason
Programming messages FieldServer is a data transfer device, thus programming messages are not required