FieldServer Driver – Serial
FS8700-74
Veeder-Root Serial Driver
Driver Code: VRoot
Version: 1.00a
Protocol Version: ( 576013-635 Revision J)
Document Rev: 1
Devices Supported: TLS-300 TLS-350 TLS-350R
| Device | Tested |
| TLS-350 | SITE
|
Interface: RS232 or RS-485 (Half-Duplex)
Baud Rates: Std Baud Rates up to 9600 (V-R limitation)
Data Bits: 7,8
Stop Bits: 1,2
Parity: Odd, Even, None
Handshaking: None
The Veeder-Root Serial driver is a client only driver. It is not capable of acting as a slave. Ie. It cannot emulate a Veeder-Root device.
The Veeder-Root Serial driver supports a limited set of functions defined by the Veeder-Root protocol specification ( 576013-635 Revision J).
The driver is capable of exposing communication statistics so that they can be monitored by a downstream device.
Only one Veeder-Root device may be connected to each port of the FieldServer. This limitation arises because the protocol is nodeless. (Messages do not identify the source/dest node.)
Alarms may be polled using two methods. The first method is to poll for the active alarm table or the system status and have the driver store alarm states for all the tanks/sensors reporting alarms. The second method is to poll for the alarm state or specific tanks/sensors.
The following table indicates the Veeder-Root functions / queries supported by the driver.
Supported Functions
| SYSTEM REPORTS (7.2.1) | I/O DEVICE REPORTS (7.2.6) | |||||
| 101 |
1 |
System Status Report | 401 |
1 |
Input Status Report | |
| 102 |
1 |
System Configuration Report | 406 |
1 |
Relay Status Report | |
| SYSTEM DIAGNOSTIC REPORTS (7.4.1) | ||||||
| 113 |
14 |
Active Alarm Report | 901 |
1 |
Self Test Results Report | |
| 114 |
19 |
Cleared Alarm Report | 902 |
1 |
System Revision Level Report | |
| 905 |
15 |
System Revision Level Report II | ||||
| IN-TANK REPORTS (7.2.2) | ||||||
| 201 |
1 |
In-Tank Inventory Report | ||||
| CONTROL FUNCTIONS (7.1) | ||||||
| 1 |
1 |
System Reset | ||||
| 2 |
1 |
Clear Power Reset Flag | ||||
| 205 |
1 |
In-Tank Status Report | 3 |
1 |
Remote Alarm Reset | |
| 20C |
15 |
In-Tank Most Recent Delivery Report | 31 |
10 |
Confirm Clear Function | |
| 20D |
15 |
In-Tank Stick Height Report | 51 |
1 |
Clear In-Tank Delivery Reports | |
| 52 |
1 |
Start In-Tank Leak Detect Test | ||||
| SENSOR REPORTS (7.2.3) | 53 |
1 |
Stop In-Tank Leak Detect Test | |||
| 301 |
1 |
Liquid Sensor Status Report | 54 |
5 |
Delete CSLD Rate Table | |
| 306 |
1 |
Vapor Sensor Status Report | 81 |
7 |
Start Pressure Line Leak Test (3.0 GPH only in V18) | |
| 311 |
1 |
Groundwater Sensor Status Report | 82 |
7 |
Stop Pressure Line Leak Test | |
| 341 |
2 |
Type A (2 Wire CL) Sensor Status Report | 83 |
10 |
Start WPLLD Line Leak Test (3.0 GPH only in V18) | |
| 346 |
2 |
Type B (3 Wire CL) Sensor Status Report | 84 |
10 |
Stop WPLLD Line Leak Test | |
| 34B |
4 |
Universal Sensor Status Report | ||||
Known Exclusions
| CONTROL FUNCTIONS (7.1) | SENSOR SETUP (7.3.5) (Continued) | |||||
| 711 |
1 |
Set Groundwater Sensor Configuration | ||||
| 712 |
1 |
Set Groundwater Sensor Location Label | ||||
| 713 |
2 |
Set Groundwater Sensor Category | ||||
| 741 |
2 |
Set Type A (2 Wire CL) Sensor Configuration | ||||
| 742 |
2 |
Set Type A (2 Wire CL) Sensor Location Label | ||||
| 743 |
2 |
Set Type A (2 Wire CL) Sensor Type | ||||
| 744 |
2 |
Set Type A (2 Wire CL) Sensor Category | ||||
| 746 |
2 |
Set Type B (3 Wire CL) Sensor Configuration | ||||
| 747 |
2 |
Set Type B (3 Wire CL) Sensor Location Label | ||||
| 748 |
5 |
Set Type B (3 Wire CL) Sensor Type | ||||
| 749 |
2 |
Set Type B (3 Wire CL) Sensor Category | ||||
| 74B |
4 |
Set Universal Sensor Configuration | ||||
| 87 |
18 |
Start Pressure Line Leak Test by Type | 74C |
4 |
Set Universal Sensor Location Label | |
| 88 |
18 |
Start WPLLD Line Leak Test by Type | 74D |
4 |
Set Universal Sensor Type | |
| 89 |
19 |
Pressure Line Leak Pressure Offset Reset | 74E |
4 |
Set Universal Sensor Category | |
| 90 |
19 |
WPLLD Line Leak Pressure Offset Reset | VOLUMETRIC LINE LEAK SETUP (7.3.6) | |||
| 91 |
15 |
Close Current Shift | ||||
| 751 |
1 |
Set Volumetric Line Leak Configuration | ||||
| OPERATIONAL REPORTS (7.2) | 752 |
1 |
Set Volumetric Line Leak Tank Number | |||
| SYSTEM REPORTS (7.2.1) | 753 |
1 |
Set Volumetric Line Leak 2 Inch Pipe Length | |||
| 754 |
1 |
Set Volumetric Line Leak 3 Inch Pipe Length | ||||
| 755 |
1 |
Set Volumetric Line Leak Pump PSI | ||||
| 756 |
1 |
Set Volumetric Line Leak Piping Material | ||||
| 111 |
2 |
Priority Alarm History Report | 757 |
1 |
Set Volumetric Line Leak Shutdown Rate | |
| 112 |
2 |
Non-Priority Alarm History Report | 758 |
1 |
Set Volumetric Line Leak Pump Side Test | |
| 759 |
1 |
Set Volumetric Line Leak Test Type & Start Time | ||||
| 75A |
1 |
Set Line Leak Lockout Schedule (All Types) | ||||
| 116 |
119 |
Service Report History | 75B |
2 |
Set Line Disable Alarm Assignments | |
| IN-TANK REPORTS (7.2.2) | ||||||
| VOLUMETRIC LINE LEAK SETUP (7.3.6) (Continued) | ||||||
| 202 |
1 |
In-Tank Delivery Report | 75C |
2 |
Set Volumetric Line Leak Last Annual Test | |
| 203 |
1 |
In-Tank Leak Detect Report | 75D |
4 |
Set Volumetric Line Leak Dispense Mode | |
| 204 |
1 |
In-Tank Shift Inventory Report | 75E |
4 |
Set Volumetric Line Leak Fuel Type | |
| 75F |
5 |
Set Volumetric Line Leak Wait Method | ||||
| 206 |
1 |
In-Tank Alarm History Report | 760 |
6 |
Set Volumetric Line Leak Location Label | |
| 207 |
2 |
In-Tank Leak Test History Report | 761 |
7 |
Set Volumetric Line Leak Blend Partner | |
| 208 |
2 |
In-Tank Leak Test Results Report | PUMP SENSOR SETUP (7.3.7) | |||
| 20A |
110 |
HRM Adjusted Delivery Report | ||||
| 20B |
110 |
BIR Adjusted Delivery Report | 771 |
2 |
Set Pump Sensor Configuration | |
| 772 |
2 |
Set Pump Sensor Tank Number | ||||
| 773 |
4 |
Set Pump Sensor Dispense Mode | ||||
| 211 |
14 |
Tank Chart Report | PRESSURE LINE LEAK SETUP (7.3.8) | |||
| 221 |
116 |
Ticketed Delivery Report | ||||
| 225 |
116 |
Periodic Delivery Variance Report | 77C |
19 |
Set Pressure Line Leak Low Pressure Shutoff | |
| 226 |
116 |
Weekly Delivery Variance Report | 77D |
19 |
Set Pressure Line Leak Altitude Pressure Offset | |
| 227 |
116 |
Daily Delivery Variance Report | 77F |
17 |
Set Pressure Line Leak Secondary Pipe Length | |
| 780 |
7 |
Pressure Line Leak General Setup Inquiry | ||||
| IN-TANK REPORTS (7.2.2) (Continued) | 781 |
7 |
Set Pressure Line Leak Configuration | |||
| 782 |
7 |
Set Pressure Line Leak Label | ||||
| 251 |
3 |
CSLD Results Report | 783 |
7 |
Set Pressure Line Leak 0.10 GPH Test Schedule | |
| 281 |
3 |
Fuel Management Report | 784 |
7 |
Set Pressure Line Leak Shutdown Rate | |
| 282 |
119 |
FLS Diagnostic: Volume History Table | 785 |
7 |
Set Pressure Line Leak Tank Number | |
| 200 |
14 |
In-Tank Stored Inventory Report | 786 |
7 |
Set Pressure Line Leak Dispense Mode | |
| SENSOR REPORTS (7.2.3) | 787 |
7 |
Set Pressure Line Leak Disable Alarm Assignments | |||
| 788 |
9 |
Set Pressure Line Leak Piping Material | ||||
| 789 |
9 |
Set Pressure Line Leak Primary Pipe Length | ||||
| 302 |
1 |
Liquid Sensor Alarm History Report | 78A |
11 |
Set Pressure Line Leak Sensor Type | |
| 78B |
16 |
Set Pressure Line Leak 0.10 GPH Test Schedule | ||||
| 307 |
1 |
Vapor Sensor Alarm History Report | 78C |
12 |
Set Pressure Line Leak 0.20 GPH Test Schedule | |
| 78E |
17 |
Set Pressure Line Leak 0.1 GPH Auto Test Enable | ||||
| 312 |
1 |
Groundwater Sensor Alarm History Report | 78F |
17 |
Set Pressure Line Leak Dispense Threshold | |
| 342 |
2 |
Type A (2 Wire CL) Sensor Alarm History Report | RECONCILIATION SETUP (7.3.9) | |||
| 347 |
2 |
Type B (3 Wire CL) Sensor Alarm History Report | 791 |
106 |
Set Mechanical Dispenser Interface String | |
| 792 |
106 |
Set Electronic Dispenser Interface String | ||||
| 34C |
4 |
Universal Sensor Alarm History Report | 793 |
106 |
Set Reconciliation Auto Daily Closing Time | |
| 794 |
106 |
Set Auto Shift Closing Time 1 | ||||
| LINE LEAK REPORTS (7.2.4) | 795 |
106 |
Set Periodic Reconciliation Mode | |||
| 796 |
106 |
Set Periodic Reconciliation Report Length | ||||
| 351 |
1 |
Volumetric Line Leak Result Report | 797 |
106 |
Set Periodic Reconciliation Alarm Flag | |
| 352 |
1 |
Volumetric Line Leak Alarm History Report | 798 |
106 |
Set Periodic Reconciliation Alarm Threshold | |
| 353 |
2 |
Volumetric Line Leak Pump Status | 799 |
106 |
Set Periodic Reconciliation Alarm Offset | |
| 373 |
14 |
Pressure Line Leak Test Results (with 0.20 test data) | 79A |
106 |
Set Remote Printer Reconciliation Report Format | |
| 374 |
14 |
Pressure Line Leak Test History (with 0.20 test data) | 79B |
106 |
Set Shift Manual Adjustment Value | |
| 79C |
106 |
Set Daily Manual Adjustment Value | ||||
| 382 |
7 |
Pressure Line Leak Alarm History Report | 79D |
106 |
Close Current Reconciliation Shift | |
| 383 |
7 |
Pressure Line Leak Test Results (0.10 test data only) | 79E |
106 |
Clear Tank Map Table | |
| 384 |
7 |
Pressure Line Leak Test History (0.10 test data only) | 79F |
108 |
Set BIR Temperature Compensation Flag | |
| 387 |
10 |
WPLLD Line Leak Alarm History Report | WIRELESS PLLD SETUP (7.3.10) | |||
| 388 |
10 |
WPLLD Line Leak Test Results | ||||
| 389 |
12 |
WPLLD Line Leak Test History | 7A0 |
10 |
WPLLD Line Leak General Setup | |
| MISCELLANEOUS REPORTS (7.2.5) | 7A1 |
10 |
Set WPLLD Line Leak Configuration | |||
| 7A2 |
10 |
Set WPLLD Line Leak Label | ||||
| 391 |
10 |
Tanker Load Report | 7A3 |
10 |
Set WPLLD Line Leak 0.20 GPH Test Schedule | |
| I/O DEVICE REPORTS (7.2.6) | 7A4 |
10 |
Set WPLLD Line Leak Shutdown Rate | |||
| 7A5 |
10 |
Set WPLLD Line Leak Tank Number | ||||
| 7A6 |
10 |
Set WPLLD Line Leak Dispense Mode | ||||
| 402 |
1 |
Input Alarm History Report | 7A7 |
10 |
Set WPLLD Line Disable Alarm Assignments | |
| 403 |
5 |
Input/Generator Alarm History Report | 7A8 |
10 |
Set WPLLD Line Leak Pipe Type | |
| 7A9 |
10 |
Set WPLLD Line Leak Pipe Length | ||||
| 7AA |
11 |
Set WPLLD 0.10 GPH Test Schedule | ||||
| SETUP FUNCTIONS & REPORTS (7.3) | 7AC |
17 |
Set WPLLD Line Leak 0.10 GPH Test Schedule | |||
| SYSTEM SETUP (7.3.1) | 7AF |
19 |
Set WPLLD Line Leak Altitude Pressure Offset | |||
| METER MAP & DELIVERY TICKET SETUP (7.3.11) | ||||||
| 501 |
1 |
Set Time of day | ||||
| 502 |
1 |
Set Shift Start Time 1 | 7B1 |
110 |
Set BIR Meter/Tank mapping | |
| 503 |
1 |
Set Print Header Line 1 | 7B5 |
116 |
Set Ticketed Delivery | |
| 504 |
1 |
Set System RS-232 Security Code | ||||
| 505 |
1 |
Set System Type & Language Flags | I/O DEVICE SETUP (7.3.12) | |||
| 506 |
2 |
Set Periodic Test Needed Warning | ||||
| 507 |
4 |
Set Days Before Periodic Test Needed Warning | 7BC |
19 |
Set Line Disable Alarm Assignments II | |
| 508 |
4 |
Set Days Before Periodic Test Needed Alarm | 7BD |
19 |
Set Pressure Line Disable Alarm Assignments II | |
| 509 |
4 |
Set Annual Test Needed Warning | 7BE |
19 |
Set WPLLD Line Disable Alarm Assignments II | |
| 50A |
4 |
Set Days Before Annual Test Needed Warning | 801 |
1 |
Set Input Configuration | |
| 50B |
4 |
Set Days Before Annual Test Needed Alarm | 802 |
1 |
Set Input Location Label | |
| 50C |
5 |
Set Remote Printer Page Eject Flag | 803 |
1 |
Set Input Type | |
| 50D |
8 |
Set Print Temperature Compensation Flag | 804 |
4 |
Set Input Dispense Mode | |
| 50E |
8 |
Set Temperature Compensation Value | 806 |
1 |
Set Relay Configuration | |
| 50F |
10 |
Set System Date/Time Display Format | 807 |
1 |
Set Relay Location Label | |
| 511 |
110 |
Set BIR Shift Printouts Flag | 808 |
1 |
Set Relay Alarm Assignments | |
| 512 |
110 |
Set BIR Daily Printouts Flag | 809 |
2 |
Set Relay Orientation | |
| 513 |
10 |
Set Tanker Load Report Flag | 80A |
4 |
S et R elay T ype | |
| 514 |
10 |
Set H-Protocol Height/Volume format | 80B |
4 |
Set Relay Tank Assignment | |
| 515 |
110 |
Set HRM – QPLD Monthly Printout | EEPROM SETUP (7.3.13) | |||
| 516 |
14 |
Set Re-direct Local Printout Flag | ||||
| 517 |
15 |
Set System Type & Language Flags | 851 |
107 |
Restore All Setup Data from EEPROM | |
| 518 |
15 |
Set Secondary Language Code Page Output | 852 |
107 |
Save All Setup Data to EEPROM | |
| 519 |
15 |
Set PLLD & WPLLD Duration Before Precision Retest | 853 |
107 |
Clear All Setup Data from EEPROM | |
| MISCELLANEOUS SETUP (7.3.14) | ||||||
| SYSTEM SETUP (7.3.1) (Continued) | ||||||
| 881 |
9 |
Set Communication Port Data | ||||
| 51A |
15 |
Set Enable/Disable Auto Daylight Saving Time | 882 |
9 |
Initialize Communication Port Data | |
| 51B |
15 |
Set Start/End Daylight Saving Date and Time | 885 |
19 |
Set SiteLink Modem Type | |
| 51C |
116 |
Set Ticketed Delivery Flag Enable | 888 |
19 |
Communication Status Information | |
| 51D |
116 |
Set Ticketed Delivery Temperature Compensation Flag | 891 |
108 |
Set AccuChart Calibration Restart | |
| 51E |
116 |
Set Ticketed Delivery Close Day of Week | 8BC |
19 |
Set Relay Alarm Assignments II | |
| COMMUNICATIONS SETUP (7.3.2) | ||||||
| SYSTEM DIAGNOSTIC REPORTS (7.4.1) | ||||||
| 521 |
2 |
Set Receiver Configuration Flag | ||||
| 522 |
2 |
Set Receiver Location Label | ||||
| 523 |
2 |
Set Receiver Telephone Number | ||||
| 524 |
2 |
Set Receiver Dialing Destination Type | 903 |
106 |
PC Diagnostic Report | |
| 525 |
2 |
Set Receiver Port Number to Dial | ||||
| 526 |
2 |
Set Receiver Retry Number | IN-TANK DIAGNOSTIC REPORTS (7.4.2) | |||
| 527 |
2 |
Set Receiver Retry Delay Time | ||||
| 528 |
2 |
Set Receiver Confirmation Report Flag | A01 |
1 |
Probe Type and Serial Number | |
| 529 |
19 |
Set Fax Auto Dial Method | A02 |
1 |
Probe Factory Dry Calibration Values | |
| 52A |
3 |
Set Receiver Report List | A03 |
1 |
Probe Factory Wet Calibration Values | |
| 52B |
3 |
Set Receiver Auto Dial Type and Start Time | A04 |
1 |
Probe Updated Dry Calibration Values | |
| 52C |
3 |
Set Receiver Auto Dial On Alarms | A05 |
1 |
Probe Updated Wet Calibration Values | |
| 52D |
17 |
Autodial Alarm Status | A06 |
1 |
Probe Segment Sensitivity Ratios | |
| 52E |
19 |
Set Delay for Autodial on Alarm Clear | A10 |
1 |
Probe Last Sample Buffers | |
| 52F |
19 |
Set Receiver Alarm Status | A11 |
1 |
Probe Fast Average Buffers | |
| 531 |
8 |
Set RS-232 End of Message | A12 |
1 |
Probe Standard Average Buffers | |
| A13 |
1 |
Probe Long Term Average Buffers | ||||
| WARNING | ALARM | & AUTO-PRINT SETUP (7.3.3) | A20 |
1 |
Probe Leak Test Flags – Present Test | |
| A22 |
2 |
Probe Leak Test Flags – Gross Test | ||||
| 532 |
116 |
Set Ticketed Variance Analysis Printout Flags | A23 |
5 |
Tank Leak Test Averaging Buffers | |
| 533 |
116 |
Set Ticketed Delivery Book Variance Printout Flags | A51 |
3 |
CSLD Diagnostics: Rate Table | |
| 534 |
116 |
Set Ticketed Delivery Variance Printout Flags | A52 |
3 |
CSLD Diagnostics: Rate Test | |
| 546 |
15 |
Set Tank Periodic Test Needed Warning | A53 |
3 |
CSLD Diagnostics: Volume History Table | |
| 547 |
15 |
Set Days Before Tank Periodic Test Needed Warning | A54 |
3 |
CSLD Diagnostics: Moving Average Table | |
| 548 |
15 |
Set Days Before Tank Periodic Test Needed Alarm | A55 |
3 |
CSLD Diagnostics: Leak Test Status | |
| 549 |
15 |
Set Tank Annual Test Needed Warning | A61 |
110 |
HRM Diagnostic Report | |
| 54A |
15 |
Set Days Before Tank Annual Test Needed Warning | A62 |
112 |
HRM Daily History | |
| 54B |
15 |
Set Days Before Tank Annual Test Needed Alarm | A81 |
6 |
Fuel Management Diagnostic Report | |
| 54C |
19 |
Set CSLD Evaporation Reid Vapor Pressure Chart | A91 |
9 |
Power Outage Diagnostic Report | |
| 553 |
19 |
Set Line Re-Enable Method | ||||
| 554 |
18 |
Set Periodic Line Leak Test Auto-Confirm | SENSOR DIAGNOSTIC REPORTS (7.4.3) | |||
| 555 |
18 |
Set Annual Line Leak Test Auto-Confirm | ||||
| 556 |
15 |
Set Line Periodic Test Needed Warning | B01 |
1 |
Liquid Sensor Diagnostic Report | |
| 557 |
15 |
Set Days Before Line Periodic Test Needed Warning | B06 |
1 |
Vapor Sensor Diagnostic Report | |
| 558 |
15 |
Set Days Before Line Periodic Test Needed Alarm | B07 |
3 |
Vapor Sensor Concentration (PPM) Report | |
| 559 |
15 |
Set Line Annual Test Needed Warning | B11 |
1 |
Groundwater Sensor Diagnostic Report | |
| 55A |
15 |
Set Days Before Line Annual Test Needed Warning | B21 |
1 |
Ground Temperature Sensor Diagnostic Report | |
| 55B |
15 |
Set Days Before Line Annual Test Needed Alarm | B41 |
2 |
Type A Sensor (2 Wire CL) Diagnostic Report | |
| 5BC |
19 |
Set Receiver Auto Dial on Alarm II | B46 |
2 |
Type B Sensor (3 Wire CL) Diagnostic Report | |
| 500 |
14 |
Set Inventory Record Time 1 | B4B |
4 |
Universal Sensor Diagnostic Report | |
| LINE LEAK DIAGNOSTIC REPORTS (7.4.4) | ||||||
| IN-TANK SETUP (7.3.4) | ||||||
| B50 |
1 |
Volumetric Line Leak Status | ||||
| 601 |
1 |
Set Tank Configuration | B51 |
1 |
Volumetric Line Leak Diagnostic Gross Test History | |
| 602 |
1 |
Set Tank Product Label | B52 |
1 |
Volumetric Line Leak 0.1 & 0.2 GPH Diagnostic History | |
| 603 |
1 |
Set Tank Product Code | B71 |
2 |
Pump Sensor Diagnostic | |
| 604 |
1 |
Set Tank 1 Point Full Height Volume | B7C |
19 |
Pressure Line Leak Pressure Offset Test | |
| 605 |
1 |
Set Tank 4 Point Full | B7D |
19 |
WPPLD Line Leak Pressure Offset Test | |
| 606 |
1 |
Set Tank 20 Point Full | B7E |
19 |
Pressure Line Leak Pressure Offset Monitor Report | |
| 607 |
1 |
Set Tank Diameter | B7F |
19 |
WPLLD Line Leak Pressure Offset Monitor Report | |
| 608 |
1 |
Set Tank Tilt | B81 |
7 |
Pressure Line Leak Diagnostic Report | |
| 609 |
1 |
Set Tank Thermal Expansion Coefficient | B82 |
10 |
WPLLD Line Leak Diagnostic Report | |
| 60A |
9 |
Set Tank Linear Calculated Full Volume | B83 |
10 |
WPLLD Line Leak Communication Diagnostic Report | |
| 60B |
15 |
Set Tank Stick Height Function Enable | ||||
| 60C |
15 |
Set Tank Stick Height Offset | LINE LEAK DIAGNOSTIC REPORTS (7.4.4) (continued) | |||
| 610 |
1 |
Set Tank Delivery Delay | ||||
| 611 |
1 |
Set Tank Leak Test Type & Start Time | B87 |
19 |
Pressure Line Leak 3.0 GPH Test Diagnostic | |
| 612 |
1 |
Set Tank Manifolded Partners | B88 |
19 |
Pressure Line Leak Mid-range Test Diagnostic | |
| 613 |
3 |
Set CSLD Probability of Detection | B89 |
19 |
Pressure Line Leak 0.2 GPH Test Diagnostic | |
| 614 |
5 |
Set CSLD Climate Factor | B8A |
19 |
Pressure Line Leak 0.1 GPH Test Diagnostic | |
| 615 |
108 |
Set BIR Meter Data Present | B8B |
19 |
WPLLD Line Leak 3.0 GPH Test Diagnostic | |
| 616 |
110 |
Set AccuChart Update Scheduling | B8C |
19 |
WPLLD Line Leak Mid-range Test Diagnostic | |
| 618 |
19 |
Set Tank CSLD Evaporation Compensation | B8D |
19 |
WPLLD Line Leak 0.2 GPH Test Diagnostic | |
| 619 |
19 |
Set Tank Stage II Vapor Recovery | B8E |
19 |
WPLLD Line Leak 0.1 GPH Test Diagnostic | |
| 621 |
1 |
Set Tank Low Level Limit | RECONCILIATION | |||
| 622 |
1 |
Set Tank High Level Limit | ||||
| 623 |
1 |
Set Tank Overfill Level Limit | B91 |
108 |
AccuChart Diagnostics Report | |
| 624 |
1 |
Set Tank High Water Level Limit | B93 |
108 |
AccuChart Status Report | |
| 625 |
1 |
Set Tank Sudden Loss Limit | B94 |
108 |
AccuChart Calibration History Report | |
| 626 |
1 |
Set Tank Leak Alarm Limit | BA0 |
110 |
MDIM Totalizer Report | |
| 627 |
2 |
Set Tank High Water Warning Limit | RECONCILIATION REPORTS (7.5) | |||
| 628 |
2 |
Set Tank Maximum Volume Limit | ||||
| 629 |
2 |
Set Tank Delivery Required Limit | C01 |
106 |
Basic Inventory Reconciliation Daily “Row” Report | |
| 62A |
2 |
Set Tank Annual Leak Test Minimum Volume | C02 |
106 |
Basic Inventory Reconciliation Daily “Column” Report | |
| C03 |
106 |
Basic Inventory Reconciliation Shift “Row” Report | ||||
| IN-TANK SETUP (7.3.4) (Continued) | C04 |
106 |
Basic Inventory Reconciliation Shift “Column” Report | |||
| C05 |
106 |
Basic Inventory Reconciliation Periodic “Row” Report | ||||
| 62B |
2 |
Set Tank Last Annual Test | C06 |
106 |
Basic Inventory Reconciliation Periodic “Column” Report | |
| 62C |
2 |
Set Tank Periodic Test Type | C07 |
114 |
Basic Inventory Reconciliation Periodic “Row” Report | |
| 62D |
2 |
Set Enable/Disable Tank Leak Test Fail Alarms | C08 |
114 |
Basic Inventory Reconciliation Periodic “Column” Report | |
| 62E |
3 |
Set CAP0 Probe Conductive Boot Flag | C09 |
119 |
Individual Basic Reconciliation Daily History Diagnostic | |
| 62F |
3 |
Set Mag Probe Float Size | ||||
| 630 |
3 |
Set Tank Leak Test Notify | VARIANCE ANALYSIS REPORTS (7.6) | |||
| 631 |
5 |
Set Tank Leak Test Averaging | ||||
| 632 |
5 |
Set Tank Test Siphon Break | C10 |
116 |
Periodic Book Variance | |
| 633 |
9 |
Set Leak Test Report Type | C11 |
116 |
Weekly Book Variance | |
| 634 |
110 |
Set Tank HRM Reconciliation Warning Limit | C12 |
116 |
Daily Book Variance | |
| 635 |
110 |
Set Tank HRM Reconciliation Alarm Limit | C20 |
116 |
Periodic Variance Analysis Report | |
| 636 |
14 |
Set Tank Periodic Leak Test Minimum Volume | C21 |
116 |
Weekly Variance Analysis Report | |
| 639 |
115 |
Set Tank AccuChart End Shape Type and Factor | C22 |
116 |
Daily Variance Analysis Report | |
| 680 |
6 |
Fuel Management General Setup Inquiry | C25 |
119 |
Periodic Variance Analysis Daily Report | |
| 681 |
6 |
Set Fuel Management Delivery Needed Warning | ||||
| 682 |
6 |
Set Fuel Management Automatic Report Print Time | ||||
| 683 |
6 |
Set Fuel Management Average Daily Sales | ||||
| SENSOR SETUP (7.3.5) | ||||||
| 701 |
1 |
Set Liquid Sensor Configuration | ||||
| 702 |
1 |
Set Liquid Sensor Location Label | ||||
| 703 |
1 |
Set Liquid Sensor Type | ||||
| 704 |
2 |
Set Liquid Sensor Category | ||||
| 706 |
1 |
Set Vapor Sensor Configuration | ||||
| 707 |
1 |
Set Vapor Sensor Location Label | ||||
| 708 |
1 |
Set Vapor Sensor Alarm Threshold | ||||
| 709 |
2 |
Set Vapor Sensor Category | ||||