FS8700-74 – Veeder-Root Serial Driver

FieldServer Driver – Serial

FS8700-74

Veeder-Root Serial Driver

 

Driver Code: VRoot

Version: 1.00a

Protocol Version: ( 576013-635 Revision J)

Document Rev:                        1

Devices Supported: TLS-300 TLS-350 TLS-350R

 

Device Tested
TLS-350 SITE

 

 

Interface: RS232 or RS-485 (Half-Duplex)

Baud Rates: Std Baud Rates up to 9600 (V-R limitation)

Data Bits: 7,8

Stop Bits: 1,2

Parity: Odd, Even, None

Handshaking: None

 

The Veeder-Root Serial driver is a client only driver. It is not capable of acting as a slave. Ie. It cannot emulate a Veeder-Root device.

The Veeder-Root Serial driver supports a limited set of functions defined by the Veeder-Root protocol specification ( 576013-635 Revision J).

The driver is capable of exposing communication statistics so that they can be monitored by a downstream device.

Only one Veeder-Root device may be connected to each port of the FieldServer. This limitation arises because the protocol is nodeless. (Messages do not identify the source/dest node.)

Alarms may be polled using two methods. The first method is to poll for the active alarm table or the system status and have the driver store alarm states for all the tanks/sensors reporting alarms. The second method is to poll for the alarm state or specific tanks/sensors.

The following table indicates the Veeder-Root functions / queries supported by the driver.

 

Supported Functions

SYSTEM REPORTS (7.2.1) I/O DEVICE REPORTS (7.2.6)
101

1

System Status Report 401

1

Input Status Report
102

1

System Configuration Report 406

1

Relay Status Report
SYSTEM DIAGNOSTIC REPORTS (7.4.1)
113

14

Active Alarm Report 901

1

Self Test Results Report
114

19

Cleared Alarm Report 902

1

System Revision Level Report
905

15

System Revision Level Report II
IN-TANK REPORTS (7.2.2)
201

1

In-Tank Inventory Report
CONTROL FUNCTIONS (7.1)
1

1

System Reset
2

1

Clear Power Reset Flag
205

1

In-Tank Status Report 3

1

Remote Alarm Reset
20C

15

In-Tank Most Recent Delivery Report 31

10

Confirm Clear Function
20D

15

In-Tank Stick Height Report 51

1

Clear In-Tank Delivery Reports
52

1

Start In-Tank Leak Detect Test
SENSOR REPORTS (7.2.3) 53

1

Stop In-Tank Leak Detect Test
301

1

Liquid Sensor Status Report 54

5

Delete CSLD Rate Table
306

1

Vapor Sensor Status Report 81

7

Start Pressure Line Leak Test (3.0 GPH only in V18)
311

1

Groundwater Sensor Status Report 82

7

Stop Pressure Line Leak Test
341

2

Type A (2 Wire CL) Sensor Status Report 83

10

Start WPLLD Line Leak Test (3.0 GPH only in V18)
346

2

Type B (3 Wire CL) Sensor Status Report 84

10

Stop WPLLD Line Leak Test
34B

4

Universal Sensor Status Report

Known Exclusions

 

CONTROL FUNCTIONS (7.1) SENSOR SETUP (7.3.5) (Continued)
711

1

Set Groundwater Sensor Configuration
712

1

Set Groundwater Sensor Location Label
713

2

Set Groundwater Sensor Category
741

2

Set Type A (2 Wire CL) Sensor Configuration
742

2

Set Type A (2 Wire CL) Sensor Location Label
743

2

Set Type A (2 Wire CL) Sensor Type
744

2

Set Type A (2 Wire CL) Sensor Category
746

2

Set Type B (3 Wire CL) Sensor Configuration
747

2

Set Type B (3 Wire CL) Sensor Location Label
748

5

Set Type B (3 Wire CL) Sensor Type
749

2

Set Type B (3 Wire CL) Sensor Category
74B

4

Set Universal Sensor Configuration
87

18

Start Pressure Line Leak Test by Type 74C

4

Set Universal Sensor Location Label
88

18

Start WPLLD Line Leak Test by Type 74D

4

Set Universal Sensor Type
89

19

Pressure Line Leak Pressure Offset Reset 74E

4

Set Universal Sensor Category
90

19

WPLLD Line Leak Pressure Offset Reset VOLUMETRIC LINE LEAK SETUP (7.3.6)
91

15

Close Current Shift
751

1

Set Volumetric Line Leak Configuration
OPERATIONAL REPORTS (7.2) 752

1

Set Volumetric Line Leak Tank Number
SYSTEM REPORTS (7.2.1) 753

1

Set Volumetric Line Leak 2 Inch Pipe Length
754

1

Set Volumetric Line Leak 3 Inch Pipe Length
755

1

Set Volumetric Line Leak Pump PSI
756

1

Set Volumetric Line Leak Piping Material
111

2

Priority Alarm History Report 757

1

Set Volumetric Line Leak Shutdown Rate
112

2

Non-Priority Alarm History Report 758

1

Set Volumetric Line Leak Pump Side Test
759

1

Set Volumetric Line Leak Test Type & Start Time
75A

1

Set Line Leak Lockout Schedule (All Types)
116

119

Service Report History 75B

2

Set Line Disable Alarm Assignments
IN-TANK REPORTS (7.2.2)
VOLUMETRIC LINE LEAK SETUP (7.3.6) (Continued)
202

1

In-Tank Delivery Report 75C

2

Set Volumetric Line Leak Last Annual Test
203

1

In-Tank Leak Detect Report 75D

4

Set Volumetric Line Leak Dispense Mode
204

1

In-Tank Shift Inventory Report 75E

4

Set Volumetric Line Leak Fuel Type
75F

5

Set Volumetric Line Leak Wait Method
206

1

In-Tank Alarm History Report 760

6

Set Volumetric Line Leak Location Label
207

2

In-Tank Leak Test History Report 761

7

Set Volumetric Line Leak Blend Partner
208

2

In-Tank Leak Test Results Report PUMP SENSOR SETUP (7.3.7)
20A

110

HRM Adjusted Delivery Report
20B

110

BIR Adjusted Delivery Report 771

2

Set Pump Sensor Configuration
772

2

Set Pump Sensor Tank Number
773

4

Set Pump Sensor Dispense Mode
211

14

Tank Chart Report PRESSURE LINE LEAK SETUP (7.3.8)
221

116

Ticketed Delivery Report
225

116

Periodic Delivery Variance Report 77C

19

Set Pressure Line Leak Low Pressure Shutoff
226

116

Weekly Delivery Variance Report 77D

19

Set Pressure Line Leak Altitude Pressure Offset
227

116

Daily Delivery Variance Report 77F

17

Set Pressure Line Leak Secondary Pipe Length
780

7

Pressure Line Leak General Setup Inquiry
IN-TANK REPORTS (7.2.2) (Continued) 781

7

Set Pressure Line Leak Configuration
782

7

Set Pressure Line Leak Label
251

3

CSLD Results Report 783

7

Set Pressure Line Leak 0.10 GPH Test Schedule
281

3

Fuel Management Report 784

7

Set Pressure Line Leak Shutdown Rate
282

119

FLS Diagnostic: Volume History Table 785

7

Set Pressure Line Leak Tank Number
200

14

In-Tank Stored Inventory Report 786

7

Set Pressure Line Leak Dispense Mode
SENSOR REPORTS (7.2.3) 787

7

Set Pressure Line Leak Disable Alarm Assignments
788

9

Set Pressure Line Leak Piping Material
789

9

Set Pressure Line Leak Primary Pipe Length
302

1

Liquid Sensor Alarm History Report 78A

11

Set Pressure Line Leak Sensor Type
78B

16

Set Pressure Line Leak 0.10 GPH Test Schedule
307

1

Vapor Sensor Alarm History Report 78C

12

Set Pressure Line Leak 0.20 GPH Test Schedule
78E

17

Set Pressure Line Leak 0.1 GPH Auto Test Enable
312

1

Groundwater Sensor Alarm History Report 78F

17

Set Pressure Line Leak Dispense Threshold
342

2

Type A (2 Wire CL) Sensor Alarm History Report RECONCILIATION SETUP (7.3.9)
347

2

Type B (3 Wire CL) Sensor Alarm History Report 791

106

Set Mechanical Dispenser Interface String
792

106

Set Electronic Dispenser Interface String
34C

4

Universal Sensor Alarm History Report 793

106

Set Reconciliation Auto Daily Closing Time
794

106

Set Auto Shift Closing Time 1
LINE LEAK REPORTS (7.2.4) 795

106

Set Periodic Reconciliation Mode
796

106

Set Periodic Reconciliation Report Length
351

1

Volumetric Line Leak Result Report 797

106

Set Periodic Reconciliation Alarm Flag
352

1

Volumetric Line Leak Alarm History Report 798

106

Set Periodic Reconciliation Alarm Threshold
353

2

Volumetric Line Leak Pump Status 799

106

Set Periodic Reconciliation Alarm Offset
373

14

Pressure Line Leak Test Results (with 0.20 test data) 79A

106

Set Remote Printer Reconciliation Report Format
374

14

Pressure Line Leak Test History (with 0.20 test data) 79B

106

Set Shift Manual Adjustment Value
79C

106

Set Daily Manual Adjustment Value
382

7

Pressure Line Leak Alarm History Report 79D

106

Close Current Reconciliation Shift
383

7

Pressure Line Leak Test Results (0.10 test data only) 79E

106

Clear Tank Map Table
384

7

Pressure Line Leak Test History (0.10 test data only) 79F

108

Set BIR Temperature Compensation Flag
387

10

WPLLD Line Leak Alarm History Report WIRELESS PLLD SETUP (7.3.10)
388

10

WPLLD Line Leak Test Results
389

12

WPLLD Line Leak Test History 7A0

10

WPLLD Line Leak General Setup
MISCELLANEOUS REPORTS (7.2.5) 7A1

10

Set WPLLD Line Leak Configuration
7A2

10

Set WPLLD Line Leak Label
391

10

Tanker Load Report 7A3

10

Set WPLLD Line Leak 0.20 GPH Test Schedule
I/O DEVICE REPORTS (7.2.6) 7A4

10

Set WPLLD Line Leak Shutdown Rate
7A5

10

Set WPLLD Line Leak Tank Number
7A6

10

Set WPLLD Line Leak Dispense Mode
402

1

Input Alarm History Report 7A7

10

Set WPLLD Line Disable Alarm Assignments
403

5

Input/Generator Alarm History Report 7A8

10

Set WPLLD Line Leak Pipe Type
7A9

10

Set WPLLD Line Leak Pipe Length
7AA

11

Set WPLLD 0.10 GPH Test Schedule
SETUP FUNCTIONS & REPORTS (7.3) 7AC

17

Set WPLLD Line Leak 0.10 GPH Test Schedule
SYSTEM SETUP (7.3.1) 7AF

19

Set WPLLD Line Leak Altitude Pressure Offset
METER MAP & DELIVERY TICKET SETUP (7.3.11)
501

1

Set Time of day
502

1

Set Shift Start Time 1 7B1

110

Set BIR Meter/Tank mapping
503

1

Set Print Header Line 1 7B5

116

Set Ticketed Delivery
504

1

Set System RS-232 Security Code
505

1

Set System Type & Language Flags I/O DEVICE SETUP (7.3.12)
506

2

Set Periodic Test Needed Warning
507

4

Set Days Before Periodic Test Needed Warning 7BC

19

Set Line Disable Alarm Assignments II
508

4

Set Days Before Periodic Test Needed Alarm 7BD

19

Set Pressure Line Disable Alarm Assignments II
509

4

Set Annual Test Needed Warning 7BE

19

Set WPLLD Line Disable Alarm Assignments II
50A

4

Set Days Before Annual Test Needed Warning 801

1

Set Input Configuration
50B

4

Set Days Before Annual Test Needed Alarm 802

1

Set Input Location Label
50C

5

Set Remote Printer Page Eject Flag 803

1

Set Input Type
50D

8

Set Print Temperature Compensation Flag 804

4

Set Input Dispense Mode
50E

8

Set Temperature Compensation Value 806

1

Set Relay Configuration
50F

10

Set System Date/Time Display Format 807

1

Set Relay Location Label
511

110

Set BIR Shift Printouts Flag 808

1

Set Relay Alarm Assignments
512

110

Set BIR Daily Printouts Flag 809

2

Set Relay Orientation
513

10

Set Tanker Load Report Flag 80A

4

S et R elay T ype
514

10

Set H-Protocol Height/Volume format 80B

4

Set Relay Tank Assignment
515

110

Set HRM – QPLD Monthly Printout EEPROM SETUP (7.3.13)
516

14

Set Re-direct Local Printout Flag
517

15

Set System Type & Language Flags 851

107

Restore All Setup Data from EEPROM
518

15

Set Secondary Language Code Page Output 852

107

Save All Setup Data to EEPROM
519

15

Set PLLD & WPLLD Duration Before Precision Retest 853

107

Clear All Setup Data from EEPROM
MISCELLANEOUS SETUP (7.3.14)
SYSTEM SETUP (7.3.1) (Continued)
881

9

Set Communication Port Data
51A

15

Set Enable/Disable Auto Daylight Saving Time 882

9

Initialize Communication Port Data
51B

15

Set Start/End Daylight Saving Date and Time 885

19

Set SiteLink Modem Type
51C

116

Set Ticketed Delivery Flag Enable 888

19

Communication Status Information
51D

116

Set Ticketed Delivery Temperature Compensation Flag 891

108

Set AccuChart Calibration Restart
51E

116

Set Ticketed Delivery Close Day of Week 8BC

19

Set Relay Alarm Assignments II
COMMUNICATIONS SETUP (7.3.2)
SYSTEM DIAGNOSTIC REPORTS (7.4.1)
521

2

Set Receiver Configuration Flag
522

2

Set Receiver Location Label
523

2

Set Receiver Telephone Number
524

2

Set Receiver Dialing Destination Type 903

106

PC Diagnostic Report
525

2

Set Receiver Port Number to Dial
526

2

Set Receiver Retry Number IN-TANK DIAGNOSTIC REPORTS (7.4.2)
527

2

Set Receiver Retry Delay Time
528

2

Set Receiver Confirmation Report Flag A01

1

Probe Type and Serial Number
529

19

Set Fax Auto Dial Method A02

1

Probe Factory Dry Calibration Values
52A

3

Set Receiver Report List A03

1

Probe Factory Wet Calibration Values
52B

3

Set Receiver Auto Dial Type and Start Time A04

1

Probe Updated Dry Calibration Values
52C

3

Set Receiver Auto Dial On Alarms A05

1

Probe Updated Wet Calibration Values
52D

17

Autodial Alarm Status A06

1

Probe Segment Sensitivity Ratios
52E

19

Set Delay for Autodial on Alarm Clear A10

1

Probe Last Sample Buffers
52F

19

Set Receiver Alarm Status A11

1

Probe Fast Average Buffers
531

8

Set RS-232 End of Message A12

1

Probe Standard Average Buffers
A13

1

Probe Long Term Average Buffers
WARNING ALARM & AUTO-PRINT SETUP (7.3.3) A20

1

Probe Leak Test Flags – Present Test
A22

2

Probe Leak Test Flags – Gross Test
532

116

Set Ticketed Variance Analysis Printout Flags A23

5

Tank Leak Test Averaging Buffers
533

116

Set Ticketed Delivery Book Variance Printout Flags A51

3

CSLD Diagnostics: Rate Table
534

116

Set Ticketed Delivery Variance Printout Flags A52

3

CSLD Diagnostics: Rate Test
546

15

Set Tank Periodic Test Needed Warning A53

3

CSLD Diagnostics: Volume History Table
547

15

Set Days Before Tank Periodic Test Needed Warning A54

3

CSLD Diagnostics: Moving Average Table
548

15

Set Days Before Tank Periodic Test Needed Alarm A55

3

CSLD Diagnostics: Leak Test Status
549

15

Set Tank Annual Test Needed Warning A61

110

HRM Diagnostic Report
54A

15

Set Days Before Tank Annual Test Needed Warning A62

112

HRM Daily History
54B

15

Set Days Before Tank Annual Test Needed Alarm A81

6

Fuel Management Diagnostic Report
54C

19

Set CSLD Evaporation Reid Vapor Pressure Chart A91

9

Power Outage Diagnostic Report
553

19

Set Line Re-Enable Method
554

18

Set Periodic Line Leak Test Auto-Confirm SENSOR DIAGNOSTIC REPORTS (7.4.3)
555

18

Set Annual Line Leak Test Auto-Confirm
556

15

Set Line Periodic Test Needed Warning B01

1

Liquid Sensor Diagnostic Report
557

15

Set Days Before Line Periodic Test Needed Warning B06

1

Vapor Sensor Diagnostic Report
558

15

Set Days Before Line Periodic Test Needed Alarm B07

3

Vapor Sensor Concentration (PPM) Report
559

15

Set Line Annual Test Needed Warning B11

1

Groundwater Sensor Diagnostic Report
55A

15

Set Days Before Line Annual Test Needed Warning B21

1

Ground Temperature Sensor Diagnostic Report
55B

15

Set Days Before Line Annual Test Needed Alarm B41

2

Type A Sensor (2 Wire CL) Diagnostic Report
5BC

19

Set Receiver Auto Dial on Alarm II B46

2

Type B Sensor (3 Wire CL) Diagnostic Report
500

14

Set Inventory Record Time 1 B4B

4

Universal Sensor Diagnostic Report
LINE LEAK DIAGNOSTIC REPORTS (7.4.4)
IN-TANK SETUP (7.3.4)
B50

1

Volumetric Line Leak Status
601

1

Set Tank Configuration B51

1

Volumetric Line Leak Diagnostic Gross Test History
602

1

Set Tank Product Label B52

1

Volumetric Line Leak 0.1 & 0.2 GPH Diagnostic History
603

1

Set Tank Product Code B71

2

Pump Sensor Diagnostic
604

1

Set Tank 1 Point Full Height Volume B7C

19

Pressure Line Leak Pressure Offset Test
605

1

Set Tank 4 Point Full B7D

19

WPPLD Line Leak Pressure Offset Test
606

1

Set Tank 20 Point Full B7E

19

Pressure Line Leak Pressure Offset Monitor Report
607

1

Set Tank Diameter B7F

19

WPLLD Line Leak Pressure Offset Monitor Report
608

1

Set Tank Tilt B81

7

Pressure Line Leak Diagnostic Report
609

1

Set Tank Thermal Expansion Coefficient B82

10

WPLLD Line Leak Diagnostic Report
60A

9

Set Tank Linear Calculated Full Volume B83

10

WPLLD Line Leak Communication Diagnostic Report
60B

15

Set Tank Stick Height Function Enable
60C

15

Set Tank Stick Height Offset LINE LEAK DIAGNOSTIC REPORTS (7.4.4) (continued)
610

1

Set Tank Delivery Delay
611

1

Set Tank Leak Test Type & Start Time B87

19

Pressure Line Leak 3.0 GPH Test Diagnostic
612

1

Set Tank Manifolded Partners B88

19

Pressure Line Leak Mid-range Test Diagnostic
613

3

Set CSLD Probability of Detection B89

19

Pressure Line Leak 0.2 GPH Test Diagnostic
614

5

Set CSLD Climate Factor B8A

19

Pressure Line Leak 0.1 GPH Test Diagnostic
615

108

Set BIR Meter Data Present B8B

19

WPLLD Line Leak 3.0 GPH Test Diagnostic
616

110

Set AccuChart Update Scheduling B8C

19

WPLLD Line Leak Mid-range Test Diagnostic
618

19

Set Tank CSLD Evaporation Compensation B8D

19

WPLLD Line Leak 0.2 GPH Test Diagnostic
619

19

Set Tank Stage II Vapor Recovery B8E

19

WPLLD Line Leak 0.1 GPH Test Diagnostic
621

1

Set Tank Low Level Limit RECONCILIATION
622

1

Set Tank High Level Limit
623

1

Set Tank Overfill Level Limit B91

108

AccuChart Diagnostics Report
624

1

Set Tank High Water Level Limit B93

108

AccuChart Status Report
625

1

Set Tank Sudden Loss Limit B94

108

AccuChart Calibration History Report
626

1

Set Tank Leak Alarm Limit BA0

110

MDIM Totalizer Report
627

2

Set Tank High Water Warning Limit RECONCILIATION REPORTS (7.5)
628

2

Set Tank Maximum Volume Limit
629

2

Set Tank Delivery Required Limit C01

106

Basic Inventory Reconciliation Daily “Row” Report
62A

2

Set Tank Annual Leak Test Minimum Volume C02

106

Basic Inventory Reconciliation Daily “Column” Report
C03

106

Basic Inventory Reconciliation Shift “Row” Report
IN-TANK SETUP (7.3.4) (Continued) C04

106

Basic Inventory Reconciliation Shift “Column” Report
C05

106

Basic Inventory Reconciliation Periodic “Row” Report
62B

2

Set Tank Last Annual Test C06

106

Basic Inventory Reconciliation Periodic “Column” Report
62C

2

Set Tank Periodic Test Type C07

114

Basic Inventory Reconciliation Periodic “Row” Report
62D

2

Set Enable/Disable Tank Leak Test Fail Alarms C08

114

Basic Inventory Reconciliation Periodic “Column” Report
62E

3

Set CAP0 Probe Conductive Boot Flag C09

119

Individual Basic Reconciliation Daily History Diagnostic
62F

3

Set Mag Probe Float Size
630

3

Set Tank Leak Test Notify VARIANCE ANALYSIS REPORTS (7.6)
631

5

Set Tank Leak Test Averaging
632

5

Set Tank Test Siphon Break C10

116

Periodic Book Variance
633

9

Set Leak Test Report Type C11

116

Weekly Book Variance
634

110

Set Tank HRM Reconciliation Warning Limit C12

116

Daily Book Variance
635

110

Set Tank HRM Reconciliation Alarm Limit C20

116

Periodic Variance Analysis Report
636

14

Set Tank Periodic Leak Test Minimum Volume C21

116

Weekly Variance Analysis Report
639

115

Set Tank AccuChart End Shape Type and Factor C22

116

Daily Variance Analysis Report
680

6

Fuel Management General Setup Inquiry C25

119

Periodic Variance Analysis Daily Report
681

6

Set Fuel Management Delivery Needed Warning
682

6

Set Fuel Management Automatic Report Print Time
683

6

Set Fuel Management Average Daily Sales
SENSOR SETUP (7.3.5)
701

1

Set Liquid Sensor Configuration
702

1

Set Liquid Sensor Location Label
703

1

Set Liquid Sensor Type
704

2

Set Liquid Sensor Category
706

1

Set Vapor Sensor Configuration
707

1

Set Vapor Sensor Location Label
708

1

Set Vapor Sensor Alarm Threshold
709

2

Set Vapor Sensor Category