Driver Version: 1.01
Document Revision: 2
FieldServer Driver – Serial
FS8700-43
VESDA
Description
The VESDA driver allows the FieldServer to read data from VESDA LaserPLUS controllers (FAS or FD type) via the VESDA High Level Interface (HLI) communications module, using ETA232. The FieldServer can be used only as a Client with this driver, and operates in the HLI Master/Slave mode.
| Fieldserver Mode | Nodes | Comments |
| Client | 1 | 1 HLI can be connected to each RS232 port |
| Server | nil | Not applicable |
Formal Driver Type
Serial
Client Only
Connection Information
| Connection type: | ETA232 |
| Baud Rates: | 19200 Baud (determined by VESDA HLI) |
| Data Bits: | 8 |
| Stop Bits: | 1 |
| Parity: | None |
| Multidrop Capability | No |
Proprietary Physical Interfaces Supported
| Fieldserver Model | Adapter Model # | Vendor | Physical Medium |
| X20, X40 | VESDA HLI |
Note: both LaserPLUS FAS (First Alarm Sector) and FD types are supportedVESDAETA232
Devices tested
| Device | Tested (FACTORY, SITE) |
| VESDA HLI | FACTORY |
Connection configurations
Communications functions – Supported functions at a glance
Data Types Supported
| FieldServer Data Type | Description (or Device Data Type) |
| Analog Input | Smoke Level, Airflow |
| Digital Input | Pipe Status, Faults, Alarms |
| Analog Register | n/a |
| Digital Register | n/a |
| Analog Output | n/a |
| Digital Output | Remote Input commands |
Read Operations supported
| FieldServer as a Client | FieldServer as a Server |
| Read Analog / Binary Status: | n/a |
| Zone Update (Command 4) |
Update Display Status (Command 10)
Current Fault Status (Command 12)
Update Airflow Status (Command 16)n/a
Write (control) Operations supported
| FieldServer as a Client | FieldServer as a Server |
| Write Binary Commands: | n/a |
| Remote Input (command 6) – values: Reset, Isolate, De-Isolate, Silence, Test, Scan Start, Scan Stop | n/a |
Unsupported Functions and Data Types
| Function | Reason |
| Comprehensive Level Interface functionality | FieldServer is a data transfer device, and as such, programming and configuration messages are not implemented |
THIS PAGE INTENTIONALLY LEFT BLANK