FS8700-14 – GE Mark IV Speedtronic

Driver Version: 1.01

Document Revision: 5

FieldServer Driver – Serial

FS8700-14

GE Mark IV Speedtronic

 

Description

The GE Mark IV Speedtronic driver allows the FieldServer to receive status data from GE Mark IV Speedtronic devices. The driver can receive data over a RS-232 or RS-485 serial communications line.  The driver can only receive status data and therefore acts as a passive client.

 

Fieldserver Mode Nodes Comments
Client 1-10 (max) The max number of nodes is limited by the amount of physical ports on the FieldServer.

 

Formal Driver Type

Serial

Passive Client

 

Compatibility Matrix

FieldServer Model Compatible with this driver
FS-x2010 Yes
FS-x2011 Yes
FS-x40 Yes
FS-x30 Yes

 

Connection Information

Connection type: EIA232 or EIA485 (Two wire, Half-Duplex)
Baud Rates: 300; 1200; 2400; 4800; 9600; 19200; 28800; 38400 Baud – Vendor limitation.
Data Bits: 8 – Vendor limitation
Stop Bits: 1 – Vendor limitation
Parity: Even – Vendor limitation
Multidrop Capability No

 

Devices tested

Device Tested (FACTORY, SITE)
GE Mark IV Speedtronic TBC

 

Connection configurations


Communications functions – Supported functions at a glance:

Data Types Supported

FieldServer Data Type Description (or Device Data Type)
Analog Input Integer Points
Digital Input Logic Points
Analog Register Miscellaneous Points
Digital Register Annunciator Alarms

 

Read Operations supported

FieldServer as a PassiveClient
Read All Points and Alarm Statuses

 

Unsupported Functions and Data Types

Function Reason
GE Mark IV Speedtronic Only Rev. 2 12/13/84 of Speedtronic protocol is currently supported

 

Driver Point List

Byte No.

Signal

Description

Zero Pt.

Maximum

Units

Bytes

Miscellaneous Points

1

TIME

SECONDS

0

59

1

2

TIME

MINUTES

0

59

1

3

TIME

HOUR

0

24

1

4

TIME

DAY

0

9

5

TIME

MONTH

0

12

6

TIME

YEAR

0

99

7

TIMR-01

TOTAL FIRED HOURS

0

9999999.9

11

TIMR-02

MANUALLY INIT STARTS

0

9999999.9

15

CNTR-01

PEAK FIRED HOURS

0

9999999.9

19

CNTR-02

TOTAL STARTS

0

9999999.9

23

CNTR-03

FAST LOAD STARTS

0

9999999.9

27

CNTR-04

FIRED STARTS

0

9999999.9

31

CNTR-05

TRIPS

0

9999999.9

 

Byte No.

Signal

Description

Zero Pt.

Maximum

Units

Bytes

Integer Points

35

TTX01-1

EXHAUST TEMPERATURE TC = 1

0

2048

DEG F

2

37

TTX01-2

EXHAUST TEMPERATURE TC = 2

0

2048

DEG F

2

39

TTX01-3

EXHAUST TEMPERATURE TC = 3

0

2048

DEG F

2

41

TTX01-4

EXHAUST TEMPERATURE TC = 4

0

2048

DEG F

2

43

TTX01-5

EXHAUST TEMPERATURE TC = 5

0

2048

DEG F

2

45

TTX01-6

EXHAUST TEMPERATURE TC = 6

0

2048

DEG F

2

47

TTX01-7

EXHAUST TEMPERATURE TC = 7

0

2048

DEG F

2

49

TTX01-8

EXHAUST TEMPERATURE TC = 8

0

2048

DEG F

2

51

TTX01-9

EXHAUST TEMPERATURE TC = 9

0

2048

DEG F

2

53

TTX01-10

EXHAUST TEMPERATURE TC = 10

0

2048

DEG F

2

55

TTX01-11

EXHAUST TEMPERATURE TC = 11

0

2048

DEG F

2

57

TTX01-12

EXHAUST TEMPERATURE TC = 12

0

2048

DEG F

2

59

TTX01-13

EXHAUST TEMPERATURE TC = 13

0

2048

DEG F

2

61

TTX01-14

EXHAUST TEMPERATURE TC = 14

0

2048

DEG F

2

63

TTX01-15

EXHAUST TEMPERATURE TC = 15

0

2048

DEG F

2

65

TTX01-16

EXHAUST TEMPERATURE TC = 16

0

2048

DEG F

2

67

TTX01-17

EXHAUST TEMPERATURE TC = 17

0

2048

DEG F

2

69

TTX01-18

EXHAUST TEMPERATURE TC = 18

0

2048

DEG F

2

71

TTXC

EX TEMP AVG LOW’S – HIGH AND LOW REJECTED

0

2048

DEG F

2

73

CTIF-1

COMP INLET FLANGE TEMP 1

0

2048

DEG F

2

75

CTIF-2

COMP INLET FLANGE TEMP 2

0

2048

DEG F

2

77

CTDA-1

COMP DISCHARGE TEMP 1

0

2048

DEG F

2

79

CTDA-2

COMP DISCHARGE TEMP 2

0

2048

DEG F

2

81

TTWS1FI1

TURB WHEELSPACE TEMP 1ST STG FWD INNER

0

2048

DEG F

2

83

TTWS1FI2

TURB WHEELSPACE TEMP 1ST STG FWD INNER

0

2048

DEG F

2

85

TTWS1FO1

TURB WHEELSPACE TEMP 1ST STG FWD OUTER

0

2048

DEG F

2

87

TTWS1FO2

TURB WHEELSPACE TEMP 1ST STG FWD OUTER

0

2048

DEG F

2

89

TTWS1FA1

TURB WHEELSPACE TEMP 1ST STG AFT OUTER

0

2048

DEG F

2

91

TTWS1FA2

TURB WHEELSPACE TEMP 1ST STG AFT OUTER

0

2048

DEG F

2

93

TTWS2FO1

TURB WHEELSPACE TEMP 2ND STG FWD INNER

0

2048

DEG F

2

95

TTWS2FO2

TURB WHEELSPACE TEMP 2ND STG FWD INNER

0

2048

DEG F

2

97

TTWS2AO1

TURB WHEELSPACE TEMP 2ND STG AFT OUTER

0

2048

DEG F

2

99

TTWS2AO2

TURB WHEELSPACE TEMP 2ND STG AFT OUTER

0

2048

DEG F

2

101

TTWS3FO1

TURB WHEELSPACE TEMP 3RD STG FWD INNER

0

2048

DEG F

2

103

TTWS3FO2

TURB WHEELSPACE TEMP 3RD STG FWD INNER

0

2048

DEG F

2

105

TTWS3AO1

TURB WHEELSPACE TEMP 3RD STG AFT OUTER

0

2048

DEG F

2

107

TTWS3AO2

TURB WHEELSPACE TEMP 3RD STG AFT OUTER

0

2048

DEG F

2

109

TTXSPL

COMBUSTION MONITOR ALLOWABLE SPREAD

0

2048

DEG F

2

111

TTXSP1

COMBUSTION MONITOR ACTUAL SPREAD 1

0

2048

DEG F

2

113

TTXSP2

COMBUSTION MONITOR ACTUAL SPREAD 2

0

2048

DEG F

2

115

LTTH1

LUBE TEMP TURBINE HEADER, GT/GG

0

2048

DEG F

2

117

LTB1D

LUBE TEMP NO. 1 TURB. BRG. DRAIN

0

2048

DEG F

2

119

LTB2D

LUBE TEMP NO. 2 TURB. BRG. DRAIN

0

2048

DEG F

2

121

LTBT1D

LUBE TEMP NO. 1 THRUST BRG. DRAIN

0

2048

DEG F

2

123

BTLG1

BEARING METAL TEMP LEAD GEAR =1

0

2048

DEG F

2

125

BTLG2

BEARING METAL TEMP LEAD GEAR =2

0

2048

DEG F

2

127

BTLG3

BEARING METAL TEMP LEAD GEAR =3

0

2048

DEG F

2

129

BTLG4

BEARING METAL TEMP LEAD GEAR =4

0

2048

DEG F

2

131

BTLG5

BEARING METAL TEMP LEAD GEAR =5

0

2048

DEG F

2

133

BTGJ11

BEARING METAL TEMP GEN. JOURNAL =1

0

2048

DEG F

2

135

BTGJ21

BEARING METAL TEMP GEN. JOURNAL =2

0

2048

DEG F

2

137

BB1

VIBRATION TRANSDUCER = 1

0

8

IN/SEC

2

139

BB2

VIBRATION TRANSDUCER = 2

0

8

IN/SEC

2

141

BB4

VIBRATION TRANSDUCER = 4

0

8

IN/SEC

2

143

BB5

VIBRATION TRANSDUCER = 5

0

8

IN/SEC

2

145

BB7

VIBRATION TRANSDUCER = 7

0

8

IN/SEC

2

147

BB8

VIBRATION TRANSDUCER = 8

0

8

IN/SEC

2

149

BB9

VIBRATION TRANSDUCER = 9

0

8

IN/SEC

2

151

BB-MAX

VIBRATION MAX SELECT

0

8

IN/SEC

2

153

PN

TURBINE STARTING DEVICE SPEED

0

125

% SPEED

2

155

TNH

TURBINE SPEED HP

0

125

% SPEED

2

157

TNR

SPEED CONTROL REFERENCE

0

125

% SPEED

2

159

FSR1

LIQUID FUEL STROKE REF. FROM FUEL SPLITTER

1

100

%

2

161

FSR2

GAS FUEL STROKE REF. FROM FUEL SPLITTER

1

100

%

2

163

CPD

COMPRESSOR DISCHARGE PRESSURE

0

2048

PSI

2

165

FPCI

INTERVALVE PRESSURE

0

2048

PSI

2

167

TTRXB

SPEED BIASED TEMPERATURE CONTROL REF.

0

2048

DEG F

2

169

CSRGV

VIGV REFEENCE ANGLE

0

100

DEGR

2

171

CSGV

INLET GUIDE VANE ANGLE (SCALED)

0

100

DEGR

2

173

FOROUT

LIQUID FUEL FLOW REFERENCE

0

10

V DC

2

175

FO

LIQUID FUEL FLOW

0

64

m/SEC

2

177

FSROUT

GAS CONTROL VALVE POSITION REFERENCE

0

10

V DC

2

179

FSG

GAS CONTROL VALVE LVDT POSITION

0

100

%

2

181

FPRG

GAS RATIO VALVE CONTROL PRESS REF.

0

10

V DC

2

183

FSGR

SPEED RATIO VALVE CALIBR. POS.

0

10

V DC

2

185

DW

GENERATOR LOAD

0.00

204.80

MW

2

187

SVL

SYSTEM LINE VOLTAGE

0

150

V RMS

2

189

SFL

SYSTEM LINE FREQUENCY

0.00

62.50

HZ

2

191

DVAR

GENERATOR LOAD VARS (SCALED)

0.00

204.80

MVAR

2

193

DDUMP1

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

0

32768

CNT1S

2

195

DDUMP2

0

32768

CNT1S

2

197

DDUMP3

0

32768

CNT1S

2

199

DDUMP4

0

32768

CNT1S

2

201

DDUMP5

0

32768

CNT1S

2

203

DDUMP6

0

32768

CNT1S

2

205

DDUMP7

0

32768

CNT1S

2

207

DDUMP8

0

32768

CNT1S

2

207

DDUMP8

0

32768

CNT1S

2

 

Byte No.

Signal

Description

Logic Zero

Logic

One

Bytes

Logic points

211

0

L30D-SD

NORMAL DISPLAY MESSAGE “SHUTDOWN STATUS”

0

1

1/8

1

L30D-SU

NORMAL DISPLAY MESSAGE “STARTUP STATUS”

0

1

1/8

2

L30D-RUN

NORMAL DISPLAY MESSAGE “RUN STATUS”

0

1

1/8

3

L30D-RSZ

NORMAL DISPLAY MESSAGE “NOT READY TO START”

0

1

1/8

4

L30D-RSZ

NORMAL DISPLAY MESSAGE “READY TO START”

0

1

1/8

5

L30D-STG

NORMAL DISPLAY MESSAGE “STARTING”

0

1

1/8

6

L30D-CRN

NORMAL DISPLAY MESSAGE “CRANKING”

0

1

1/8

7

L63SUF 1

STARTUP FSR FIRING FUEL COMMAND

0

1

1/8

212

0

STARTUP FSR WARMUP FUEL COMMAND

0

1

1/8

1

NORMAL DISPLAY MESSAGE “ACCELERATING”

0

1

1/8

2

NORMAL DISPLAY MESSAGE “FULL SPEED NO LOAD”

0

1

1/8

3

NORMAL DISPLAY MESSAGE “SYNCHRONIZING”

0

1

1/8

4

NORMAL DISPLAY MESSAGE “SPINNING RESERVE”

0

1

1/8

5

NORMAL DISPLAY MESSAGE “LOADING”

0

1

1/8

6

NORMAL DISPLAY MESSAGE “FAST LOADING”

0

1

1/8

7

NORMAL DISPLAY MESSAGE “PRESELECTED LOAD”

0

1

1/8

213

0

NORMAL DISPLAY MESSAGE “BASE LOAD”

0

1

1/8

1

NORMAL DISPLAY MESSAGE “PEAK LOAD”

0

1

1/8

2

NORMAL DISPLAY MESSAGE “PART LOAD”

0

1

1/8

3

NORMAL DISPLAY MESSAGE “UNLOADING”

0

1

1/8

4

NORMAL DISPLAY MESSAGE “FIRED SHUTDOWN”

0

1

1/8

5

NORMAL DISPLAY MESSAGE “COASTING DOWN”

0

1

1/8

6

NORMAL DISPLAY MESSAGE “ON COOLDOWN”

0

1

1/8

7

NORMAL DISPLAY MESSAGE “OFF COOLDOWN”

0

1

1/8

214

0

OFF MODE SELECTED

0

1

1/8

1

CRANK MODE SELECTED

0

1

1/8

2

FIRE MODE SELECTED

0

1

1/8

3

AUTO MODE SELECTED

0

1

1/8

4

REMOTE MODE SELECTED

0

1

1/8

5

NORMAL DISPLAY MESSAGE “START SELECT”

0

1

1/8

6

NORMAL DISPLAY MESSAGE “STOP SELECT”

0

1

1/8

7

PRE-SELECTED LOAD COMMAND

0

1

1/8

215

0

BASE LOAD COMMAND

0

1

1/8

1

PEAK LOAD COMMAND

0

1

1/8

2

FSR SHUTDOWN CONTROL

0

1

1/8

3

FSR STARTUP CONTROL

0

1

1/8

4

FSR ACCELERATION CONTROL HP SPEED

0

1

1/8

5

FSR TEMPERATURE CONTROL

0

1

1/8

6

FSR SPEED DROOP CONTROL

0

1

1/8

7

FSR SPEED ISOCH CONTROL

0

1

1/8

216

0

MIN FSR LOGIC

0

1

1/8

1

FSR MANUAL CONTROL

0

1

1/8

2

SEQUENCE IN PROGRESS

0

1

1/8

3

10V CONTROL MESSAGE – MAXIMUM ANGLE

0

1

1/8

4

10V CONTROL MESSAGE – TEMPERATURE CONTROL

0

1

1/8

5

10V CONTROL MESSAGE – MANUAL CONTROL

0

1

1/8

6

NORMAL DISPLAY MESSAGE “VOLTAGE MATCHING”

0

1

1/8

7

AUXILIARY TO FAST LOAD START SIGNAL

0

1

1/8

217

0

WATER WASH SELECTED

0

1

1/8

1

FUEL LINE PURGE IN PROGRESS

0

1

1/8

2

MASTER PROTECTIVE SIGNAL

0

1

1/8

3

NORMAL SHUTDOWN

0

1

1/8

4

TURBINE COMPLETE SEQUENCE

0

1

1/8

5

HP ZERO SPEED SIGNAL

0

1

1/8

6

MINIMUM SPEED SIGNAL (APPR 20%)

0

1

1/8

7

ACCELERATING FUEL SPEED SIGNAL (APPR 40%)

0

1

1/8

218

0

HP OPERATING SPEED SIGNAL

0

1

1/8

1

FLAME DETECTED CHANNEL =1

0

1

1/8

2

FLAME DETECTED CHANNEL =2

0

1

1/8

3

FLAME DETECTED CHANNEL =3

0

1

1/8

4

FLAME DETECTED CHANNEL =4

0

1

1/8

5

GENERATOR BREAKER CLOSURE

0

1

1/8

6

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

0

1

1/8

7

0

1

1/8

219

0

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

0

1

1/8

1

0

1

1/8

2

0

1

1/8

3

0

1

1/8

4

0

1

1/8

5

0

1

1/8

6

0

1

1/8

7

0

1

1/8

220

0

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

0

1

1/8

1

0

1

1/8

2

0

1

1/8

3

0

1

1/8

4

0

1

1/8

5

0

1

1/8

6

0

1

1/8

7

0

1

1/8

221

0

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

0

1

1/8

1

0

1

1/8

2

0

1

1/8

3

0

1

1/8

4

0

1

1/8

5

0

1

1/8

6

0

1

1/8

7

0

1

1/8

 

Byte No.

Description

LogicZero

LogicOne

Bytes

Annunciator Alarms

222

ALARM 0-7

0

FF

1

223

ALARM 8-15

0

FF

1

224

ALARM 16-23

0

FF

1

225

ALARM 24-31

0

FF

1

226

ALARM 32-39

0

FF

1

227

ALARM 40-47

0

FF

1

228

ALARM 48-55

0

FF

1

229

ALARM 56-63

0

FF

1

230

ALARM 64-71

0

FF

1

231

ALARM 72-79

0

FF

1

232

ALARM 80-87

0

FF

1

233

ALARM 88-95

0

FF

1

234

ALARM 96-103

0

FF

1

235

ALARM 104-111

0

FF

1

236

ALARM 112-119

0

FF

1

237

ALARM 120-127

0

FF

1

238

ALARM 128-135

0

FF

1

239

ALARM 136-143

0

FF

1

240

ALARM 144-151

0

FF

1

241

ALARM 152-159

0

FF

1

242

ALARM 160-167

0

FF

1

243

ALARM 168-175

0

FF

1

244

ALARM 176-183

0

FF

1

245

ALARM 184-191

0

FF

1

246

ALARM 192-199

0

FF

1

247

ALARM 200-207

0

FF

1

248

ALARM 208-215

0

FF

1

249

ALARM 216-223

0

FF

1

250

ALARM 224-231

0

FF

1

251

ALARM 232-239

0

FF

1

252

ALARM 240-247

0

FF

1

253

ALARM 248-255

0

FF

1

 


THIS PAGE INTENTIONALLY LEFT BLANK