FieldServer VADD Driver
FS-8705-09
Rapid Engineering ICSI or ICSII Controller Protocol
Description
This driver is used to exchange data between a FieldServer and an ICSI or ICSII HVAC controller device manufactured by Rapid Engineering.
The driver is a serial driver using a RS-485 serial port to connect between the FieldServer and the ICSII capable device.
The driver provides client functionality.
As a client the driver can poll for data from the ICSI or ICSII device as well as being able to some control points and set points. Details are provided below.
Server functionality is built into the driver but is not documented or supported. This functionality is implemented to support our ongoing QC efforts.
The driver is fully compatible with other FieldServer drivers and meets FieldServer’s quality assurance standards. The driver was developed by Chipkin Automation Systems, an Approved FieldServer Integrator.
| Fieldserver Mode | Nodes | Comments |
| Client | 99 | Up to 99 ICSI or ICSII devices can be linked on one RS485 network. The functional specification of the EIA485 standard limits the number of nodes per segment to 32. If additional network segments are required then repeaters are required.
The network must consist exclusively of ICSI or ICSII devices. For mixed configurations call for more info. |
Formal Driver Type
Serial
Client
Compatibility Matrix
| FieldServer Model | Compatible with this driver |
| FS-x2010 | Yes, |
| FS-x2011 | Yes, |
| FS-x30 | Yes, |
| FS-X40 | Yes, |
Connection Information
| Connection type: | RS-485 |
| Baud Rates: | Driver Supports : 110; 300; 600; 1200; 2400; 4800; 9600; 19200; 28800; 38400; 57600; 115200 Baud
Vendor Equipment support 9600 Baud |
| Data Bits: | Driver Supports : 7,8 |
| Stop Bits: | Driver Supports : 1,2 |
| Parity: | Driver Supports : Odd, Even, None |
| Hardware interface: | N/A |
| Multidrop Capability | Yes |
Devices tested
| Device | Tested (FACTORY, SITE) |
| Call Chipkin Automation Systems for an update on this information. | This driver has been tested at Sequoia Engineering (an approved FieldServer Integrator) using an ICSII controller during July 2004. It was subsequently tested in Beta form by a customer connected to a network of ICSII controllers during August 2004. Since then the driver has been successfully installed at a number of sites. |
Connection configurations
Connection Notes
Communications functions – Supported functions at a glance:
Read / Write Operations supported
| Cmd # | FieldServer as a Client |
| 1 | Heater Status Report (Read command) |
| 2 | Setpoints Report (Read command) |
| 3 | Occupied Schedule for Air handler (Read Command) |
| 4 | Aux. Output Schedule Report. (Read Command) |
| 5 | Setpoint Range Report (Read Command) |
| 6 | Error and Reset (Read / Write command) |
| 7 | Last Power UP and Energy Info Report (Read Command) |
| 8 | Change Mode ( Write Command) |
| 9 | Change Setpoint (Write Command) |
| 10 | Change Schedule for Air handler (Write command) |
| 20 | Change Schedule for Aux Output (Write command) |
| 11 | Zero Energy Counters ( Write Command) |
| 13 | Aux Output control definition / setpoint (Write command0 |
| 12 | Version Info & Config ( Read Command) |
| Uni#1 | Universal Command to Change Date, time (Write Command) |
Unsupported Functions and Data Types
| Cmd # | Description |
Data Points
The FieldServer reads data from the ICSII device. The data points below are the points available to the FieldServer but this does not necessarily mean that they are valid for the HVAC device connected to the ICSII.
|
Description |
Category |
R/W |
|
day of week |
Heater Status Info |
R |
|
date (MMDDYY) |
Heater Status Info |
R |
|
(HHMM) |
Heater Status Info |
R |
|
mode |
Heater Status Info |
R |
|
current state |
Heater Status Info |
R |
|
current space temp setpoint |
Heater Status Info |
R |
|
space temp times 10 |
Heater Status Info |
R |
|
discharge temp |
Heater Status Info |
R |
|
outside air temp |
Heater Status Info |
R |
|
pressure setpoint times 1000 |
Heater Status Info |
R |
|
pressure times 1000 |
Heater Status Info |
R |
|
outside air damper |
Heater Status Info |
R |
|
return air damper |
Heater Status Info |
R |
|
inputs (hex) |
Heater Status Info |
R |
|
outputs (hex) |
Heater Status Info |
R |
|
current error |
Heater Status Info |
R |
|
space relative humidity |
Heater Status Info |
R |
|
valve position |
Heater Status Info |
R |
|
future |
Heater Status Info |
R |
|
future |
Heater Status Info |
R |
|
occupied temperature |
Setpoints Info |
RW |
|
unoccupied temperature |
Setpoints Info |
RW |
|
maximum discharge temperature |
Setpoints Info |
RW |
|
minimum discharge temperature |
Setpoints Info |
RW |
|
building pressure times 100 |
Setpoints Info |
RW |
|
occupied burner turnoff times |
Setpoints Info |
RW |
|
unoccupied heater turnoff times |
Setpoints Info |
RW |
|
occupied open relief times |
Setpoints Info |
RW |
|
unoccupied open relief times |
Setpoints Info |
RW |
|
low temperature shutdown |
Setpoints Info |
RW |
|
percent outside air |
Setpoints Info |
RW |
|
burner turnoff setpoint enable/disable(1=Enable) |
Setpoints Info |
RW |
|
outside air temp. control enable/disable(1=Enable) |
Setpoints Info |
RW |
|
room relative humidity setpoint |
Setpoints Info |
RW |
|
dry-bulb enonomizer setpoint |
Setpoints Info |
RW |
|
econ type (0,1,2) none, dry-bulb, enthalpy |
Setpoints Info |
RW |
|
future |
Setpoints Info |
RW |
|
future |
Setpoints Info |
RW |
|
period(1,5,9,13,17 ), start (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(1,5,9,13,17 ), stop (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(2,6,10,14,18), start (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(2,6,10,14,18), stop (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(3,7,11,15,19), start (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(3,7,11,15,19), stop (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(4,8,12,16,20), start (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(4,8,12,16,20), stop (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(na,na,na,na,21), start (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(na,na,na,na,21), stop (XXXXX = DHHMM) |
Occupied Schedule for Air Handler |
RW |
|
period(1,5,9,13,17 ), start (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(1,5,9,13,17 ), stop (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(2,6,10,14,18), start (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(2,6,10,14,18), stop (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(3,7,11,15,19), start (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(3,7,11,15,19), stop (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(4,8,12,16,20), start (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(4,8,12,16,20), stop (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(na,na,na,na,21), start (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
period(na,na,na,na,21), stop (XXXXX = DHHMM) |
Aux Output Schedule |
RW |
|
occupied temperature, minimum maximum |
Setpoint Ranges |
R |
|
unoccupied temperature, minimum maximum |
Setpoint Ranges |
R |
|
maximum discharge temperature, minimum maximum |
Setpoint Ranges |
R |
|
minimum discharge temperature, minimum maximum |
Setpoint Ranges |
R |
|
building pressure, minimum maximum |
Setpoint Ranges |
R |
|
occupied burner turnoff, minimum maximum |
Setpoint Ranges |
R |
|
unoccupied heater turnoff, minimum maximum |
Setpoint Ranges |
R |
|
occupied open relief, minimum maximum |
Setpoint Ranges |
R |
|
unoccupied open relief, minimum maximum |
Setpoint Ranges |
R |
|
low temperature shutdown, minimum maximum |
Setpoint Ranges |
R |
|
percent outside air, minimum maximum |
Setpoint Ranges |
R |
|
error log no. 1, error no., MMDDYY, HHMM |
Error Info |
R |
|
error log no. 2, error no., MMDDYY, HHMM |
Error Info |
R |
|
error log no. 3, error no., MMDDYY, HHMM |
Error Info |
R |
|
error log no. 4, error no., MMDDYY, HHMM |
Error Info |
R |
|
last power up date (MMDDYY) |
Last Power UP and Energy Info |
R |
|
last power up time (HHMM) |
Last Power UP and Energy Info |
R |
|
number of power ups |
Last Power UP and Energy Info |
R |
|
number of fan starts |
Last Power UP and Energy Info |
R |
|
cumulative fan hours on, thousands |
Last Power UP and Energy Info |
R |
|
cumulative fan hours on, 0-999 |
Last Power UP and Energy Info |
R |
|
CCF – thousands |
Last Power UP and Energy Info |
R |
|
CCF – 0-999 |
Last Power UP and Energy Info |
R |
|
CCFH – low rate * 100 (CCF) |
Last Power UP and Energy Info |
R |
|
CCFH – min rate * 100 (CCF) |
Last Power UP and Energy Info |
R |
|
CCFH – max rate * 100 <- NOTE: *100 (CCF) |
Last Power UP and Energy Info |
R |
|
CCFH – high rate * 100 <- NOTE: *100 (CCF) |
Last Power UP and Energy Info |
R |
|
CCFH – current rate (same as 9-12 ??) |
Last Power UP and Energy Info |
R |
|
Reset Fan Energy Counter |
Reset Energy Counters |
W |
|
Reset Gas Energy counter |
Reset Energy Counters |
W |
|
Control Type |
Aux output control Settings |
W |
|
Sub Type |
Aux output control Settings |
W |
|
Level |
Aux output control Settings |
W |
Support
Please contact Chipkin Automation Systems directly for driver support.
Revision History
| Date | Resp | Format | Driver Ver. | Doc.
Rev. |
Comment |
| 12May2004 | PMC | 0.00 | 0 | Initial Draft issued for customer review. | |
| 19Jun2004 | PMC | 1.00a | 1 | 1st Release. Minor changes to DFS. Only change of note was to remove function 12 from the ‘unsupported function’ list. | |
| 19Aug2004 | PMC | 1.00a | 2 | Added connection information.
Added part number Spelling corrections Notes on testing. |
|
| 20Aug2004 | PMC | 1.00a | 3 | Add Reference to Rapid Engineering | |
| 20Oct2004 | PMC | 1.00a | 4 | References to ICSi’s added | |
| 17Dec2004 | PMC | 1.00d | 0 | Time and Date write command is now supported. | |
| 14Jan2004 | PMC | 1.00e | 0 | Minor changes and banner change. | |