FS-8700-97 – Lutron eLumen Zone/Area Machine

FieldServer Driver – Serial
FS-8700-97
Lutron eLumen Zone/Area Machine

Driver Description

The Lutron eLumen Machine Zone/Area Machine driver, hereafter simply referred to as the Lutron Machine driver, provides a BACnet IP interface to a Lutron eLumen panel. The driver can be configured to represent either zones or areas as used in the Lutron eLumen panel. The FieldServer acts as both client and server to provide BACnet objects to an external BACnet client. In server mode, the FieldServer collects data from the eLumen panel and holds the data ready for reads from an external BACnet client. In client mode, the FieldServer executes pre-defined commands on the eLumen.

FieldServer Model Nodes Comments
Client 1 Only one Lutron Machine driver client node may be connected to a Lutron eLumen panel.
Server 1 One BACnet IP node provides an upstream interface to the Lutron eLumen panel.

 

Formal Driver Type

Serial
Client only.

 

Compatibility Matrix

FieldServer Model Compatible with this driver
FS-B2010 Yes
FS-B2011 (LonWorks) Yes
FS-B40 Series Yes

 

Connection Information

Connection type: RS-232, RS-485
Baud Rates: 9600
Data Bits: 8
Stop Bits: 1
Parity: None
Multidrop Capability: No

 

Devices tested:

Device Tested (FACTORY, SITE)
Lutron Grafik 6000 Site

 

Connection configurations


 

Communications functions – Supported functions at a glance:

Data Types Supported

FieldServer Data Type Description (or Device Data Type)
Analog Input Zone Intensity, Last Scene number
Binary Input Relay status, Scene on status
Analog Output Desired Intensity, Desired Scene, Scripts
Binary Output Scripts
Multistate Output Scripts
Analog Value System variables
Binary Value System variables

 

Read and Write operations supported

FieldServer as a Client FieldServer as a Server
Read Analog Input Status: Provide Analog Input Status:
Get Zone Intensity, Get Area Status Get Zone Intensity, Get Area Status
Read Binary Input Status: Provide Binary Input Status:
Get Zone Intensity, Get Area Status Get Zone Intensity, Get Area Status
Read Analog Value Status: Provide Analog Value Status:
Get System Variable Value Get System Variable Value
Read Binary Value Status: Provide Binary Value Status:
Get System Variable Value Get System Variable Value
Write Analog Setpoints: Accept Analog Setpoints:
Select Scene in Area, Run Script Select Scene in Area, Run Script
Write Binary Commands: Accept Binary Commands:
Run Script Run Script

 

Unsupported Functions and Data Types

Function Reason
Programming messages FieldServer is a data transfer device, and as such, programming messages are not required
If you liked this post;
  • Please consider subscribing to our RSS feed