FieldServer Driver – Serial
FS-8700-70
WS3000 TABS
Description
The WS3000 TABS driver is set up for (AS&C) Alarm Surveillance and Control applications. The TABS protocol works over a multidrop RS-422 line or over a RS-232 line and allows only one master and up to 32 slaves on a serial channel. Slaves are assigned station addresses that range from 0 to 31. The master does not have a station address. The protocol is strictly command/response with the master polling the slave devices. Each slave can be configured to hold the data for one to 256 displays. Each display contains 64 alarms status points represented by bits.
Formal Driver Type
Serial
Client or Server
Connection Information
| Connection type: | RS-232 or RS-485 (Two wire, Half-Duplex) |
| Baud Rates: | 1200; 2400; 4800; 9600 Baud |
| Data Bits: | 8 |
| Stop Bits: | 1 |
| Parity: | Odd, Even, None |
Devices tested:
| Device | Tested (SITE, FACTORY) |
| WS3000 Super Scanner | FACTORY |
Connection configurations
Communications functions – Supported functions at a glance:
Data Types Supported
| FieldServer Data Type | Description (or Device Data Type) |
| Digital Inputs | Display alarm points |
Read Operations supported
| FieldServer as a Client | FieldServer as a Server |
| Read Binary Status: | Provide Binary Status: |
| Get AS&C Configuration | Uses Configuration info |
| Scan All Displays | Point statuses |
| Scan Changed Displays | Changed point statuses |
Write (control) Operations supported
| FieldServer as a Client | FieldServer as a Server |
| Write Binary Commands: | Accept Binary Commands: |
| AS&C Remote Control Type 0 | AS&C Remote Control Type 0 |
| AS&C Remote Control Type 1 | AS&C Remote Control Type 1 |
| AS&C Remote Control Type 2 | AS&C Remote Control Type 2 |
| AS&C Remote Control Types 128 to 255 | AS&C Remote Control Types 128 to 255 |
Functions Described
The following limitations exist:
1) Long addressing mode is not supported limiting the number of displays to 256 per node.
Unsupported Devices or Protocol Options
| Device | Description |
| WS3000 | TBOS Protocol |
| WS3000 | Teltrac Protocol |
THIS PAGE INTENTIONALLY LEFT BLANK