FS-8700-23 – CB Link

FieldServer Driver – Serial
FS-8700-23
CB Link

 

Driver Description

The CB-Link driver allows the FieldServer to transfer data to and from devices over RS-485 using CB-Link protocol. Refer to “Model 833-2771 CB-Link” Manual #65-0216 and “Model 833-2757 General Purpose Interface ControlBus Module” Manual #65-0220 from Cleaver Brooks.

 

Formal Driver Type

Serial
Server Only

 

Connection Information

Connection type: RS-485
Baud Rates: 9600
Parity: None

 

Devices tested:

Device Tested (FACTORY, SITE)
Cleaver Brooks Hawk, EC78XX Honeywell Link Site

The FieldServer can accept any information transmitted by the CB Hawk, including:

  • Program, operate, auto, man, rem modes
  • Flame failure
  • Gas pressure Sensor high/low
  • Fuel selection
  • Atomizing air off
  • Steam pressure, water temperature, oil pressure sensor information
  • Lockout and pre-ignition interlock
  • AC line frequency
  • Excess AC line noise
  • Damper motor
  • Replace battery
  • Fuel selection, recycle limits, oil pressure, oil temperature, lockout/interlock, open oil drawer hold
  • Standby, prepurge, pilot ignition, fuel change, main ignition, run, post purge, safety shutdown
  • Low fire cutoff, flame detected, test switch, damper motor holds
  • Call CB service.

 

Connection configurations

NETWORK INTERFACE UNIT
MAKE MODEL NAME
Honeywell Q7700 Network Interface Unit
Cleaver Brooks 833-2771 CB-Link

 

CONTROL MODULES
MAKE MODEL No. OF MODULE MODULE NAME PROPERTY FILE NAME (.BP1;.BP2) CONFIGURATION FILE NAME (.CSV) NOTES
Honeywell QS7700A BCS7700 N/A N/A N/A
Honeywell QS7800A 7800 SERIES Control N/A N/A N/A
Honeywell QS7800C QM40XX Data Acquisition Module ON REQUEST QM40XX Data Acquisition Modules
Armstrong QS7800D Trapscan System ON REQUEST ON REQUEST
Honeywell QS7800E PulsaFeeder PULSAtrol PULSA PULSA
Honeywell QS7800A S7830 Expanded Annunciator S7830 S7830 Expanded Annunciator
Honeywell QS7800A S7800 Keyboard/Display Module S7800 S7800
Honeywell QS7800A ST7800 Relay Module ST7800 Requires S7800 module
Honeywell RM7800E,G,L,M Relay Modules RM78XX RM78XX
Honeywell RM7840E,G,L,M Relay Modules RM78XX RM78XX
Honeywell N/A, this is the chassis that the above modules plug into Q7700A,B
CB-Link 833-2727 Display Module N/A N/A
CB-Link 833-2729 Data Control Bus Module N/A N/A
CB-Link 833-2734 CB 783 ON REQUEST ON REQUEST Requires 833-2727 or 833-2729 on module
CB-Link 833-2734 CB 780 ON REQUEST ON REQUEST Requires 833-2727 or 833-2729 on module
CB-Link 833-2734 CB 784 ON REQUEST ON REQUEST Requires 833-2727 or 833-2729 on module
CB-Link 833-2425 CB-Hawk Hawk Hawk Requires 833-2727 or 833-2729 on module

Note: SYSNet is the generic name for networks of the above modules. Controlbus is the generic name for the networks in a NIM/CBLink configuration.