FS-8700-20 – Profibus DP

FieldServer Driver – Fieldbus

FS-8700-20

Profibus DP

 

Description

The Profibus DP driver allows the FieldServer to transfer data to and from devices using Profibus DP protocol with the use of a communications adapter card installed in the FieldServer. The FieldServer can function as either a DP Master or a DP Slave on the Profibus network.

As a slave, the Profibus DP driver allows the FieldServer to be a single DP slave station to another DP master.  This slave is capable of transferring 244 bytes of input and 244 bytes of output data to the other master.  If it is necessary to transfer more data to a Profibus master, then the Profibus DPMS driver will be necessary.  When used as a DP master, the adapter card provides a total of 16Kbytes of input and 16Kbytes of output data to be transferred with DP slaves.

 

Fieldserver Mode Nodes Comments
DP Master 126 The DP Master can communicate with up to 126 DP Slaves.
DP Slave 1 The DP Slave can represent one slave node on the network.

 

Formal Driver Type

Fieldbus

Client

 

Compatibility Matrix

FieldServer Model Compatible with this driver
FS-x2010 No
FS-x2011 No
FS-x40 Yes

 

Connection Information

Connection type: Profibus
Baud Rates: 9600, 19200, 93.75K, 187.5K, 500K, 750K, 1.5M, 3M, 6M, 12M
Hardware interface: SST 5136-PFB-ISA

 

Devices tested

Device Tested (FACTORY, SITE)
SST 5136-PFB-ISA ( DP Slave ) FieldServer Technologies
SST 5136-PBMS ( Multiple DP Slaves ) FieldServer Technologies

 

Connection configurations

 

Connection Notes

Please note that actual baud rates achievable on the Profibus network depend on the type and quality of network cable used as well as to the correct termination of the network. Please refer to Profibus network wiring requirements and to other device manufacturer’s documentation if necessary.

 

 

Communications functions – Supported functions at a glance:

Data Types Supported

FieldServer Data Type Description (or Device Data Type)
2-byte Integer ( Signed and Unsigned ) Buffer arranged as words
8-bit Byte Buffer arranged as bytes
4-byte Float Buffer arranged as double-words
Bit Buffer arranged as bytes

 

Data Operations supported

FieldServer as a DP Master
Accept Input Buffer Data from a DP Slave
Provide Output Buffer Data to a DP Slave

 

FieldServer as a DP Slave
Accept Output Buffer Data from a DP Master
Provide Input Buffer Data to a DP Master

 

Unsupported Functions and Data Types

Function Reason
Programming messages The FieldServer is a data transfer device, and as such, programming messages are not required


 