FS-8700-125 – Stulz

FieldServer Driver

FS-8700-125

Stulz

 

Description

The Stulz driver allows the transfer of data from a Stulz device using the Stulz monitoring protocol version 1.7.  The Fieldserver can act as a Client.

Currently, only the C6000 microcontroller is supported as the protocol only specifies read capabilities on that unit.

The Client is configurable to read all information into separate data points and supports writing to selected points as specified below.

It supports the following formats:

  • Float values
  • Binary values
  • Integer values

 

Fieldserver Mode Remote Nodes Comments
Client 32 The protocol supports only one Client per bus, which can poll 32 server devices

 

Formal Driver Type

Serial

Client Only

 

Compatibility Matrix

FieldServer Model Compatible with this driver
FS-x2010 Yes
FS-x2011 Yes
FS-x40 Yes
FS-x30 Yes

 

Connection Information

Connection type: RS-485 (Two wire, Half-Duplex)
Baud Rates: 9600 – Vendor Limitation
Data Bits: 8
Stop Bits: 1
Parity: None
Multidrop Capability Yes

 

Devices tested

Device Tested (FACTORY, SITE)
C6000 FACTORY

 

Connection configurations

 

Connection Notes

Use terminating resistors to enhance communication quality.


Communications functions – Supported functions at a glance:

Read Operations supported

FieldServer as a Client
Read Analog Status:
  • Temperatures
  • Humidity
  • Set points
  • GE/CW valve outputs
  • Humidifier outputs
  • Date/time
  • Module 1-6 data
  • Alarm set points
Read Binary Status:
  • Module 1-6 statuses
  • Compressor statuses
  • General statuses
  • Error states

 

Write (Control) Operations supported

FieldServer as a Client
Write Analog Setpoints:
  • Set points
  • Alarm set points
  • Module 1-6 set points
  • Date/time
Write Binary Commands:
  • Reset alarms
  • Stop/start
  • G/CW mode

 

Unsupported Functions and Data Types

Function Reason
Programming messages FieldServer is a data transfer device, and as such, programming messages are not required

 

Unsupported Devices or Protocol Options

Device Details
C1001/2 The protocol does not specify any reading functions for this device
C1010 The protocol does not specify any reading functions for this device
C4000 The protocol does not specify any reading functions for this device
C5000 The protocol does not specify any reading functions for this device

 

Complete command table

FieldServer as a Client
Command descriptions and supported status
Command Description

Data_type

Signed

Range

Units

C6000

Active commands

ls Long state request

Byte

N

r

m1fss

Module 1 fan speed setpoint

Integer

N

0..100

%

r/w

m2fss

Module 2 fan speed setpoint

Integer

N

0..100

%

r/w

m3fss

Module 3 fan speed setpoint

Integer

N

0..100

%

r/w

m4fss

Module 4 fan speed setpoint

Integer

N

0..100

%

r/w

m5fss

Module 5 fan speed setpoint

Integer

N

0..100

%

r/w

m6fss

Module 6 fan speed setpoint

Integer

N

0..100

%

r/w

m1dcsst

Module 1 drycooler summer start

Integer

N

0..50

C

r/w

m1dcwst

Module 1 drycooler winter start

Integer

N

0..30

C

r/w

m2dcsst

Module 2 drycooler summer start

Integer

N

0..50

C

r/w

m2dcwst

Module 2 drycooler winter start

Integer

N

0..30

C

r/w

m3dcsst

Module 3 drycooler summer start

Integer

N

0..50

C

r/w

m3dcwst

Module 3 drycooler winter start

Integer

N

0..30

C

r/w

m4dcsst

Module 4 drycooler summer start

Integer

N

0..50

C

r/w

m4dcwst

Module 4 drycooler winter start

Integer

N

0..30

C

r/w

m5dcsst

Module 5 drycooler summer start

Integer

N

0..50

C

r/w

m5dcwst

Module 5 drycooler winter start

Integer

N

0..30

C

r/w

m6dcsst

Module 6 drycooler summer start

Integer

N

0..50

C

r/w

m6dcwst

Module 6 drycooler winter start

Integer

N

0..30

C

r/w

Passive_Client commands

wt Water temperature

Float

Y

-50..50

C

r

rat Return air temperature

Float

N

0..100

C

r

sat Supply air temperature

Float

N

0..100

C

r

rah Return air humidity

Float

N

0..100

%

r

sah Supply air humidity

Float

N

0..100

%

r

oat Outside air temperature

Float

Y

-50..50

C

r

oah Outside air humidity

Float

N

0..100

%

r

tss Temperature set point shift

Float

Y

-12.7..12.7

C

r

hss Humidity set point shift

Float

Y

-12.7..12.7

%

r

swv Software version

r

m1o1 Module 1 digital out status byte 1

Packed_Bit

r

0

Reheat 1

Bit

r

1

Compressor 1

Bit

r

2

Humidification 1

Bit

r

3

Dehumidification 1

Bit

r

4

Fan 1

Bit

r

5

Dry cooler

Bit

r

6

Alarm relays 1 (1= no alarm)

Bit

r

7

PWW

Bit

r

m1o2 Module 1 digital out status byte 2

Packed_Bit

r

0

Reheat 2

Bit

r

1

Glycol pump

Bit

r

2

Louver (0=closed, 1=open)

Bit

r

3

Alarm relays 2 (1= no alarm)

Bit

r

4

Alarm relays 3 (1= no alarm)

Bit

r

5

Alarm relays 4 (1= no alarm)

Bit

r

6

Alarm relays 5 (1= no alarm)

Bit

r

7

Glycol pump 1/2 select

Bit

r

m2o1[1] Module 2 digital out status byte 1

Packed_Bit

r

m2o2[2] Module 2 digital out status byte 2

Packed_Bit

r

m3o1Error! Bookmark not defined. Module 3 digital out status byte 1

Packed_Bit

r

m3o2Error! Bookmark not defined. Module 3 digital out status byte 2

Packed_Bit

r

m4o1Error! Bookmark not defined. Module 4 digital out status byte 1

Packed_Bit

r

m4o2Error! Bookmark not defined. Module 4 digital out status byte 2

Packed_Bit

r

m5o1Error! Bookmark not defined. Module 5 digital out status byte 1

Packed_Bit

r

m5o2Error! Bookmark not defined. Module 5 digital out status byte 2

Packed_Bit

r

m6o1Error! Bookmark not defined. Module 6 digital out status byte 1

Packed_Bit

r

m6o2Error! Bookmark not defined. Module 6 digital out status byte 2

Packed_Bit

r

m1i1 Module 1 digital in status byte 1

Packed_Bit

r

0

Compressor low pressure

Bit

r

1

Compressor high pressure

Bit

r

2

Reheat 1 failure

Bit

r

3

Humidification failure

Bit

r

4

Air flow failure

Bit

r

5

Filter clogged

Bit

r

6

Aux alarm 1

Bit

r

7

Reheat 2 alarm

Bit

r

m1i2 Module 1 digital in status byte 2

Packed_Bit

r

0

Conductivity too high

Bit

r

1

Ultrasonic failure

Bit

r

2

Glycol pump 1 failure

Bit

r

3

Glycol pump 2 failure

Bit

r

4

Drycooler failure

Bit

r

5

Water detector

Bit

r

6

Aux alarm 2

Bit

r

7

Aux alarm 3

Bit

r

m2i1[3] Module 2 digital in status byte 1

Packed_Bit

r

m2i2[4] Module 2 digital in status byte 2

Packed_Bit

r

m3i1Error! Bookmark not defined. Module 3 digital in status byte 1

Packed_Bit

r

m3i2Error! Bookmark not defined. Module 3 digital in status byte 2

Packed_Bit

r

m4i1Error! Bookmark not defined. Module 4 digital in status byte 1

Packed_Bit

r

m4i2Error! Bookmark not defined. Module 4 digital in status byte 2

Packed_Bit

r

m5i1Error! Bookmark not defined. Module 5 digital in status byte 1

Packed_Bit

r

m5i2Error! Bookmark not defined. Module 5 digital in status byte 2

Packed_Bit

r

m6i1Error! Bookmark not defined. Module 6 digital in status byte 1

Packed_Bit

r

m6i2Error! Bookmark not defined. Module 6 digital in status byte 2

Packed_Bit

r

m1gecw Module 1 analogue out GE/CW

Float

N

0..100

r

m2gecw Module 2 analogue out GE/CW

Float

N

0..100

r

m3gecw Module 3 analogue out GE/CW

Float

N

0..100

r

m4gecw Module 4 analogue out GE/CW

Float

N

0..100

r

m5gecw Module 5 analogue out GE/CW

Float

N

0..100

r

m6gecw Module 6 analogue out GE/CW

Float

N

0..100

r

m1pww Module 1 analogue out PWW

Float

N

0..100

r

m2pww Module 2 analogue out PWW

Float

N

0..100

r

m3pww Module 3 analogue out PWW

Float

N

0..100

r

m4pww Module 4 analogue out PWW

Float

N

0..100

r

m5pww Module 5 analogue out PWW

Float

N

0..100

r

m6pww Module 6 analogue out PWW

Float

N

0..100

r

m1aoh Module 1 analogue out humidifier

Float

N

0..100

r

m2aoh Module 2 analogue out humidifier

Float

N

0..100

r

m3aoh Module 3 analogue out humidifier

Float

N

0..100

r

m4aoh Module 4 analogue out humidifier

Float

N

0..100

r

m5aoh Module 5 analogue out humidifier

Float

N

0..100

r

m6aoh Module 6 analogue out humidifier

Float

N

0..100

r

m1aosv Module 1 analogue out suction valve

Float

N

0..100

r

m2aosv Module 2 analogue out suction valve

Float

N

0..100

r

m3aosv Module 3 analogue out suction valve

Float

N

0..100

r

m4aosv Module 4 analogue out suction valve

Float

N

0..100

r

m5aosv Module 5 analogue out suction valve

Float

N

0..100

r

m6aosv Module 6 analogue out suction valve

Float

N

0..100

r

m16doc2 Module 1-6 digital out compressor 2

Packed_Bit

r

0

Module 1 compressor 2

Bit

r

1

Module 2 compressor 2

Bit

r

2

Module 3 compressor 2

Bit

r

3

Module 4 compressor 2

Bit

r

4

Module 5 compressor 2

Bit

r

5

Module 6 compressor 2

Bit

r

6

Not used

Bit

r

7

Not used

Bit

r

m14dic2 Module 1-4 digital in compressor 2

Packed_Bit

r

0

modul 1 compressor 2 low pressure

Bit

r

1

modul 1 compressor 2 high pressure

Bit

r

2

modul 2 compressor 2 low pressure

Bit

r

3

modul 2 compressor 2 high pressure

Bit

r

4

modul 3 compressor 2 low pressure

Bit

r

5

modul 3 compressor 2 high pressure

Bit

r

6

modul 4 compressor 2 low pressure

Bit

r

7

modul 4 compressor 2 high pressure

Bit

r

m56dic2 Module 5-6 digital in compressor 2

Packed_Bit

r

0

modul 5 compressor 2 low pressure

Bit

r

1

modul 5 compressor 2 high pressure

Bit

r

2

modul 6 compressor 2 low pressure

Bit

r

3

modul 6 compressor 2 high pressure

Bit

r

4

not used

Bit

r

5

not used

Bit

r

6

not used

Bit

r

7

not used

Bit

r

sett Setpoint temperature

Float

N

10..35

C

r/w

seth Setpoint humidity

Integer

N

10..90

%

r/w

year Date – Year

Integer

N

0..99

r/w

month Date – Month

Integer

N

1..12

r/w

day Date – Day

Integer

N

1..31

r/w

hour Time – Hour

Integer

N

0..23

r/w

minute Time – Minute

Integer

N

0..59

r/w

ratha Return air temperature too high alarm

Integer

N

0..30

C

r/w

satha Supply air temperature too high alarm

Integer

N

0..30

C

r/w

ratla Return air temperature too low alarm

Integer

N

0..30

C

r/w

satla Supply air temperature too low alarm

Integer

N

0..30

C

r/w

wtha Water temperature too high alarm

Integer

N

0..50

C

r/w

wtla Water temperature too low alarm

Integer

Y

-50..30

C

r/w

rahha Return air humidity too high alarm

Integer

N

0..90

%

r/w

sahha Supply air humidity too high alarm

Integer

N

0..90

%

r/w

rahla Return air humidity too low alarm

Integer

N

0..90

%

r/w

sahla Supply air humidity too low alarm

Integer

N

0..90

%

r/w

Module 1

1comps Compressor start

Float

N

0..10

r/w

1comph Compressor hysteresis

Float

N

0..10

r/w

1svst Suction valve start

Float

N

0..10

r/w

1svpb Suction valve proportional ban

Float

N

0..10

r/w

1drycst Drycooler start temperature

Integer

N

0..45

r

1drycet Drycooler enable temperature

Integer

N

0..45

r

1gpst Glycol-pump start temperature

Integer

N

0..100

r/w

1gecwvo GE/CW valve off temperature

Integer

N

0..35

C

r/w

1gecwvs GE/CW valve start temperature

Float

N

0..10

r/w

1gecwvpb GE/CW valve proportional band

Float

N

0..10

r/w

1r1st Reheat 1 start temperature

Float

N

0..10

r/w

1r1h Reheat 1 hyteresis

Float

N

0..10

r/w

1r2st Reheat 2 start temperature

Float

N

0..10

r/w

1r2h Reheat 2 hysteresis

Float

N

0..10

r/w

1r3st Reheat 3 start temperature

Float

N

0..10

r/w

1r3h Reheat 3 hysteresis

Float

N

0..10

r/w

1pwwvs PWW valve start temperature

Float

N

0..10

r/w

1pwwvpb PWW valve proportional band

Float

N

0..10

r/w

1dhs Dehumidification start

Integer

N

0..90

r/w

1dhh Dehumidification hysteresis

Integer

N

0..90

r/w

1hums Humidification start

Integer

N

0..90

r/w

1humh Humidification hysteresis

Integer

N

0..90

r/w

1humsa Humidification start (analogue)

Integer

N

0..90

r/w

1humpba Humidification proportional band

Integer

N

0..90

r/w

1gcph Glycol-pump hysteresis

Float

N

0..10

r/w

Module 2

2comps Compressor start

Float

N

0..10

r/w

2comph Compressor hysteresis

Float

N

0..10

r/w

2svst Suction valve start

Float

N

0..10

r/w

2svpb Suction valve proportional ban

Float

N

0..10

r/w

2drycst Drycooler start temperature

Integer

N

0..45

C

r

2r1st Reheat 1 start temperature

Float

N

0..10

r/w

2r1h Reheat 1 hyteresis

Float

N

0..10

r/w

2r2st Reheat 2 start temperature

Float

N

0..10

r/w

2r2h Reheat 2 hysteresis

Float

N

0..10

r/w

2r3st Reheat 3 start temperature

Float

N

0..10

r/w

2r3h Reheat 3 hysteresis

Float

N

0..10

r/w

2dhs Dehumidification start

Integer

N

0..90

%

r/w

2dhh Dehumidification hysteresis

Integer

N

0..90

%

r/w

2hums Humidification start

Integer

N

0..90

%

r/w

2humh Humidification hysteresis

Integer

N

0..90

%

r/w

2humsa Humidification start (analogue)

Integer

N

0..90

%

r/w

2humpba Humidification proportional band

Integer

N

0..90

%

r/w

2gecwvs GE/CW valve start temperature

Float

N

0..10

r/w

2gecwvpb GE/CW valve proportional band

Float

N

0..10

r/w

Module 3

3comps Compressor start

Float

N

0..10

r/w

3comph Compressor hysteresis

Float

N

0..10

r/w

3svst Suction valve start

Float

N

0..10

r/w

3svpb Suction valve proportional ban

Float

N

0..10

r/w

3drycst Drycooler start temperature

Integer

N

0..45

C

r

3r1st Reheat 1 start temperature

Float

N

0..10

r/w

3r1h Reheat 1 hyteresis

Float

N

0..10

r/w

3r2st Reheat 2 start temperature

Float

N

0..10

r/w

3r2h Reheat 2 hysteresis

Float

N

0..10

r/w

3r3st Reheat 3 start temperature

Float

N

0..10

r/w

3r3h Reheat 3 hysteresis

Float

N

0..10

r/w

3dhs Dehumidification start

Integer

N

0..90

%

r/w

3dhh Dehumidification hysteresis

Integer

N

0..90

%

r/w

3hums Humidification start

Integer

N

0..90

%

r/w

3humh Humidification hysteresis

Integer

N

0..90

%

r/w

3humsa Humidification start (analogue)

Integer

N

0..90

%

r/w

3humpba Humidification proportional band

Integer

N

0..90

%

r/w

3gecwvs GE/CW valve start temperature

Float

N

0..10

r/w

3gecwvpb GE/CW valve proportional band

Float

N

0..10

r/w

Module 4

4comps Compressor start

Float

N

0..10

r/w

4comph Compressor hysteresis

Float

N

0..10

r/w

4svst Suction valve start

Float

N

0..10

r/w

4svpb Suction valve proportional ban

Float

N

0..10

r/w

4drycst Drycooler start temperature

Integer

N

0..45

C

r

4r1st Reheat 1 start temperature

Float

N

0..10

r/w

4r1h Reheat 1 hyteresis

Float

N

0..10

r/w

4r2st Reheat 2 start temperature

Float

N

0..10

r/w

4r2h Reheat 2 hysteresis

Float

N

0..10

r/w

4r3st Reheat 3 start temperature

Float

N

0..10

r/w

4r3h Reheat 3 hysteresis

Float

N

0..10

r/w

4dhs Dehumidification start

Integer

N

0..90

%

r/w

4dhh Dehumidification hysteresis

Integer

N

0..90

%

r/w

4hums Humidification start

Integer

N

0..90

%

r/w

4humh Humidification hysteresis

Integer

N

0..90

%

r/w

4humsa Humidification start (analogue)

Integer

N

0..90

%

r/w

4humpba Humidification proportional band

Integer

N

0..90

%

r/w

4gecwvs GE/CW valve start temperature

Float

N

0..10

r/w

4gecwvpb GE/CW valve proportional band

Float

N

0..10

r/w

Module 5

5comps Compressor start

Float

N

0..10

r/w

5comph Compressor hysteresis

Float

N

0..10

r/w

5svst Suction valve start

Float

N

0..10

r/w

5svpb Suction valve proportional ban

Float

N

0..10

r/w

5drycst Drycooler start temperature

Integer

N

0..45

C

r

5r1st Reheat 1 start temperature

Float

N

0..10

r/w

5r1h Reheat 1 hyteresis

Float

N

0..10

r/w

5r2st Reheat 2 start temperature

Float

N

0..10

r/w

5r2h Reheat 2 hysteresis

Float

N

0..10

r/w

5r3st Reheat 3 start temperature

Float

N

0..10

r/w

5r3h Reheat 3 hysteresis

Float

N

0..10

r/w

5dhs Dehumidification start

Integer

N

0..90

%

r/w

5dhh Dehumidification hysteresis

Integer

N

0..90

%

r/w

5hums Humidification start

Integer

N

0..90

%

r/w

5humh Humidification hysteresis

Integer

N

0..90

%

r/w

5humsa Humidification start (analogue)

Integer

N

0..90

%

r/w

5humpba Humidification proportional band

Integer

N

0..90

%

r/w

5gecwvs GE/CW valve start temperature

Float

N

0..10

r/w

5gecwvpb GE/CW valve proportional band

Float

N

0..10

r/w

Module 6

6comps Compressor start

Float

N

0..10

r/w

6comph Compressor hysteresis

Float

N

0..10

r/w

6svst Suction valve start

Float

N

0..10

r/w

6svpb Suction valve proportional ban

Float

N

0..10

r/w

6drycst Drycooler start temperature

Integer

N

0..45

C

r

6r1st Reheat 1 start temperature

Float

N

0..10

r/w

6r1h Reheat 1 hyteresis

Float

N

0..10

r/w

6r2st Reheat 2 start temperature

Float

N

0..10

r/w

6r2h Reheat 2 hysteresis

Float

N

0..10

r/w

6r3st Reheat 3 start temperature

Float

N

0..10

r/w

6r3h Reheat 3 hysteresis

Float

N

0..10

r/w

6dhs Dehumidification start

Integer

N

0..90

%

r/w

6dhh Dehumidification hysteresis

Integer

N

0..90

%

r/w

6hums Humidification start

Integer

N

0..90

%

r/w

6humh Humidification hysteresis

Integer

N

0..90

%

r/w

6humsa Humidification start (analogue)

Integer

N

0..90

%

r/w

6humpba Humidification proportional band

Integer

N

0..90

%

r/w

6gecwvs GE/CW valve start temperature

Float

N

0..10

r/w

6gecwvpb GE/CW valve proportional band

Float

N

0..10

r/w

gst1 General status byte 1

Packed_Bit

0

0 = PC-STOP (monitoring),  1 = on

Bit

r/w

1

0 = REMOTE STOP (contact),  1 = on

Bit

r

2

0 = LOCAL STOP (key),  1 = on

Bit

r

3

0 = TIMER-STOP (weekly oper.),  1 = on

Bit

r

4

Seq. Start/Stop (0=No, 1=Yes)

Bit

r

5

WARM UP STOP

Bit

r

6

Remote UPS    1 = UPS activ

Bit

r

7

Local UPS    1 = UPS activ

Bit

r

gst2 General status byte 2

Packed_Bit

0

G/CW-mode; G:1, CW:0

Bit

r/w

1

CW-Valve OR/AND – selector

Bit

r

2

not used

3

not used

4

not used

5

not used

6

not used

7

not used
err1 Error byte 1

Packed_Bit

0

return air temp. too high alarm

Bit

r

1

return air humid. Too high alarm

Bit

r

2

supply air temp. too high alarm

Bit

r

3

supply air humid. Too high alarm

Bit

r

4

water temp. too high alarm

Bit

r

5

return air temp. too low alarm

Bit

r

6

return air humid. Too low alarm

Bit

r

7

supply air temp. too low alarm

Bit

r

err2 Error byte 2

Packed_Bit

0

supply air humid. Too low alarm

Bit

r

1

water temp. too low alarm

Bit

r

2

supervisor failure

Bit

r

3

freeze alarm

Bit

r

4

fire / smoke detector

Bit

r

5

sensor failure

Bit

r

6

controller failure

Bit

r

7

IO-board transmission failure

Bit

r

ar[5] Alarm reset

None

w

 

 

 

 

THIS PAGE INTENTIONALLY LEFT BLANK


[1] These commands’ structure match the m1o1 structure

[2] These commands’ structure match the m1o2 structure

[3] These commands’ structure match the m1i1 structure

[4] These commands’ structure match the m1i2 structure

[5] Writing any value to this command will reset the alarms on the Stulz unit