FieldServer Driver
FS-8700-125
Stulz
Description
The Stulz driver allows the transfer of data from a Stulz device using the Stulz monitoring protocol version 1.7. The Fieldserver can act as a Client.
Currently, only the C6000 microcontroller is supported as the protocol only specifies read capabilities on that unit.
The Client is configurable to read all information into separate data points and supports writing to selected points as specified below.
It supports the following formats:
- Float values
- Binary values
- Integer values
| Fieldserver Mode | Remote Nodes | Comments |
| Client | 32 | The protocol supports only one Client per bus, which can poll 32 server devices |
Formal Driver Type
Serial
Client Only
Compatibility Matrix
| FieldServer Model | Compatible with this driver |
| FS-x2010 | Yes |
| FS-x2011 | Yes |
| FS-x40 | Yes |
| FS-x30 | Yes |
Connection Information
| Connection type: | RS-485 (Two wire, Half-Duplex) |
| Baud Rates: | 9600 – Vendor Limitation |
| Data Bits: | 8 |
| Stop Bits: | 1 |
| Parity: | None |
| Multidrop Capability | Yes |
Devices tested
| Device | Tested (FACTORY, SITE) |
| C6000 | FACTORY |
Connection configurations
Connection Notes
Use terminating resistors to enhance communication quality.
Communications functions – Supported functions at a glance:
Read Operations supported
| FieldServer as a Client |
| Read Analog Status: |
|
|
|
|
|
|
|
|
| Read Binary Status: |
|
|
|
|
Write (Control) Operations supported
| FieldServer as a Client |
| Write Analog Setpoints: |
|
|
|
|
| Write Binary Commands: |
|
|
|
Unsupported Functions and Data Types
| Function | Reason |
| Programming messages | FieldServer is a data transfer device, and as such, programming messages are not required |
Unsupported Devices or Protocol Options
| Device | Details |
| C1001/2 | The protocol does not specify any reading functions for this device |
| C1010 | The protocol does not specify any reading functions for this device |
| C4000 | The protocol does not specify any reading functions for this device |
| C5000 | The protocol does not specify any reading functions for this device |
Complete command table
| FieldServer as a Client | ||||||
| Command descriptions and supported status | ||||||
| Command | Description |
Data_type |
Signed |
Range |
Units |
C6000 |
|
Active commands |
||||||
| ls | Long state request |
Byte |
N |
- |
|
r |
|
m1fss |
Module 1 fan speed setpoint |
Integer |
N |
0..100 |
% |
r/w |
|
m2fss |
Module 2 fan speed setpoint |
Integer |
N |
0..100 |
% |
r/w |
|
m3fss |
Module 3 fan speed setpoint |
Integer |
N |
0..100 |
% |
r/w |
|
m4fss |
Module 4 fan speed setpoint |
Integer |
N |
0..100 |
% |
r/w |
|
m5fss |
Module 5 fan speed setpoint |
Integer |
N |
0..100 |
% |
r/w |
|
m6fss |
Module 6 fan speed setpoint |
Integer |
N |
0..100 |
% |
r/w |
|
m1dcsst |
Module 1 drycooler summer start |
Integer |
N |
0..50 |
C |
r/w |
|
m1dcwst |
Module 1 drycooler winter start |
Integer |
N |
0..30 |
C |
r/w |
|
m2dcsst |
Module 2 drycooler summer start |
Integer |
N |
0..50 |
C |
r/w |
|
m2dcwst |
Module 2 drycooler winter start |
Integer |
N |
0..30 |
C |
r/w |
|
m3dcsst |
Module 3 drycooler summer start |
Integer |
N |
0..50 |
C |
r/w |
|
m3dcwst |
Module 3 drycooler winter start |
Integer |
N |
0..30 |
C |
r/w |
|
m4dcsst |
Module 4 drycooler summer start |
Integer |
N |
0..50 |
C |
r/w |
|
m4dcwst |
Module 4 drycooler winter start |
Integer |
N |
0..30 |
C |
r/w |
|
m5dcsst |
Module 5 drycooler summer start |
Integer |
N |
0..50 |
C |
r/w |
|
m5dcwst |
Module 5 drycooler winter start |
Integer |
N |
0..30 |
C |
r/w |
|
m6dcsst |
Module 6 drycooler summer start |
Integer |
N |
0..50 |
C |
r/w |
|
m6dcwst |
Module 6 drycooler winter start |
Integer |
N |
0..30 |
C |
r/w |
|
Passive_Client commands |
||||||
| wt | Water temperature |
Float |
Y |
-50..50 |
C |
r |
| rat | Return air temperature |
Float |
N |
0..100 |
C |
r |
| sat | Supply air temperature |
Float |
N |
0..100 |
C |
r |
| rah | Return air humidity |
Float |
N |
0..100 |
% |
r |
| sah | Supply air humidity |
Float |
N |
0..100 |
% |
r |
| oat | Outside air temperature |
Float |
Y |
-50..50 |
C |
r |
| oah | Outside air humidity |
Float |
N |
0..100 |
% |
r |
| tss | Temperature set point shift |
Float |
Y |
-12.7..12.7 |
C |
r |
| hss | Humidity set point shift |
Float |
Y |
-12.7..12.7 |
% |
r |
| swv | Software version |
|
|
|
|
r |
| m1o1 | Module 1 digital out status byte 1 |
Packed_Bit |
|
|
|
r |
|
0 |
Reheat 1 |
Bit |
|
|
|
r |
|
1 |
Compressor 1 |
Bit |
|
|
|
r |
|
2 |
Humidification 1 |
Bit |
|
|
|
r |
|
3 |
Dehumidification 1 |
Bit |
|
|
|
r |
|
4 |
Fan 1 |
Bit |
|
|
|
r |
|
5 |
Dry cooler |
Bit |
|
|
|
r |
|
6 |
Alarm relays 1 (1= no alarm) |
Bit |
|
|
|
r |
|
7 |
PWW |
Bit |
|
|
|
r |
| m1o2 | Module 1 digital out status byte 2 |
Packed_Bit |
|
|
|
r |
|
0 |
Reheat 2 |
Bit |
|
|
|
r |
|
1 |
Glycol pump |
Bit |
|
|
|
r |
|
2 |
Louver (0=closed, 1=open) |
Bit |
|
|
|
r |
|
3 |
Alarm relays 2 (1= no alarm) |
Bit |
|
|
|
r |
|
4 |
Alarm relays 3 (1= no alarm) |
Bit |
|
|
|
r |
|
5 |
Alarm relays 4 (1= no alarm) |
Bit |
|
|
|
r |
|
6 |
Alarm relays 5 (1= no alarm) |
Bit |
|
|
|
r |
|
7 |
Glycol pump 1/2 select |
Bit |
|
|
|
r |
| m2o1[1] | Module 2 digital out status byte 1 |
Packed_Bit |
|
|
|
r |
| m2o2[2] | Module 2 digital out status byte 2 |
Packed_Bit |
|
|
|
r |
| m3o1Error! Bookmark not defined. | Module 3 digital out status byte 1 |
Packed_Bit |
|
|
|
r |
| m3o2Error! Bookmark not defined. | Module 3 digital out status byte 2 |
Packed_Bit |
|
|
|
r |
| m4o1Error! Bookmark not defined. | Module 4 digital out status byte 1 |
Packed_Bit |
|
|
|
r |
| m4o2Error! Bookmark not defined. | Module 4 digital out status byte 2 |
Packed_Bit |
|
|
|
r |
| m5o1Error! Bookmark not defined. | Module 5 digital out status byte 1 |
Packed_Bit |
|
|
|
r |
| m5o2Error! Bookmark not defined. | Module 5 digital out status byte 2 |
Packed_Bit |
|
|
|
r |
| m6o1Error! Bookmark not defined. | Module 6 digital out status byte 1 |
Packed_Bit |
|
|
|
r |
| m6o2Error! Bookmark not defined. | Module 6 digital out status byte 2 |
Packed_Bit |
|
|
|
r |
| m1i1 | Module 1 digital in status byte 1 |
Packed_Bit |
|
|
|
r |
|
0 |
Compressor low pressure |
Bit |
|
|
|
r |
|
1 |
Compressor high pressure |
Bit |
|
|
|
r |
|
2 |
Reheat 1 failure |
Bit |
|
|
|
r |
|
3 |
Humidification failure |
Bit |
|
|
|
r |
|
4 |
Air flow failure |
Bit |
|
|
|
r |
|
5 |
Filter clogged |
Bit |
|
|
|
r |
|
6 |
Aux alarm 1 |
Bit |
|
|
|
r |
|
7 |
Reheat 2 alarm |
Bit |
|
|
|
r |
| m1i2 | Module 1 digital in status byte 2 |
Packed_Bit |
|
|
|
r |
|
0 |
Conductivity too high |
Bit |
|
|
|
r |
|
1 |
Ultrasonic failure |
Bit |
|
|
|
r |
|
2 |
Glycol pump 1 failure |
Bit |
|
|
|
r |
|
3 |
Glycol pump 2 failure |
Bit |
|
|
|
r |
|
4 |
Drycooler failure |
Bit |
|
|
|
r |
|
5 |
Water detector |
Bit |
|
|
|
r |
|
6 |
Aux alarm 2 |
Bit |
|
|
|
r |
|
7 |
Aux alarm 3 |
Bit |
|
|
|
r |
| m2i1[3] | Module 2 digital in status byte 1 |
Packed_Bit |
|
|
|
r |
| m2i2[4] | Module 2 digital in status byte 2 |
Packed_Bit |
|
|
|
r |
| m3i1Error! Bookmark not defined. | Module 3 digital in status byte 1 |
Packed_Bit |
|
|
|
r |
| m3i2Error! Bookmark not defined. | Module 3 digital in status byte 2 |
Packed_Bit |
|
|
|
r |
| m4i1Error! Bookmark not defined. | Module 4 digital in status byte 1 |
Packed_Bit |
|
|
|
r |
| m4i2Error! Bookmark not defined. | Module 4 digital in status byte 2 |
Packed_Bit |
|
|
|
r |
| m5i1Error! Bookmark not defined. | Module 5 digital in status byte 1 |
Packed_Bit |
|
|
|
r |
| m5i2Error! Bookmark not defined. | Module 5 digital in status byte 2 |
Packed_Bit |
|
|
|
r |
| m6i1Error! Bookmark not defined. | Module 6 digital in status byte 1 |
Packed_Bit |
|
|
|
r |
| m6i2Error! Bookmark not defined. | Module 6 digital in status byte 2 |
Packed_Bit |
|
|
|
r |
| m1gecw | Module 1 analogue out GE/CW |
Float |
N |
0..100 |
|
r |
| m2gecw | Module 2 analogue out GE/CW |
Float |
N |
0..100 |
|
r |
| m3gecw | Module 3 analogue out GE/CW |
Float |
N |
0..100 |
|
r |
| m4gecw | Module 4 analogue out GE/CW |
Float |
N |
0..100 |
|
r |
| m5gecw | Module 5 analogue out GE/CW |
Float |
N |
0..100 |
|
r |
| m6gecw | Module 6 analogue out GE/CW |
Float |
N |
0..100 |
|
r |
| m1pww | Module 1 analogue out PWW |
Float |
N |
0..100 |
|
r |
| m2pww | Module 2 analogue out PWW |
Float |
N |
0..100 |
|
r |
| m3pww | Module 3 analogue out PWW |
Float |
N |
0..100 |
|
r |
| m4pww | Module 4 analogue out PWW |
Float |
N |
0..100 |
|
r |
| m5pww | Module 5 analogue out PWW |
Float |
N |
0..100 |
|
r |
| m6pww | Module 6 analogue out PWW |
Float |
N |
0..100 |
|
r |
| m1aoh | Module 1 analogue out humidifier |
Float |
N |
0..100 |
|
r |
| m2aoh | Module 2 analogue out humidifier |
Float |
N |
0..100 |
|
r |
| m3aoh | Module 3 analogue out humidifier |
Float |
N |
0..100 |
|
r |
| m4aoh | Module 4 analogue out humidifier |
Float |
N |
0..100 |
|
r |
| m5aoh | Module 5 analogue out humidifier |
Float |
N |
0..100 |
|
r |
| m6aoh | Module 6 analogue out humidifier |
Float |
N |
0..100 |
|
r |
| m1aosv | Module 1 analogue out suction valve |
Float |
N |
0..100 |
|
r |
| m2aosv | Module 2 analogue out suction valve |
Float |
N |
0..100 |
|
r |
| m3aosv | Module 3 analogue out suction valve |
Float |
N |
0..100 |
|
r |
| m4aosv | Module 4 analogue out suction valve |
Float |
N |
0..100 |
|
r |
| m5aosv | Module 5 analogue out suction valve |
Float |
N |
0..100 |
|
r |
| m6aosv | Module 6 analogue out suction valve |
Float |
N |
0..100 |
|
r |
| m16doc2 | Module 1-6 digital out compressor 2 |
Packed_Bit |
|
|
|
r |
|
0 |
Module 1 compressor 2 |
Bit |
|
|
|
r |
|
1 |
Module 2 compressor 2 |
Bit |
|
|
|
r |
|
2 |
Module 3 compressor 2 |
Bit |
|
|
|
r |
|
3 |
Module 4 compressor 2 |
Bit |
|
|
|
r |
|
4 |
Module 5 compressor 2 |
Bit |
|
|
|
r |
|
5 |
Module 6 compressor 2 |
Bit |
|
|
|
r |
|
6 |
Not used |
Bit |
|
|
|
r |
|
7 |
Not used |
Bit |
|
|
|
r |
| m14dic2 | Module 1-4 digital in compressor 2 |
Packed_Bit |
|
|
|
r |
|
0 |
modul 1 compressor 2 low pressure |
Bit |
|
|
|
r |
|
1 |
modul 1 compressor 2 high pressure |
Bit |
|
|
|
r |
|
2 |
modul 2 compressor 2 low pressure |
Bit |
|
|
|
r |
|
3 |
modul 2 compressor 2 high pressure |
Bit |
|
|
|
r |
|
4 |
modul 3 compressor 2 low pressure |
Bit |
|
|
|
r |
|
5 |
modul 3 compressor 2 high pressure |
Bit |
|
|
|
r |
|
6 |
modul 4 compressor 2 low pressure |
Bit |
|
|
|
r |
|
7 |
modul 4 compressor 2 high pressure |
Bit |
|
|
|
r |
| m56dic2 | Module 5-6 digital in compressor 2 |
Packed_Bit |
|
|
|
r |
|
0 |
modul 5 compressor 2 low pressure |
Bit |
|
|
|
r |
|
1 |
modul 5 compressor 2 high pressure |
Bit |
|
|
|
r |
|
2 |
modul 6 compressor 2 low pressure |
Bit |
|
|
|
r |
|
3 |
modul 6 compressor 2 high pressure |
Bit |
|
|
|
r |
|
4 |
not used |
Bit |
|
|
|
r |
|
5 |
not used |
Bit |
|
|
|
r |
|
6 |
not used |
Bit |
|
|
|
r |
|
7 |
not used |
Bit |
|
|
|
r |
| sett | Setpoint temperature |
Float |
N |
10..35 |
C |
r/w |
| seth | Setpoint humidity |
Integer |
N |
10..90 |
% |
r/w |
| year | Date – Year |
Integer |
N |
0..99 |
|
r/w |
| month | Date – Month |
Integer |
N |
1..12 |
|
r/w |
| day | Date – Day |
Integer |
N |
1..31 |
|
r/w |
| hour | Time – Hour |
Integer |
N |
0..23 |
|
r/w |
| minute | Time – Minute |
Integer |
N |
0..59 |
|
r/w |
| ratha | Return air temperature too high alarm |
Integer |
N |
0..30 |
C |
r/w |
| satha | Supply air temperature too high alarm |
Integer |
N |
0..30 |
C |
r/w |
| ratla | Return air temperature too low alarm |
Integer |
N |
0..30 |
C |
r/w |
| satla | Supply air temperature too low alarm |
Integer |
N |
0..30 |
C |
r/w |
| wtha | Water temperature too high alarm |
Integer |
N |
0..50 |
C |
r/w |
| wtla | Water temperature too low alarm |
Integer |
Y |
-50..30 |
C |
r/w |
| rahha | Return air humidity too high alarm |
Integer |
N |
0..90 |
% |
r/w |
| sahha | Supply air humidity too high alarm |
Integer |
N |
0..90 |
% |
r/w |
| rahla | Return air humidity too low alarm |
Integer |
N |
0..90 |
% |
r/w |
| sahla | Supply air humidity too low alarm |
Integer |
N |
0..90 |
% |
r/w |
|
Module 1 |
||||||
| 1comps | Compressor start |
Float |
N |
0..10 |
|
r/w |
| 1comph | Compressor hysteresis |
Float |
N |
0..10 |
|
r/w |
| 1svst | Suction valve start |
Float |
N |
0..10 |
|
r/w |
| 1svpb | Suction valve proportional ban |
Float |
N |
0..10 |
|
r/w |
| 1drycst | Drycooler start temperature |
Integer |
N |
0..45 |
|
r |
| 1drycet | Drycooler enable temperature |
Integer |
N |
0..45 |
|
r |
| 1gpst | Glycol-pump start temperature |
Integer |
N |
0..100 |
|
r/w |
| 1gecwvo | GE/CW valve off temperature |
Integer |
N |
0..35 |
C |
r/w |
| 1gecwvs | GE/CW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 1gecwvpb | GE/CW valve proportional band |
Float |
N |
0..10 |
|
r/w |
| 1r1st | Reheat 1 start temperature |
Float |
N |
0..10 |
|
r/w |
| 1r1h | Reheat 1 hyteresis |
Float |
N |
0..10 |
|
r/w |
| 1r2st | Reheat 2 start temperature |
Float |
N |
0..10 |
|
r/w |
| 1r2h | Reheat 2 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 1r3st | Reheat 3 start temperature |
Float |
N |
0..10 |
|
r/w |
| 1r3h | Reheat 3 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 1pwwvs | PWW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 1pwwvpb | PWW valve proportional band |
Float |
N |
0..10 |
|
r/w |
| 1dhs | Dehumidification start |
Integer |
N |
0..90 |
|
r/w |
| 1dhh | Dehumidification hysteresis |
Integer |
N |
0..90 |
|
r/w |
| 1hums | Humidification start |
Integer |
N |
0..90 |
|
r/w |
| 1humh | Humidification hysteresis |
Integer |
N |
0..90 |
|
r/w |
| 1humsa | Humidification start (analogue) |
Integer |
N |
0..90 |
|
r/w |
| 1humpba | Humidification proportional band |
Integer |
N |
0..90 |
|
r/w |
| 1gcph | Glycol-pump hysteresis |
Float |
N |
0..10 |
|
r/w |
|
Module 2 |
||||||
| 2comps | Compressor start |
Float |
N |
0..10 |
|
r/w |
| 2comph | Compressor hysteresis |
Float |
N |
0..10 |
|
r/w |
| 2svst | Suction valve start |
Float |
N |
0..10 |
|
r/w |
| 2svpb | Suction valve proportional ban |
Float |
N |
0..10 |
|
r/w |
| 2drycst | Drycooler start temperature |
Integer |
N |
0..45 |
C |
r |
| 2r1st | Reheat 1 start temperature |
Float |
N |
0..10 |
|
r/w |
| 2r1h | Reheat 1 hyteresis |
Float |
N |
0..10 |
|
r/w |
| 2r2st | Reheat 2 start temperature |
Float |
N |
0..10 |
|
r/w |
| 2r2h | Reheat 2 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 2r3st | Reheat 3 start temperature |
Float |
N |
0..10 |
|
r/w |
| 2r3h | Reheat 3 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 2dhs | Dehumidification start |
Integer |
N |
0..90 |
% |
r/w |
| 2dhh | Dehumidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 2hums | Humidification start |
Integer |
N |
0..90 |
% |
r/w |
| 2humh | Humidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 2humsa | Humidification start (analogue) |
Integer |
N |
0..90 |
% |
r/w |
| 2humpba | Humidification proportional band |
Integer |
N |
0..90 |
% |
r/w |
| 2gecwvs | GE/CW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 2gecwvpb | GE/CW valve proportional band |
Float |
N |
0..10 |
|
r/w |
|
Module 3 |
||||||
| 3comps | Compressor start |
Float |
N |
0..10 |
|
r/w |
| 3comph | Compressor hysteresis |
Float |
N |
0..10 |
|
r/w |
| 3svst | Suction valve start |
Float |
N |
0..10 |
|
r/w |
| 3svpb | Suction valve proportional ban |
Float |
N |
0..10 |
|
r/w |
| 3drycst | Drycooler start temperature |
Integer |
N |
0..45 |
C |
r |
| 3r1st | Reheat 1 start temperature |
Float |
N |
0..10 |
|
r/w |
| 3r1h | Reheat 1 hyteresis |
Float |
N |
0..10 |
|
r/w |
| 3r2st | Reheat 2 start temperature |
Float |
N |
0..10 |
|
r/w |
| 3r2h | Reheat 2 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 3r3st | Reheat 3 start temperature |
Float |
N |
0..10 |
|
r/w |
| 3r3h | Reheat 3 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 3dhs | Dehumidification start |
Integer |
N |
0..90 |
% |
r/w |
| 3dhh | Dehumidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 3hums | Humidification start |
Integer |
N |
0..90 |
% |
r/w |
| 3humh | Humidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 3humsa | Humidification start (analogue) |
Integer |
N |
0..90 |
% |
r/w |
| 3humpba | Humidification proportional band |
Integer |
N |
0..90 |
% |
r/w |
| 3gecwvs | GE/CW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 3gecwvpb | GE/CW valve proportional band |
Float |
N |
0..10 |
|
r/w |
|
Module 4 |
||||||
| 4comps | Compressor start |
Float |
N |
0..10 |
|
r/w |
| 4comph | Compressor hysteresis |
Float |
N |
0..10 |
|
r/w |
| 4svst | Suction valve start |
Float |
N |
0..10 |
|
r/w |
| 4svpb | Suction valve proportional ban |
Float |
N |
0..10 |
|
r/w |
| 4drycst | Drycooler start temperature |
Integer |
N |
0..45 |
C |
r |
| 4r1st | Reheat 1 start temperature |
Float |
N |
0..10 |
|
r/w |
| 4r1h | Reheat 1 hyteresis |
Float |
N |
0..10 |
|
r/w |
| 4r2st | Reheat 2 start temperature |
Float |
N |
0..10 |
|
r/w |
| 4r2h | Reheat 2 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 4r3st | Reheat 3 start temperature |
Float |
N |
0..10 |
|
r/w |
| 4r3h | Reheat 3 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 4dhs | Dehumidification start |
Integer |
N |
0..90 |
% |
r/w |
| 4dhh | Dehumidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 4hums | Humidification start |
Integer |
N |
0..90 |
% |
r/w |
| 4humh | Humidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 4humsa | Humidification start (analogue) |
Integer |
N |
0..90 |
% |
r/w |
| 4humpba | Humidification proportional band |
Integer |
N |
0..90 |
% |
r/w |
| 4gecwvs | GE/CW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 4gecwvpb | GE/CW valve proportional band |
Float |
N |
0..10 |
|
r/w |
|
Module 5 |
||||||
| 5comps | Compressor start |
Float |
N |
0..10 |
|
r/w |
| 5comph | Compressor hysteresis |
Float |
N |
0..10 |
|
r/w |
| 5svst | Suction valve start |
Float |
N |
0..10 |
|
r/w |
| 5svpb | Suction valve proportional ban |
Float |
N |
0..10 |
|
r/w |
| 5drycst | Drycooler start temperature |
Integer |
N |
0..45 |
C |
r |
| 5r1st | Reheat 1 start temperature |
Float |
N |
0..10 |
|
r/w |
| 5r1h | Reheat 1 hyteresis |
Float |
N |
0..10 |
|
r/w |
| 5r2st | Reheat 2 start temperature |
Float |
N |
0..10 |
|
r/w |
| 5r2h | Reheat 2 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 5r3st | Reheat 3 start temperature |
Float |
N |
0..10 |
|
r/w |
| 5r3h | Reheat 3 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 5dhs | Dehumidification start |
Integer |
N |
0..90 |
% |
r/w |
| 5dhh | Dehumidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 5hums | Humidification start |
Integer |
N |
0..90 |
% |
r/w |
| 5humh | Humidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 5humsa | Humidification start (analogue) |
Integer |
N |
0..90 |
% |
r/w |
| 5humpba | Humidification proportional band |
Integer |
N |
0..90 |
% |
r/w |
| 5gecwvs | GE/CW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 5gecwvpb | GE/CW valve proportional band |
Float |
N |
0..10 |
|
r/w |
|
Module 6 |
||||||
| 6comps | Compressor start |
Float |
N |
0..10 |
|
r/w |
| 6comph | Compressor hysteresis |
Float |
N |
0..10 |
|
r/w |
| 6svst | Suction valve start |
Float |
N |
0..10 |
|
r/w |
| 6svpb | Suction valve proportional ban |
Float |
N |
0..10 |
|
r/w |
| 6drycst | Drycooler start temperature |
Integer |
N |
0..45 |
C |
r |
| 6r1st | Reheat 1 start temperature |
Float |
N |
0..10 |
|
r/w |
| 6r1h | Reheat 1 hyteresis |
Float |
N |
0..10 |
|
r/w |
| 6r2st | Reheat 2 start temperature |
Float |
N |
0..10 |
|
r/w |
| 6r2h | Reheat 2 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 6r3st | Reheat 3 start temperature |
Float |
N |
0..10 |
|
r/w |
| 6r3h | Reheat 3 hysteresis |
Float |
N |
0..10 |
|
r/w |
| 6dhs | Dehumidification start |
Integer |
N |
0..90 |
% |
r/w |
| 6dhh | Dehumidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 6hums | Humidification start |
Integer |
N |
0..90 |
% |
r/w |
| 6humh | Humidification hysteresis |
Integer |
N |
0..90 |
% |
r/w |
| 6humsa | Humidification start (analogue) |
Integer |
N |
0..90 |
% |
r/w |
| 6humpba | Humidification proportional band |
Integer |
N |
0..90 |
% |
r/w |
| 6gecwvs | GE/CW valve start temperature |
Float |
N |
0..10 |
|
r/w |
| 6gecwvpb | GE/CW valve proportional band |
Float |
N |
0..10 |
|
r/w |
| gst1 | General status byte 1 |
Packed_Bit |
|
|
|
|
|
0 |
0 = PC-STOP (monitoring), 1 = on |
Bit |
|
|
|
r/w |
|
1 |
0 = REMOTE STOP (contact), 1 = on |
Bit |
|
|
|
r |
|
2 |
0 = LOCAL STOP (key), 1 = on |
Bit |
|
|
|
r |
|
3 |
0 = TIMER-STOP (weekly oper.), 1 = on |
Bit |
|
|
|
r |
|
4 |
Seq. Start/Stop (0=No, 1=Yes) |
Bit |
|
|
|
r |
|
5 |
WARM UP STOP |
Bit |
|
|
|
r |
|
6 |
Remote UPS 1 = UPS activ |
Bit |
|
|
|
r |
|
7 |
Local UPS 1 = UPS activ |
Bit |
|
|
|
r |
| gst2 | General status byte 2 |
Packed_Bit |
|
|
|
|
|
0 |
G/CW-mode; G:1, CW:0 |
Bit |
|
|
|
r/w |
|
1 |
CW-Valve OR/AND – selector |
Bit |
|
|
|
r |
|
2 |
not used |
|
|
|
|
|
|
3 |
not used |
|
|
|
|
|
|
4 |
not used |
|
|
|
|
|
|
5 |
not used |
|
|
|
|
|
|
6 |
not used |
|
|
|
|
|
|
7 |
not used |
|
|
|
|
|
| err1 | Error byte 1 |
Packed_Bit |
|
|
|
|
|
0 |
return air temp. too high alarm |
Bit |
|
|
|
r |
|
1 |
return air humid. Too high alarm |
Bit |
|
|
|
r |
|
2 |
supply air temp. too high alarm |
Bit |
|
|
|
r |
|
3 |
supply air humid. Too high alarm |
Bit |
|
|
|
r |
|
4 |
water temp. too high alarm |
Bit |
|
|
|
r |
|
5 |
return air temp. too low alarm |
Bit |
|
|
|
r |
|
6 |
return air humid. Too low alarm |
Bit |
|
|
|
r |
|
7 |
supply air temp. too low alarm |
Bit |
|
|
|
r |
| err2 | Error byte 2 |
Packed_Bit |
|
|
|
|
|
0 |
supply air humid. Too low alarm |
Bit |
|
|
|
r |
|
1 |
water temp. too low alarm |
Bit |
|
|
|
r |
|
2 |
supervisor failure |
Bit |
|
|
|
r |
|
3 |
freeze alarm |
Bit |
|
|
|
r |
|
4 |
fire / smoke detector |
Bit |
|
|
|
r |
|
5 |
sensor failure |
Bit |
|
|
|
r |
|
6 |
controller failure |
Bit |
|
|
|
r |
|
7 |
IO-board transmission failure |
Bit |
|
|
|
r |
| ar[5] | Alarm reset |
None |
|
|
|
w |
THIS PAGE INTENTIONALLY LEFT BLANK
[1] These commands’ structure match the m1o1 structure
[2] These commands’ structure match the m1o2 structure
[3] These commands’ structure match the m1i1 structure
[4] These commands’ structure match the m1i2 structure
[5] Writing any value to this command will reset the alarms on the Stulz unit