CAS-2700-12 Veeder TLS 300, 350, 450 Modbus Gateway

CAS-2700-12
Veeder TLS 300, 350, 450
Modbus Gateway

 

Description

The Veeder Serial Driver allows the Gateway to poll Veeder TLS Panel’s for status, real time and configuration data. Thus the driver can be used to read Tank Inventory, System Status, Tank Alarms, Sensor Alarms and more .

The Veeder Gateway serves data from a TLS panel as ModbusRTU or ModbusTCP. In addition the current data can be used by browsing to the gateway’s web server. The gateway supports all these options simultaneously. Use the data you want and ignore the other.

The Gateway connects to the TLS Panel, reads data and stores it internally. When a remote system requests data, this data is served in a form that is appropriate to the protocol. In the event that the connection to the TLS Panel is lost, or data cannot be read, the gateway can signal this to the remote data client.

The gateway requires minimal configuration and can be considered a plug and play component of a system, in that it is ready to operate out of the box with the default configuration.

The driver is a serial driver using a RS232 serial port to connect between the Gateway and the TLS Panel. The Panel must have a suitable RS232 card installed.

Specs.

  • UL and ULc approved
  • 10/100BaseT with RJ-45 connector
  • 1x RS232 Port
  • 1x RS485 Port (Different Models have additional ports)
  • 2MBytes flash memory, 8MBytes of SDRAM
  • Power: 5-24VDC
  • Operating Temperature: 0 to 70 C
  • Dimensions: 4.2″ x 3.25″ x 1″
  • LEDs: Link, Speed/Data, Power

 

Max Nodes Supported

Gateway Mode Nodes Comments
Client 1 Only 1 TLS Panel per connection
Server 0 Not supported or documented.

Connection Information – Port 1: Veeder Port

Connection type: EIA232
Baud Rates: Driver Supports : 1200, 2400, 4800, 9600; 19200Baud
Data Bits: Driver Supports : 7,8
Stop Bits: Driver Supports : 1,2
Parity: Driver Supports : Odd, Even, None
Hardware interface: N/A
Multidrop Capability No

Connection Information – Port 2: Modbus RTU Server Port

Connection type: RS485 (Jumper change to RS232)
Baud Rates: 9600; 19200 Baud
Data Bits: 8
Stop Bits: 1
Parity: None
Hardware interface: N/A
Multidrop Capability Yes

Devices tested

Device Tested (FACTORY, SITE)
Veeder TLS 300 Tested
Veeder TLS 350 Tested
Veeder TLS 350 Plus Tested
Veeder TLS 450 Tested

Connection configurations

2700-12

 

Driver Operation

The driver can be configured to execute any of the commands in the ‘supported function’ list. The data sent is stored internally in the Gateway and is made available to other protocols (Modbus RTU, Modbus TCP and HTML) .

The frequency with each data point is read is configurable. The driver retries on errors or timeouts. If the data cannot be read then after some configurable time it is marked as out of service.

The driver reports operating stats and issues on a web page, maintains a log that can be uploaded by HTTP or ftp.

Configuration

Via Web Page. Configure IP settings, Node ID’s, Baud Rate and other parameters.

Users are able to select
Up to 10 Tanks – specify the number and name of each
Up to 10 Sensors – specify the number and name of each
Up to 1 Vacuum Sensor – specify the number and name of each

The names are used to form the names of the BACnet objects and populate the web page showing current values.

User can specify
ModbusTCP: Node_ID
ModbusRTU: Node_ID, baud, parity, data length, stop bits
BACnet: Device instance number, device name.

Communications functions

Supported functions.
Not all Veeder communication functions are supported. The following functions are supported by the Web based configuration. Additional functions are supported but must be configured manually.

COMMAND
101 System Status Report
201 In-Tank Inventory Report
202 In-Tank Delivery Report
203 In-Tank Leak Detect Report
B38 Vacuum Sensor Report

The driver will not send the next command until a response has been received from the previous or until a timeout has expired.

Support

This driver was developed by Chipkin Automation Systems (CAS). CAS are proud to provide support for the driver. For support please call CAS at (866) 383-1657.

 

Revision History

Date Resp Format Driver Ver. Doc. Rev. Comment
2012Feb17 PMC 0.00 0 Created
2012Feb23 PMC 0.00 1 Typos.
If you liked this post;
  • Please consider subscribing to our RSS feed