| 102 | GENERATOR AVERAGE AC RMS FREQUENCY | 1 REGISTER (2 BYTES) LONG | READ | Average AC frequency measured at the generator output. | 1/128 Hz / bit | 0 Hz | 0 to 501.9922 Hz | |
| 100 | GENERATOR AVERAGE LINE-LINE AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Average Line to Line RMS voltage measured at the generator output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 163 | GENERATOR AVERAGE LINE-LINE AC RMS VOLTAGE PERCENT | 1 REGISTER (2 BYTES) LONG | READ | Average Line to Line RMS voltage at the generator, as a percentage of nominal generator voltage. | 0.0078125 % / bit | -251.00% | -251 to 250.99% | |
| 108 | GENERATOR PHASE A LINE-LINE AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Line to Line RMS voltage measured at the generator phase AB output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 109 | GENERATOR PHASE B LINE-LINE AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Line to Line RMS voltage measured at the generator phase BC output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 110 | GENERATOR PHASE C LINE-LINE AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Line to Line RMS voltage measured at the generator phase CA output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 148 | GENERATOR AVERAGE LINE-NEUTRAL AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | The average Line to Neutral AC RMS voltage measured at the generator output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 114 | GENERATOR PHASE A LINE-NEUTRAL AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Line to Neutral RMS voltage measured at the generator phase A output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 115 | GENERATOR PHASE B LINE-NEUTRAL AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Line to Neutral RMS voltage measured at the generator phase B output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 116 | GENERATOR PHASE C LINE-NEUTRAL AC RMS VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Line to Neutral RMS voltage measured at the generator phase C output. | 1 V / bit | 0 V | 0 to 64255 V | |
| 101 | GENERATOR AVERAGE AC RMS CURRENT | 1 REGISTER (2 BYTES) LONG | READ | Average RMS current measured at the generator output. | 1 A / bit | 0 A | 0 to 64255 V | |
| 111 | GENERATOR PHASE A AC RMS CURRENT | 1 REGISTER (2 BYTES) LONG | READ | RMS current measured at the generator phase A output. | 1 A / bit | 0 A | 0 to 64255 V | |
| 112 | GENERATOR PHASE B AC RMS CURRENT | 1 REGISTER (2 BYTES) LONG | READ | RMS current measured at the generator phase B output. | 1 A / bit | 0 A | 0 to 64255 V | |
| 113 | GENERATOR PHASE C AC RMS CURRENT | 1 REGISTER (2 BYTES) LONG | READ | RMS current measured at the generator phase C output. | 1 A / bit | 0 A | 0 to 64255 V | |
| 103 | GENERATOR OVERALL POWER FACTOR | 1 REGISTER (2 BYTES) LONG | READ | The average power factor of the generator. See APPENDIX A for a programming example. | 1/16384 / bit | -1.0 | -1.0 to 1.0 | |
| 104 | GENERATOR OVERALL POWER FACTOR LAGGING | 1 REGISTER (2 BYTES) LONG | READ | Lead/lag status for generator average power factor. | 00 = Power factor leading | 01 = Power factor lagging | 10 = Error | 11 = Not available |
| 105 | GENERATOR TOTAL PERCENT KW | 1 REGISTER (2 BYTES) LONG | READ | Total real power delivered by the generator, as a percentage of generator rated power. | 0.0078125 % / bit | -251.00% | -251 to 250.99 % | |
| 106 | GENERATOR TOTAL REAL POWER | 2 REGISTERS (4 BYTES) LONG | READ | Total real power delivered by the generator. | 1 W / bit | -2000000000 W | -2000000000 to +2211081215 W | |
| 117 | GENERATOR PHASE A REAL POWER | 2 REGISTERS (4 BYTES) LONG | READ | The real power delivered by phase A of the generator. | 1 W / bit | -2000000000 W | -2000000000 to +2211081215 W | |
| 119 | GENERATOR PHASE B REAL POWER | 2 REGISTERS (4 BYTES) LONG | READ | The real power delivered by phase B of the generator. | 1 W / bit | -2000000000 W | -2000000000 to +2211081215 W | |
| 121 | GENERATOR PHASE C REAL POWER | 2 REGISTERS (4 BYTES) LONG | READ | The real power delivered by phase C of the generator. | 1 W / bit | -2000000000 W | -2000000000 to +2211081215 W | |
| 123 | GENERATOR PHASE A APPARENT POWER | 2 REGISTERS (4 BYTES) LONG | READ | The apparent power delivered by phase A of the generator. | 1 VA / bit | -2000000000 VA | -2000000000 to +2211081215 VA | |
| 125 | GENERATOR PHASE B APPARENT POWER | 2 REGISTERS (4 BYTES) LONG | READ | The apparent power delivered by phase B of the generator. | 1 VA / bit | -2000000000 VA | -2000000000 to +2211081215 VA | |
| 127 | GENERATOR PHASE C APPARENT POWER | 2 REGISTERS (4 BYTES) LONG | READ | The apparent power delivered by phase C of the generator. | 1 VA / bit | -2000000000 VA | -2000000000 to +2211081215 VA | |
| 129 | GENERATOR PHASE A REACTIVE POWER | 2 REGISTERS (4 BYTES) LONG | READ | The reactive power delivered by phase A of the generator. | 1 VAr / bit | -2000000000 VAr | -2000000000 to +2211081215 VAr | |
| 131 | GENERATOR PHASE B REACTIVE POWER | 2 REGISTERS (4 BYTES) LONG | READ | The reactive power delivered by phase B of the generator. | 1 VAr / bit | -2000000000 VAr | -2000000000 to +2211081215 VAr | |
| 133 | GENERATOR PHASE C REACTIVE POWER | 2 REGISTERS (4 BYTES) LONG | READ | The reactive power delivered by phase C of the generator. | 1 VAr / bit | -2000000000 VAr | -2000000000 to +2211081215 VAr | |
| 135 | GENERATOR PHASE A POWER FACTOR | 1 REGISTER (2 BYTES) LONG | READ | The power factor of phase A of the generator. | 1/16384 / bit | -1.0 | -1.0 to 1.0 | |
| 136 | GENERATOR PHASE B POWER FACTOR | 1 REGISTER (2 BYTES) LONG | READ | The power factor of phase B of the generator. | 1/16384 / bit | -1.0 | -1.0 to 1.0 | |
| 137 | GENERATOR PHASE C POWER FACTOR | 1 REGISTER (2 BYTES) LONG | READ | The power factor of phase C of the generator. | 1/16384 / bit | -1.0 | -1.0 to 1.0 | |
| 138 | GENERATOR TOTAL APPARENT POWER | 2 REGISTERS (4 BYTES) LONG | READ | The total apparent power delivered by the generator. | 1 VA / bit | -2000000000 VA | -2000000000 to +2211081215 VA | |
| 140 | GENERATOR TOTAL PERCENT KVA | 1 REGISTER (2 BYTES) LONG | READ | The total apparent power delivered by the generator, as a percentage of generator rated apparent power. | 0.0078125 % / bit | -251.00% | -251 to 250.99 % | |
| 141 | GENERATOR TOTAL REACTIVE POWER | 2 REGISTERS (4 BYTES) LONG | READ | The total reactive power delivered by the generator. | 1 VAr / bit | -2000000000 VAr | -2000000000 to +2211081215 VAr | |
| 143 | GENERATOR TOTAL PERCENT KVAR | 1 REGISTER (2 BYTES) LONG | READ | The total reactive power delivered by the generator, as a percentage of generator rated reactive power. | 0.0078125 % / bit | -251.00% | -251 to 250.99 % | |
| 144 | GENERATOR TOTAL KW HOURS EXPORT | 2 REGISTERS (4 BYTES) LONG | READ | The total kilowatt-hours that have been exported by the generator. | 1 kWh / bit | 0 kWh | 0 to 4211081215 kWh | |
| 146 | GENERATOR TOTAL KVAR HOURS EXPORT | 2 REGISTERS (4 BYTES) LONG | READ | The total kilovar-hours that have been exported by the generator. | 1 kVArh / bit | 0 kVArh | 0 to 4211081215 kVArh | |
| 159 | GENERATOR PHASE A POWER FACTOR LAGGING | 1 REGISTER (2 BYTES) LONG | READ | Lead/lag status for generator phase A power factor. | 00 = Power factor leading | 01 = Power factor lagging | 10 = Error | 11 = Not available |
| 160 | GENERATOR PHASE B POWER FACTOR LAGGING | 1 REGISTER (2 BYTES) LONG | READ | Lead/lag status for generator phase B power factor. | 00 = Power factor leading | 01 = Power factor lagging | 10 = Error | 11 = Not available |
| 161 | GENERATOR PHASE C POWER FACTOR LAGGING | 1 REGISTER (2 BYTES) LONG | READ | Lead/lag status for generator phase C power factor. | 00 = Power factor leading | 01 = Power factor lagging | 10 = Error | 11 = Not available |
| 1057 | DESIRED GENSET OUTPUT VOLTAGE | 1 REGISTER (2 BYTES) LONG | READ | Applies to EMCP 3.3 only. The desired RMS voltage to be delivered by the genset. | 1 V / bit | 0 V | 0 to 64255 V | |
| 1067 | GENERATOR FREQUENCY WITHIN LIMITS | 1 REGISTER (2 BYTES) LONG | READ | Indicates whether the generator frequency is below the threshold for a generator over frequency shutdown and above the threshold for a generator under frequency shutdown. | 00 = FALSE | 01 = TRUE | ||
| 1068 | GENERATOR VOLTAGE WITHIN LIMITS | 1 REGISTER (2 BYTES) LONG | READ | Indicates whether the generator voltage is below the threshold for a generator over voltage shutdown and above the threshold for a generator under voltage shutdown. | 00 = FALSE | 01 = TRUE |