Timing Parameters

Normally a FieldServer sends a poll request to a Server device and that device gives a response back to the FieldServer.

Following are the timing parameters considered important in the fieldserver’s operation:

 

Scan_interval: It is the amount of time between successive poll requests. Its default value is 2 seconds and it belongs to Map descriptors, nodes and connections.

 

Poll_delay:  It is the time between receiving a response from a server device and the next poll request. Its default value is 0.05 seconds and it belongs to Connections only.

 

Timeout: If the FieldServer sends a poll request, and the Server device does not send a response, it is considered a timeout. The time for which the FieldServer waits before declaring a timeout can be adjusted by the timeout parameter. Its default value is 2 seconds and it belongs to Map descriptors, nodes and connections.

 

ic_timeout:  This parameter monitors the time between characters in a response. If the time exceeds the ic_timeout, the response is discarded and is considered a timeout. Its default value is 0.5 seconds and it belongs to Map descriptors, nodes and connections.

 

 

Retries: If a timeout occurs, then the FieldServer will retry the poll request a few more times. Number of times tried is specified by the retries parameter. Its default value is 3 times and belongs to nodes only.

 

Retry_interval: The interval between retries is specified by the retry_interval. The Fieldserver will send poll requests at the end of each retry_interval. Once the specified numbers of retries have been sent, the FieldServer will mark the node offline. Its default value is 10 seconds and belongs to nodes only.

 

Recovery_interval: Once a node has been marked offline, it will wait for a period specified by recovery_interval before sending another poll request. Its default value is 30 seconds and it belongs to nodes only.

 

Probation_delay: Once the communications have been re-established, the FieldServer will wait for a period called probation_delay, before marking the node as online. Its default value is 1 minute and it belongs to nodes only.

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

0 Responses to “Timing Parameters”


  1. No Comments

Leave a Reply



Pages