How often should a BACnet MSTP device search for a new master?

A BACnet MSTP device should search for a new master after it has gotten the token more then Npoll – 1 times.
If your device is on a large network (20+ nodes) and Npoll is set to a very high number it may take a long time for your device to find a new device between its own MAC address and its next station.

For example
There are three devices on the network, 0×02, 0×03, 0×07.
All of the devices have a Npoll of 255, and have received the token 254 times since the start.

0×02 receives the token and increments its own TokenCount to 255. 0×02 now goes in to poll for master mode and attempts to find a new master, the NS (next station) just happens to be the PS (poll station) as well so TokenCount is reset to zero with out a poll for master message being sent out. 0×02 sends the token to 0×03.

0×03 receives the token and increments its own TokenCount to 255. 0×03 now goes in to poll for master mode and attempts to find a new master. It will poll for a new master between the range of 0×04-0×06. If it does not find a new master it will pass the token on to 0×07.

0×07 receives the token and increments its own TokenCount to 255. 0×03 now goes in to poll for master mode and attempts to find a new master. It will poll for a new master between the range of 0×08-Nmax_master then 0×00-0×01. But 0×07 has a Nmax_info_frames of 5 so it will only poll for 5 new master before it will pass on the token to 0×02. Next time 0×07 receives the token it will start to poll for a new master where it last left off at 5 frames a time.

Npoll
The number of tokens received or used before a Poll For Master cycle is executed: Default: 50.

Nmax_master
This parameter represents the value of the Max_Master property of the node’s Device object. The value of Max_Master specifies the highest allowable address for master nodes. The value of Max_Master shall be less than or equal to 127. If Max_Master is not writable in a node, its value shall be 127.

Nmax_info_frames
This parameter represents the value of the Max_Info_Frames property of the node’s Device object. The value of Max_Info_Frames specifies the maximum number of information frames the node may send before it must pass the token. Max_Info_Frames may have different values on different nodes. This may be used to allocate more or less of the available link bandwidth to particular nodes. If Max_Info_Frames is not writable in a node, its value shall be 1.

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

0 Responses to “How often should a BACnet MSTP device search for a new master?”


  1. No Comments

Leave a Reply



Pages