To change the CAS BACnet explorer MSTP MaxMaster.
1) Open the settings file with notepad. The settings file is stored in of two places
C:\Users\<username>\Documents\CAS BACnet Explorer\Settings.xml
C:\Users\<username>\Documents\CAS BACnet Explorer (beta)\Settings.xml
2) Find the iMSTPNmaxMaster value
<key name=”iMSTPNmaxMaster” value=”127“/>
3) Change the value to a number between 1-254. Note: 255 (OxFF) is reserved for broadcasts.
From the BACnet Spec:
This parameter represents the value of the Max_Master property of the node’s Device object. The value of Max_Master specifies the highest allowable address for master nodes. The value of Max_Master shall be less than or equal to 127. If Max_Master is not writable in a node, its value shall be 127.
Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!
Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have
0 Responses to “Chipkin BACnet Explorer set the max master”