<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
		>
<channel>
	<title>Comments on: Changing the BACNet Present Value (Or Why the Present Value doesn’t change)</title>
	<atom:link href="http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change/feed" rel="self" type="application/rss+xml" />
	<link>http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change</link>
	<description>Resources and News for industrial automation</description>
	<lastBuildDate>Mon, 16 Jan 2012 10:29:36 +0000</lastBuildDate>
	<sy:updatePeriod>hourly</sy:updatePeriod>
	<sy:updateFrequency>1</sy:updateFrequency>
	<generator>http://wordpress.org/?v=3.3.1</generator>
	<item>
		<title>By: llucica</title>
		<link>http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change/comment-page-1#comment-1963</link>
		<dc:creator>llucica</dc:creator>
		<pubDate>Fri, 06 Jan 2012 16:05:17 +0000</pubDate>
		<guid isPermaLink="false">http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change#comment-1963</guid>
		<description>Henning and Rick - Thanks for your feedback and compliment. We have updated the diagram!</description>
		<content:encoded><![CDATA[<p>Henning and Rick &#8211; Thanks for your feedback and compliment. We have updated the diagram!</p>
]]></content:encoded>
	</item>
	<item>
		<title>By: Rick Umstattd</title>
		<link>http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change/comment-page-1#comment-1954</link>
		<dc:creator>Rick Umstattd</dc:creator>
		<pubDate>Thu, 15 Dec 2011 15:57:38 +0000</pubDate>
		<guid isPermaLink="false">http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change#comment-1954</guid>
		<description>Henning is correct in that the priority array is backward.

a &#039;1&#039; priority is higher than a &#039;16&#039; priority....

otherwise, thanks for the document - Chipkin is a valuable resource to understanding BACnet networks!</description>
		<content:encoded><![CDATA[<p>Henning is correct in that the priority array is backward.</p>
<p>a &#8217;1&#8242; priority is higher than a &#8217;16&#8242; priority&#8230;.</p>
<p>otherwise, thanks for the document &#8211; Chipkin is a valuable resource to understanding BACnet networks!</p>
]]></content:encoded>
	</item>
	<item>
		<title>By: Henning</title>
		<link>http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change/comment-page-1#comment-1747</link>
		<dc:creator>Henning</dc:creator>
		<pubDate>Thu, 05 Aug 2010 11:46:21 +0000</pubDate>
		<guid isPermaLink="false">http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change#comment-1747</guid>
		<description>In the first figure the priority array should go from highest to lowest, not from highest to highest.
It&#039;s explained well in the text, just the word in the diagram is wrong.

Thanks for this site!</description>
		<content:encoded><![CDATA[<p>In the first figure the priority array should go from highest to lowest, not from highest to highest.<br />
It&#8217;s explained well in the text, just the word in the diagram is wrong.</p>
<p>Thanks for this site!</p>
]]></content:encoded>
	</item>
	<item>
		<title>By: pchipkin</title>
		<link>http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change/comment-page-1#comment-105</link>
		<dc:creator>pchipkin</dc:creator>
		<pubDate>Thu, 20 Mar 2008 14:57:28 +0000</pubDate>
		<guid isPermaLink="false">http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change#comment-105</guid>
		<description>&lt;p&gt;The Bacnet specification doesnt require a Bacnet device to track the souce of commands. It says that such an implementation would be a vendors own decision.&lt;/p&gt;
&lt;p&gt;During our support work for many customers with many systems we have not seen a situation where someone produced such information so we assume that no one has implemented it.&lt;/p&gt;
&lt;p&gt;We have a software tool, which is provided with the CAS Bacnet explorer - Call the CAS BACnet Watchdog that monitors traffice aimed at a particualr device or object and keep a record of time and source and command. Contact us for details.&lt;/p&gt;
</description>
		<content:encoded><![CDATA[<p>The Bacnet specification doesnt require a Bacnet device to track the souce of commands. It says that such an implementation would be a vendors own decision.</p>
<p>During our support work for many customers with many systems we have not seen a situation where someone produced such information so we assume that no one has implemented it.</p>
<p>We have a software tool, which is provided with the CAS Bacnet explorer &#8211; Call the CAS BACnet Watchdog that monitors traffice aimed at a particualr device or object and keep a record of time and source and command. Contact us for details.</p>
]]></content:encoded>
	</item>
	<item>
		<title>By: Sean M.</title>
		<link>http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change/comment-page-1#comment-102</link>
		<dc:creator>Sean M.</dc:creator>
		<pubDate>Thu, 20 Mar 2008 02:26:11 +0000</pubDate>
		<guid isPermaLink="false">http://www.chipkin.com/articles/changing-the-bacnet-present-value-or-why-the-present-value-doesn%e2%80%99t-change#comment-102</guid>
		<description>Does the device track the source of the commands. I mean - is there a corresponding array that get filled in with the device instance ID or something like that eadh time a priority is commanded ? How do you know who commanded/wrote ?</description>
		<content:encoded><![CDATA[<p>Does the device track the source of the commands. I mean &#8211; is there a corresponding array that get filled in with the device instance ID or something like that eadh time a priority is commanded ? How do you know who commanded/wrote ?</p>