CAS BACnet Explorer – What data type do I use to write to a binary output.

Normally a binary output will uses a BACnetBinaryPV(ENUMERATED) data type for the present value. The enumeration has one of two values 0=inactive, and 1=active.


BACnetBinaryPV ::= ENUMERATED {
inactive (0),
active (1)
}

In the CAS BACnet Explorer you will set the data type to “ENUMERATED” and the data value to either “0″ or “1″.

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

0 Responses to “CAS BACnet Explorer – What data type do I use to write to a binary output.”


  1. No Comments

Pages