The BACnet spec defined the media for MSTP as follows (2004) ;
“An MS/TP EIA-485 network shall use shielded, twisted-pair cable with characteristic impedance between 100 and 130 ohms. Distributed capacitance between conductors shall be less than 100 pF per meter (30 pF per foot). Distributed capacitance between conductors and shield shall be less that 200 pF per meter (60 pF per foot). Foil or braided shields are acceptable. The maximum recommended length of an MS/TP segment is 1200 meters (4000 feet) with AWG 18 (0.82 mm2 conductor area) cable. The use of greater distances and/or different wire gauges shall comply with the electrical specifications of EIA-485.”
Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!
Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have
0 Responses to “Cable Specifications for RS485 Networks - BACnet MSTP”