BACnet MSTP (RS485), Cable selection does make a difference.

All cables offer impedance (resistance). Some cables are designed so that the impedance is relatively independent of distance. You want one of these cables. A clue to knowing if you selected one is to look at the cable’s Nominal Impedance. If they quote a number such a 100Ohms you have a good cable. If they quote an impedance per meter/foot you have chosen the wrong kind. Wrong in the sense – to determine the value of terminating resistors now requires measurements and calculations. Choose low capacitance cables.

Can you use Cat5 cable ? Yes. Use one pair for Tx,Rx and a conductor from another pair for the ground reference signal.

We recommend these two cables.

Belden 3106A

Belden 3106A - RS485 Cable 

Multi-Conductor – EIA Industrial RS-485 PLTC/CM
22 AWG stranded (7×30) tinned copper conductors, Datalene® insulation, twisted pairs, overall Beldfoil® shield (100% coverage) plus a tinned copper braid (90% coverage), drain wire, UV resistant PVC jacket. 
 

Belden 3107A

Belden 3107A - RS485 Cable 

Multi-Conductor – EIA Industrial RS-485 PLTC/CM
22 AWG stranded (7×30) tinned copper conductors, Datalene® insulation, twisted pairs, overall Beldfoil® shield (100% coverage) plus a tinned copper braid (90% coverage), drain wire, UV resistant PVC jacket.

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

1 Response to “BACnet MSTP (RS485), Cable selection does make a difference.”


  1. 1 Avi Cohen Feb 16th, 2010 at 11:41 pm

    Hi, I wonder dose a 120 +/- Ohm,PF/M@1Khz& 1.5PF/M @ 1Khz will be ok for BACnet Ms/Tp communication line?
    Regards,
    Avi

Leave a Reply