The BACnet standard describes two types of Life Safety objects. The two types of these objects include:
- Life Safety Point Object Type
- Life Safety Zone Object Type
The Life Safety Point object type is defined by the standard as those objects related to fire, safety, and security applications. The condition of this object type is determined by the following two factors:
- Mode
- State
The object mode is usually under the control of the device operator. The object state indicates the controller condition depending on the internal logic of the device.
Life Safety Point object applications can include the following automation related devices:
- Automatic Fire Detectors
- Sirens
- Pull Stations
The following table will present the properties and related datatypes of the Life Safety Point object from the BACnet standard:
| Property | Datatype |
| Object_Identifier | BACnet Object Identifier |
| Object_Name | Character String |
| Object_Type | BACnet Object Type |
| Present_Value | BACnet Life Safety State |
| Tracking_Value_ | BACnet Life Safety State |
| Description | Character String |
| Device_Type | Character String |
| Status_Flags | BACnet Status Flags |
| Event_State | BACnet Event State |
| Reliability | BACnet Reliability |
| Out_of_Service | Boolean |
| Mode | BACnet Life Safety Mode |
| Accepted_Modes | List of BACnet Life Safety Mode |
| Time_Delay | Unsigned |
| Notification_Class | Unsigned |
| Life_Safety_Alarm_Values | List of BACnet Life Safety State |
| Alarm_Values | List of BACnet Life Safety State |
| Fault_Values | List of BACnet Life Safety State |
| Event_Enable | BACnet Event Transition Bits |
| Acked_Transitions | BACnet Event Transition Bits |
| Notify_Type | BACnet Notify Type |
| Event_Time_Stamps | BACnet Array (3) of BACnet Time Stamp |
| Silenced | BACnet Silenced State |
| Operation_Expected | BACnet Life Safety Operation |
| Maintenance_Required | BACnet Maintenance |
| Setting | Unsigned |
| Direct_Reading | Real |
| Units | BACnet Engineering Units |
| Member_Of | List of BACnet Device Object Reference |
| Profile_Name | Character String |
The Life Safety Zone object type has similar conditional and property qualities as the Life Safety Point object type, but the focus is concentrated on a group of Life Safety Point and Zone objects.
The following table will present the properties and related datatypes of the Life Safety Zone object from the BACnet standard:
| Property | Datatype |
| Object_Identifier | BACnet Object Identifier |
| Object_Name | Character String |
| Object_Type | BACnet Object Type |
| Present_Value | BACnet Life Safety State |
| Tracking_Value | BACnet Life Safety State |
| Description | Character String |
| Device_Type | Character String |
| Status_Flags | BACnet Status Flags |
| Event_State | BACnet Event State |
| Reliability | BACnet Reliability |
| Out_of_Service | Boolean |
| Mode | BACnet Life Safety Mode |
| Accepted_Modes | List of BACnet Life Safety Mode |
| Time_Delay | Unsigned |
| Notification_Class | Unsigned |
| Life_Safety_Alarm_Values | List of BACnet Life Safety State |
| Alarm_Values | List of BACnet Life Safety State |
| Fault_Values | List of BACnet Life Safety State |
| Event_Enable | BACnet Event Transition Bits |
| Acked_Transitions | BACnet Event Transition Bits |
| Notify_Type | BACnet Notify Type |
| Event_Time_Stamps | BACnet Array (3) of BACnet Time Stamp |
| Silenced | BACnet Silenced State |
| Operation_Expected | BACnet Life Safety Operation |
| Maintenance_Required | Boolean |
| Zone_Members | List of BACnet Device Object Reference |
| Member_Of | List of BACnet Device Object Reference |
| Profile_Name | Character String |
The developer should pay attention to the Mode and State qualities of both Life Safety object types.
The following structure example from the standard will examine both Life Safety object types from actual automation applications. Specifically, the Point object will focus on a building smoke detector. The Zone object will examine the fire zone within a building.
Life Safety Point Object Example:
Property: Object_Identifier = (Life Safety Point, Instance 2)
Property: Object_Name = “SMK3W”
Property: Object_Type = LIFE_SAFETY_POINT
Property: Present_Value = PREALARM
Property: Tracking_Value = PREALARM
Property: Description = “Floor 3, West Zone Smoke Detector”
Property: Device_Type = “Old Smokey model 123″
Property: Status_Flags = {TRUE, FALSE, FALSE, FALSE}
Property: Event_State = LIFE_SAFETY_ALARM
Property: Reliability = NO_FAULT_DETECTED
Property: Out_Of_Service = FALSE
Property: Mode = ON
Property: Accepted_Modes = {ENABLED, DISABLED, TEST}
Property: Time_Delay = 10
Property: Notification_Class = 39
Property: Life_Safety_Alarm_Values = (ALARM)
Property: Alarm_Values = (PREALARM)
Property: Fault_Values = (FAULT)
Property: Event_Enable = {TRUE, TRUE, TRUE}
Property: Acked_Transitions = {TRUE, TRUE, TRUE}
Property: Notify_Type = ALARM
Property: Event_Time_Stamps = ((23-MAR-95, 18:50:21.2), (*-*-*, *:*:*.*),(23-MAR-95, 19:01:34.0))
Property: Silenced = SILENCE_AUDIBLE
Property: Operation_Expected = RESET_ALARM
Property: Maintenance_Required = NONE
Property: Setting = 50
Property: Direct_Reading = 84.3
Property: Units = PERCENT-OBSCURATION-PER-METER
Property: Member_Of = ((Life Safety Zone, Instance 5))
Life Safety Zone Object Example:
Property: Object_Identifier = (Life Safety Zone, Instance 2)
Property: Object_Name = “SMK3″
Property: Object_Type = LIFE_SAFETY_ZONE
Property: Present_Value = PREALARM
Property: Tracking_Value = PREALARM
Property: Description = “Floor 3 Smoke”
Property: Status_Flags = {TRUE FALSE, FALSE, FALSE}
Property: Event_State = LIFE_SAFETY_ALARM
Property: Reliability = NO_FAULT_DETECTED
Property: Out_Of_Service = FALSE
Property: Mode = ON
Property: Accepted_Modes = {ENABLED, DISABLED, TEST}
Property: Time_Delay = 10
Property: Notification_Class = 39
Property: Life_Safety_Alarm_Values = (ALARM)
Property: Alarm_Values = (PREALARM)
Property: Fault_Values = (FAULT)
Property: Event_Enable = {TRUE, TRUE, TRUE}
Property: Acked_Transitions = {TRUE, TRUE, TRUE}
Property: Notify_Type = ALARM
Property: Event_Time_Stamps = ((23-MAR-95, 18:50:21.2), (*-*-*, *:*:*.*),(23-MAR-95,19:01:34.0))
Property: Silenced = UNSILENCED
Property: Operation_Expected = SILENCE_AUDIBLE
Property: Maintenance_Required = NONE
Property: Zone_Members = ((Life Safety Point, Instance 22),(Life Safety Point, Instance 23))
Property: Member_Of = ((Life Safety Zone, Instance 5))
Written by: Scott Cosby
© Chipkin Automation Systems 2007
Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!
Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have
Can you provide simulator for BAC Net Object type for testing purpose? Ideal requirement could be around 2000-10000 data points with most of the object type (including life safety point).
Your immediate support will be highly appreciated..
Thanks & Regards,
DB