CAS BACnet Explorer – What data type do I use to write to a binary output.

Normally a binary output will uses a BACnetBinaryPV(ENUMERATED) data type for the present value. The enumeration has one of two values 0=inactive, and 1=active.


BACnetBinaryPV ::= ENUMERATED {
inactive (0),
active (1)
}

In the CAS BACnet Explorer you will set the data type to “ENUMERATED” and the data value to either “0″ or “1″.