Archive for August, 2008

Visual Slick Backup option

The Backup options tab can be found under tools->Configuration->File options, select Backup tab. You need to check “Make Backup files” to enable the backup option. Visual Slick will then make a backup of every file the first time used in a given edit session. With this option enabled you can select different backup directories options:

  • Global directory – Backup files are placed in a single directory (You can specify the directory)
  • Same directory as *.BAK – placed in same directory as backup file but their extension changed to “.bak”
  • Global nested directory – uses the directory and path name of destination file
  • Use child directory – placed in same directory as destination file

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

DNP3 Class Data

The DNP3 protocol is organized in data types or object group as well as class data. Some of the object groups are as follows:

  • Binary inputs
  • Binary outputs
  • Analog inputs
  • Analog outputs
  • Counters
  • Time and date
  • File transfer objects, etc.

Each object group can contain one or more data points. A data point is a single data value of a specific object group. Every object groups also contains data variations. These variations are there to indicate the different methods of specifying data within an object group. For example, the variation of analog input data allows for 16-bit signed integer values, 32-bit signed integer values or even 32-bit floating point values.

In the DNP3 protocol object groups and the data points within them are further organized into Class data. This provides a more efficient way of requesting data. Four classes are defined in DNP3. Class 0 represents all the static data of unchanged event data. Class 1, 2 and 3 on the other hand represent different priorities of change event data. This allows the user to poll more frequently for higher priority changed data more often without using a lot of bandwidth. This is because the class data response only returns the class data that changed since the last poll, keeping the response message small and efficient.

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

FieldServer Modbus TCP – Device / Station Address (ID) 0 (Zero)

Many Modbus TCP clients send polls with the Station / Device address (ID) set to zero.

Fieldserver’s cannot be configured as station zero so they cannot respond. There is a work around. Set the FieldServer Node_ID parameter to a value of 239. When Modbus TCP messages are received, the FieldServer looks at the one byte station number. If it is zero it changes the byte to 239 and then passes the message for processing by the driver. Thus if the server node is configured as 239 the FieldServer can respond correctly.

One example of a Modbus Client that sends requests to station zero is the EZ Touch Panel HMI from EZAutomation.net

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have

BACnet MSTP Installation, RS485 and Cables

BACnet MSTP uses RS485 (also known as EIA485) as it physical layer. This is good and bad.

Search the Internet on RS485 you will find Bob Perrins’s article called the “THE ART AND SCIENCE OF RS-485.” It is his reference to Art that makes RS485 bad. What he means is that RS485 is often non-trivial and getting a network working can rely more on experience and experimentation.

Here is our simplified advice:

1. RS485 is a 3 conductor network. You take a huge risk by not installing the 3rd conductor. You risk blowing 485 ports, you risk unstable operation (works sometimes and doesn’t work other times) and finally you risk re-installation. For a more detailed discussion read this article. The more power sources used to power devices, the greater the physical separation of devices, the less well grounded devices and power sources are the greater the risk. Remember this statement : The so called Ground Terminal on a RS485 interface is not a connection to ground. It is a common reference signal. The voltage level on the Tx/Rx conductors are measured relative to this voltage level.

You can (if you must) use a shield drain wire as the 3rd conductor (ground reference conductor)

2. Always connect the ground reference conductor first if you are connecting a device that is powered up or you are connecting your laptop an operating network.

OR

Always choose devices that have optical isolation – this almost always will protect the RS485 transmitter/receivers.

3. You can get away without the shield. The twisted pair used for Tx and Rx is more effective at noise cancellation than the shield.

4. Take care where you run your cables. It seems obvious not to wind your cable around other cables or sources of electricity/magnetism. People are often surprised to find that the worst source of induced noise are switching DC loads. Another big culprit are Variable Frequency drives.

5. Cable selection does make a difference.

All cables offer impedance (resistance). Some cables are designed so that the impedance is relatively independent of distance. You want one of these cables. A clue to knowing if you selected one is to look at the cable’s Nominal Impedance. If they quote a number such a 100Ohms you have a good cable. If they quote an impedance per meter/foot you have chosen the wrong kind. Wrong in the sense – to determine the value of terminating resistors now requires measurements and calculations. Choose low capacitance cables.

Can you use Cat5 cable ? Yes. Use one pair for Tx,Rx and a conductor from another pair for the ground reference signal.

We recommend these two cables.

Belden 3106A

Multi-Conductor – EIA Industrial RS-485 PLTC/CM
22 AWG stranded (7×30) tinned copper conductors, Datalene® insulation, twisted pairs, overall Beldfoil® shield (100% coverage) plus a tinned copper braid (90% coverage), drain wire, UV resistant PVC jacket.

Belden 3107A

Multi-Conductor – EIA Industrial RS-485 PLTC/CM
22 AWG stranded (7×30) tinned copper conductors, Datalene® insulation, twisted pairs, overall Beldfoil® shield (100% coverage) plus a tinned copper braid (90% coverage), drain wire, UV resistant PVC jacket.

6. How do you put more than 32 devices on a single RS485 trunk ?

The simple answer is use a repeater but in practice one isn’t always necessary.

The RS485 stardard is based on 32 devices. Since the standard was developed most RS485 chips present less than the full unit load originally specified. Today you get half and quarter load devices. Thus to see how many devices you can install you simply get the data sheets and add the loads. Look for “UL” on the data sheet. It stands for Unit Load.

7. Cable Lengths and Baud Rates

Practically speaking you can go up to 4000 feet at baud rates up to 76800 baud. Above that you need to do a little math and reduce the length. For example, at 115k baud your cable should not be much longer than 2500 feet.

However, the higher the baud rate the more sensitive the cable is to the quality of installation – issues like how much twisted pair is unwound at each termination start to become very very important.

Our advise: For longer networks with lots of devices, choose 38k400 baud over 76k800 baud and optimize using COV, separate networks and by setting the Max Master to a lower number.


Source: Ten Ways to Bulletproof RS-485 Interfaces National Semiconductor
Application Note 1057 John Goldie October 1996

8. How many devices to install on a single RS485 Trunk (Bandwidth Issues)

How many devices to install on a single RS485 Trunk (Bandwidth Issues)

There are non electrical considerations to determine how many devices you put on an MSTP network.

The chart below illustrates (from one installation) how little of the bandwidth is used to transfer data. The APDU’s are application layer message that poll and respond with property values – they do work for us as data consumers. The rest is used to maintain the network – passing the token around and looking for new devices.

It’s not possible to provide a calculator to work out how many devices to install on a single network but the following list provides some help in assessing bandwidth considerations.

  • How many of the devices will be BACnet slaves.

    Token passing and looking for new devices on the MSTP trunk consumes a fair amount of bandwidth.

    A BACnet slave can be read/written but never gets the token. So it can’t initiate any messages because it never gets the token. The more slaves the fewer token passes. Typically you are not able to put a device in slave mode. Most vendors implement their devices as masters (ie token passing devices).

  • How many Objects in each device are you interested in monitoring?

    The more you read and the greater the frequency the more bandwidth that will be consumed.

    It takes approx 30 bytes to poll for a single property. It takes about 40 bytes to reply. A token is 8 bytes as is a Poll for master.
    Assume that 50% of your bandwidth will be used by overhead (token, poll for master).
    Divide the baud rate by 10 to get bytes per seconds.
    Using a number like 30+40=70 as a best case and 100 as a worst case (obviously reading descriptions will take more) multiply by the number of objects and properties you are going to poll on a regular basis.

    Here are some typical numbers assuming the device doesn’t support the ‘multiple’ services (see below).

    Baud 38400
    Bytes per sec (divide Baud by 10) 3840
    Overhead use (token and poll for master) 50%
    Byte per sec for payload (a) 1920
    Typical Poll and response for a single property (b) 70
    Number of properties that can be polled per sec (=a/b) 27.42857
    Typical number of props that will polled per object 4
    (pres value, status_flags, reliability, out of service)
    Number of objects per sec 6.857143
  • How many properties from each of these objects?
  • What is the baud rate?
  • What is Max Master Set to?

    Every few cycles each (master) token passing device on the network must look to see if there are new devices. Max Master determines the biggest address that must be searched for. Each search involves sending a message and waiting for a response or a timeout (if the devices isn’t there). Timeouts cost time. The higher the number of Max Master (default is 127) the more potential devices must be searched for. If you use Max master to improve bandwidth then you must adjust it in each device.

  • Do the devices support the “Read/Write Property Multiple” services or must each property be read in a separate message.

    Find the answer to this question by reading the BIBs statement for each device or you could explore the device object of the device, find the property called BACnetServicesSupported and then look at the 14th item in the array to see if Read Property Multiple is supported and the 16th for Write Property Multiple. However, we have found that a large number of devices don’t display this information.

    Obviously, if you can read a chunk of properties in one message you will be better off than if you can only read a single one.

  • Can you use BACNet’s COV mechanism.

    COV stands for Change of Value. When a device supports COV another device / application can subscribe to receive notifications when an object property changes. This means the data client doesn’t have to poll for data continuously but can wait passively to be notified of the change. This reduces the number of messages on a network dramatically.

  • Some devices are slower than others.

    BACnet allows up to 15 msec for a device to use the token. Since most messages on a MSTP network are token passes a device that uses the token in 5 msec will consume much less bandwidth than one that takes 15msec. (A number of vendors relax this requirement to allow for other vendors implementations. The more relaxed the more bandwidth is consumed doing nothing.)

9. What can go wrong with 485 ?

Lets say you adopted all the best practices for installation of the network but you get intermittent or unacceptable performance because of packet loss, noise, collisions … Then you should consider hiring an expert to resolve your problems because now you are in the ‘Art’ part of RS485. These are some of the things they will look at.

  • Reflections

    Without a scope and expertise you wont know this is a factor. Its easy and cheap to eliminate. Look at the cable spec. Find the nominal impedance. Buy two resistors of the same value. At each end of the trunk install the resistors between the Tx and Rx terminals. If you don’t have obvious ends of the trunk (because you created a star) then we recommend re-cabling to form a linear trunk or we wish you luck.

    Some devices have terminating resistors built into them. If the vendor did a poor job, the default is to have the resistor active and they must be disabled unless they are the terminating devices on the network. Read vendor docs.

  • Biasing, Idle State Biasing, Fail Safe Biasing, Anti Aliasing

    There are a whole string of terms uses as synonyms to describe this phenomenon.

    To use two wires ( as opposed to full duplex 4 wire) for RS485 each devices transmitter and receiver must be set to an idle state to release the line for others use. Releasing the line means allowing it to ‘float’. It must not be allowed to float at any voltage level so devices have pull up/down resistors to pull the line to an allowable ‘floating’ voltage. (the floating state is also known as the tri-state. ) The load presented by other devices on the network affects this floating so the resistor values may need to be changed depending on the number of devices installed and the values of the pull up/down resistors they are using. (You can imagine how tricky its going to be to resolve this). If a device floats out of the specified range then to other devices it will look like the floating devices isn’t floating at all. The other devices will think that it is transmitting or receiving and thus blocking the line.

    The simplest way of knowing if this is a factor – Does the device work properly when it is the only device on the network ?. When you install it in the full network other devices or this device stops working properly. This device and/or the pull up/down resistors of other devices are candidates for investigation.

    A number of vendors have a range of pull up/down resistors installed and allow you to change the selection using software or jumpers.

  • Line Drive On / Off

    To use two wires for RS485 each devices transmitter and receiver must be set to an idle state to release the line for others use. When a device wants to send it must grab the line. When it has finished sending it must release the line. You can see there are potential problems here. What happens if one device waits too long after sending its last bit before releasing the line – its possible that the other devices will miss some bits of data.

10. Take care with the topology. The best topology is a single trunk that in-outs on the terminal blocks of each device it connects. What do we mean by best ? We mean the choice which is least likely to cause problems.

Best arrangement. (Showing TX conductor for reference only)

Getting worse. Making the connections to the RS485 terminals, drops instead of connections starts to give the electrical signals all kinds of complicated paths for reflections and harmonics. Its obvious that if the drops are long and are not twisted then you also have more chance to induce noise. (Showing TX conductor for reference only)

Worst. Avoid Star configurations. They are so much harder to debug when it gets tricky. (Showing TX conductor for reference only)

Did you like this post?

Subscribe To The RSS Feed!
To catch many more articles like this in the future, make it easy on yourself and subscribe to me via RSS. You will not regret it!

Do you have a question?
We will do our best to try and solve any building automation, protocol, integration problem you may have



Pages